Sontay GL-CO-RFG361 Quick Start Manual Download Page 3

Page 3 of 4 

UK Sales Tel: 0845 345 7253 

International Tel: +44 1732 861225 

GL-CO-RFG361 

Issue: 5.5 

Date Of Issue: 28/10/2008 

© 2008 Sontay Limited. All rights reserved. 

Alarm Levels (continued) 

Self Diagnostics 

 

The alarm threshold for Natural Gas is about 16% of the 
LEL. This is below the limit set by the manufacturing stan-
dards (20% LEL). The pre-alarm threshold is about 66.6% 
of the alarm threshold. Using the SENSITIVITY pot the 
thresholds can be adjusted within the limits established the 
manufacturing standards. Turning the pot t in-
creases the sensitivity and turning towards - decreases the 
sensitivity. 
 

Sensor location 

 
Natural gas 

 

100 to 500mm from the ceiling    

LPG 

 

 

100  to  500mm  from  the  floor          

CO 

 

 

1.5 to 2m from the floor 

 
It is advisable to position sensors at a certain distance from 
gas appliances, so as to avoid nuisance triggering. 
 
Boilers & DHW   

1 to 2 meters   

 

              

Gas cookers 

 

2 to 3 meters 

 

Cable Types 

 
Power & relay   

1.5mm²   

 

 

 

Sensor up to 40m 

1.5mm²   

 

 

 

Sensor up to 60m 

2.5mm² 

 

Operation 

 
When the controller is switched on it remains inactive for 1.5 
to 2 minutes with the FAULT and ALARM LEDs flashing, to 
allow the sensor to stabilise. 
 
When the gas concentration exceeds the pre-alarm thresh-
old the ALARM LED blinks. 
 
When the gas concentration exceeds the alarm threshold, 
after a delay of about 20 seconds: 
 

• 

The  internal buzzer will sound (if enabled) 

• 

The ALARM LED switches ON 

• 

Activates the operational control 

 
 
 
 
 
 
 

In the event of a fault or incorrect connection of the sensor 
the following LED states will occur: 

Commissioning 

 
1.  Apply power to controller - POWER LED lights. 

 

 

2.  Wait 2 minutes for sensor to stabilise. 

 

 

 

3.  Set SENSITIVITY pot to ‘0’   

 

 

 

 

4.  Simulate presence of gas (gas from a lighter should 

work). 

 

 

 

 

 

 

 

5.  When the alarm threshold is reached, after a 20 second 

delay the ALARM LED will light, the buzzer will sound (if 
enabled) and the relay operate. 

 

 

 

 

6.  Stop gas simulation. When the concentration falls below 

the alarm threshold:  

 

 

 

                                                                

Without latching alarm - buzzer ceases, ALARM LED 
blinks slowly    

 

 

 

 

                                                   

With latching alarm - buzzer continues until RESET button 
is pressed for at least 5 seconds. 
 

Gas Shut Off Valve 

 
This must be installed on the gas feed pipe, possibly outside 
the space controlled, in a place which is easily accessible 
and is protected from bad weather. 
NB  In LPG installations the valve must be installed down-
stream of the pressure reducing valve. 

Type of Fault

Fault LED Alarm LED

Sensor self-heating element broken ON

OFF

No connection to terminal G

ON

OFF

No connection to terminal B

ON

OFF

No connection to terminal M

OFF

ON

Connections G & B reversed

ON

OFF

Connections G & M reversed

OFF

ON

Connections B & M reversed

OFF

ON

Reviews: