GL

-

CO

-

RFG

-

65x

 

1, 2 or 3

-

Channel Gas Leak Alarm Systems

 

Issue Number 7.1

 

27/08/2021

 

Four Elms Road 

-

 Edenbridge

 

Kent 

-

 TN8 6AB 

-

 UK

 

Page 3 of  5

 

Installation

 

 

1.The GL

-

CO

-

RFG65x should only be installed by a competent, suitably trained technician, experienced in installation with hazardous voltages. 

(>50Vac & <1000Vac or >75Vdc & 1500Vdc)

 

 

2.

 

Ensure that all power is disconnected before carrying out any work on the GL

-

CO

-

RFG365x. Maximum cable is 2.5mm², care must be 

 

taken not to over tighten terminals.

 

 

3.Separate the base from the cover, if DIN rail mounting clip onto the DIN rail.

 

 

4.

 

Make connections as required using the following cables:

 

 

1.5 mm² cross

-

section for power and relay control outputs,

 

 

1 mm² cross

-

section for sensors positioned up to a maximum distance of 50 meters; or 

 

 

1.5 mm² cross

-

section for sensors positioned up to a maximum distance of 75 meters. 

 

 

5.NB It is advised that no more than 2 cables be inserted into a single terminal. Use external junction boxes if necessary.

 

 

6.

 

Select the 

link functions

” 

to adapt the detector to the desired type of operational control the replace the cover on the base using the 4 

 

screws provided, if panel mounting fix to panel door, using the panel mounting kit (panel cut out 138 x 138 ±0.5%).

 

 

Fascia & Wiring      

 

 

 

 

 

 

 

 

 

 

Example:

 

 

 

 

       

Example:

 

 

 

1

 

Sensitivity potentiometer

 

 

2

 

Power supply LED

 

 

3

 

Fault LED(s)

 

 

4

 

Alarm LED(s)

   

 

 

5

 

Reset button

 

 

Links

 

 

Warning, when changing link functions ensure all power is disconnected first. 

 

 

Link Functions:

 

-

 F1

   

 

 

 

 

 

 

 

F3 

-

 F4

 

No link

 

Internal buzzer enabled

  

 

 

 

 

No link

 

Relay with latching alarm

 

Linked

 

Internal buzzer disabled

 

 

 

 

 

Linked

 

Relay with non

-

latching alarm

 

 

F2 

-

 F3

 

No link

 

Relay normally energised when no gas present

  

 

B2 

-

 H2

 

 

Linked

 

Relay normally de

-

energised when no gas present

 

 

linked

 

B2 sensor not connected

 

 

B3 

-

 H3

 

Linked

 

B3 sensor not connected

 

 

Operational relay output (when in alarm):

 

No link 

 

F2 

-

 F3

 

1

-

3 opens, 2

-

3 closes  

   

4

-

6 opens, 5

-

6 closes  

 

Linked

 

F2 

-

 F3

 

1

-

3 closes 2

-

3 opens

   

4

-

6 closes, 5

-

6 opens

 

 

Latching alarm & reset:

 

F3 

-

 F4

 linked:

 

Alarm ceases when the gas concentration falls below the threshold level and the ALARM LED blinks slowly. Press the RESET button to clear 
the LED status.

 

 

 

F3 

-

 F4

 unlinked:

 

Alarm continues even when the gas concentration falls below the threshold level. To deactivate press the RESET button for at least 5 seconds.

 