Operation manual
Page 13 of 37
Safety
Protection class
I / PE conductor
Overvoltage category
III
Degree of protection
IP 56
Rated short-withstand current (ICW)
1.5 kA
Ambient conditions
Environment
Outdoor
Storage temperature range
0 °C ... 40 °C
Transport temperature range
-15 °C ... 50 °C
Max. rel. humidity
90 %, non-condensing
Permissible installation altitude
2,000 m above sea level
Pollution degree
3
Backup specification
Nominal backup current (Continuous)
22 A
Nominal output voltage
230 V
Nominal power
5000 W
Nominal frequency
50 Hz
Max backup power (Max 30mins)
5300 VA
Max backup power (Max 60s)
7050 VA
Max backup power (Max 300ms)
7600 VA
Maximum compatible PV inverter
6kW
Certifications
Grid connections
AS/NZS 4777.2:2020
EMC / EMI protection
EN 61000-6-1, EN 61000-6-3, IEC 62040-2
Safety
IEC 62040-1, IEC 62477-1, IEC 62619, IEC
62109-1, IEC 62109-2
Additional ambient conditions:
-
The installation location must not be at risk of flooding.
-
Installation room should be ventilated.
-
The currently applicable building codes must be observed.
-
Even floor, suitable for heavy loads.
-
Observe fire control standards.
-
Free from corrosive and explosive gases (ammonia content max. 20 ppm).
-
Free from dust (especially flour dust or sawdust).
-
Free from vibrations.
-
Free access to the installation location.
-
If possible, no direct sunlight.