Sonnen Protect2500 Operating Instructions Download Page 4

 
 
 

 

 

 

 

 

S o n n e n   A u s t r a l i a   P t y   L t d  

6 0 4   S o u t h   T o w e r  

1-5 Railway Street, Chatswood 

NSW 2067  

ACN 611 337 547 

0408 802 388 

[email protected] 

 

 

 

 

 

 

 

 

 

 

4.2 

Function 

 

 

 Grid operation 

 no grid outage 

 

 
 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

In grid-connection operation protection against indirect 
contact is ensured by the residual current device (RCD) 
at  the  feed  to  the  socket  outlet  of  the  sonnenProtect 
unit. 
 
 

 

 

 

Figure 3: Grid operation 
 
 
 

 

4.3 

Function 

 

 

 Emergency operation 

 grid outage 

 

 
 

 

 

 
 

 

 

 

In an emergency backup or no grid-connection operation 
protection  against  indirect  contact  is  ensured  by  the 
residual current device  (RCD)  at  the  feed to the  socket 
outlet of the sonnenProtect unit.

  

 

If a grid outage occurs, the connection to the public grid 
is disconnected in the storage system. The plug outlet (1) 
is supplied with electrical power from the storage system 

until the battery’s minimum

 charging status is achieved.  

If  an  insulation  fault  occurs  (RE  <  RAL),  then  the  RCD 
terminates the connection to the MCB and socket outlet. 
When  the  insulation  fault  no  longer  exists,  the 
connection to the plug outlet is re-established once the 
RCD reset switch in reversed. 
 
When  in  backup  mode  the  electrical  power  will  be 
supplied  until  the  backup  buffer  of  the  storage  system 
batteries is depleted. Once the backup buffer is used up 

and  the  battery’s  minimum  state  of  charge  has

  been 

reached,  the  plug  outlet  of  the  sonnenProtect  is  no 
longer supplied with electrical power. 

 

 

Figure 4: Emergency backup operation

 

Reviews: