Installation (continued): 

Installation heat calculator 

Sontay recommends mounting the calculator on the wall. Do not mount the device at the pipe or attach it directly on the flow sensor. 
 
The mounting adapter at the backside of the calculator can be used for DIN-rail mounting or “reverse” for wall mounting. 
 
For wall mounting attach the adapter with at least two screws to the wall and clip the calculator on it. 
 
For rail mounting lift the adapter a little bit, place the calculator on the rail and push the adapter back until it locks. 
  
  
  
  
 
  
  

DIN-rail 

mounting 

   Wall 

mounting 

Connection sensors 

The mounting of the temperature sensors should be done symmetrical with direct immersion. If immersion sleeves are used they have 
to be checked for conformity to MID and have to be marked accordingly. The installation of immersion sleeves has to be done 
according to DIN EN 1434-2. 
  

 

The sensor cables are marked with colours (red = supply, blue = return). Do not buckle, extend or shorten the wire. 

 

Do only use paired sensors with the same serial number on it. 

 

 

 

 

 

 

 

 

Supply and return sensors must be inserted into the immersion sleeves completely.   

 

 

 

 

Installation points in the flow sensor can be used for symmetrical installation of the temperature sensors. 

 

 

 

Seal temperature sensor after installation to prevent unauthorized demounting (seals included). 

 

 

 

Do not wrap or install wires along hot pipes. 

 

Connection flow sensor 

The total length of the wire between flow sensor and calculator should not exceed 10m. Mind the polarity at electronic flow sensors. 
  

Operation test 

Check the calculator for any error codes in the display after installation (see Page 5 for error codes). Most of the errors can be deleted 
by pressing the button. 
If the error appears permanently, it will be detected at the next measuring cycle and displayed again. Check whether the volume 
information is updated and the displayed temperatures correspond to the present ones while the system is running (measuring cycle 2 
minutes max.). 
When attaching the top cover on the housing pulses on the inputs can possibly be generated. Check readings of the inputs and correct 
if necessary. 
  

Sealing 

Seal the device with the included seals to prevent unauthorized opening. 
  

Maintenance 

Repairs or overhaul are only allowed by the manufacturer or companies authorized by the manufacturer. 

 

 

Pocket Selection  

When selecting pockets you should always try and install the pocket so that the tip is in the centre of the flow.  
  
A good guide on what pocket length to select is; 
  

45mm Pockets  

 

 

105mm Pockets    

 

140mm Pockets 

Flow sensors   

DN15 to DN40mm 

 

DN50 to DN80mm 

 

DN100mm to DN200mm 

  

Summary of Contents for MW-MD

Page 1: ...ystems They are for use with mechanical flow parts With its dynamic measuring cycle even the smallest energy consumptions are reliably collected The large multifunction display permanently shows the h...

Page 2: ...ction IP54 The MW MD range of heat meter integrators the default location of installation of the flow sensor is in the return It can be programmed for the meter to be installed in the flow but this mu...

Page 3: ...he device is maintenance free during the service life Repairs can only be made by the manufacturer Declaration of Conformity Sontay Ltd declares that this product with the number of the EC type examin...

Page 4: ...ely Installation points in the flow sensor can be used for symmetrical installation of the temperature sensors Seal temperature sensor after installation to prevent unauthorized demounting seals inclu...

Page 5: ...and outgoing of the M Bus wires L1 24 L2 25 The symbols in the table below show the meter s operational status The status messages only appear in the main display energy The temporary display of the...

Page 6: ...perature difference Flow Maximum flow Instantaneous power Pulse value counter 1 Pulse value counter 2 Energy at SRD Date SRD SRD value external counter 1 SRD value external counter 2 Monthly values in...

Page 7: ...ergy 1st monthly value input 1 1st monthly value input 2 Sensor type installation point Pulse value Basic configuration Model number Date battery end Time Datum M Bus address Baud rate Input display E...

Reviews: