LKZ-1500-
LITE ● LKZ-1500 – USER MANUAL
41
5.2.3.3
Tracing of damaged insulation and grounding area
Cable insulation failure relative to the ground with the resistance of hundreds Ohm may be locat-
ed with insulation control sensors
– A-frame/DKI-E. Connect the Transmitter in accordance with
. The grounding wire shall be connected to the Transmitter jack with the
marking. The
methods of locating are generally the same as those described in sec. 5.2.1 and 5.2.2.
In case the cable insulation resistance relative to the ground does not allow the use of the insula-
tion control, the method of phase tracing may be applied. It is optimum when the earth leakage im-
pedance can be up to 0.5 MΩ.
The area of damaged insulation shall be determined initially with a reflection-coefficient meter.
One operator only locates by this method, and no additional sensors are required.
Fig. 38 Connecting diagram and signal strength for the method of insulation damage tracing
with insulation control
Fig. 39 Connecting diagram and phase shift at the phase method
of cable insulation failure locating
A-frame
SENSOR input signal strength
Earth fault location
SENSOR
SENSOR
SENSOR
SENSOR
SENSOR
mV
mV
mV
mV
mV
Hz
Hz
Hz
Hz
Hz
Hz
Hz
Hz
Hz
Hz
Ground
Earth fault location
LKN-1500
TRACE
Summary of Contents for LKZ-1500
Page 1: ......
Page 2: ......
Page 18: ...LKZ 1500 LITE LKZ 1500 USER MANUAL 16 Fig 10 LKO 1500 receiver panel...
Page 30: ...LKZ 1500 LITE LKZ 1500 USER MANUAL 28 Fig 25 Locating with Compass line...
Page 57: ...LKZ 1500 LITE LKZ 1500 USER MANUAL 55 NOTES...
Page 58: ...LKZ 1500 LITE LKZ 1500 USER MANUAL 56 NOTES...
Page 59: ......
Page 60: ......