background image

               

                SM6901B    Us er Ma nual                   

http://www.sonbus.com/ 

Sha nghai Son

best Industrial Co., Ltd                                                                             Page4

 

Device ID 

Function id 

Start Address 

Data Length 

CRC16 

FA 

03 

00 64 

00 02 

90 5F 

        FA is 250 for the general address. When you don't know the address, you can use 250 to get the real 

device address, 00 64 is the device model register. 

        For the correct query command, the device will respond, for example the response data is: 01 03 02 

07 12 3A 79, the format of which is as shown in the following table: 

Device ID 

Function id 

Start Address 

Model Code 

CRC16 

01 

  03 

02 

55 3C 00 01 

3A 79 

        Response should be in the data, the first byte 01 indicates that the real address of the current device is, 

55 3C converted to decimal 20182 indicates that the current device main model is 21820, the last two bytes 

00 01 Indicates that the device has a status quantity. 

        (2)Change device address 

        For example, if the current device address is 1, we want to change to 02, the command is:01 06 00 66 

00 02 E8 14 . 

Device ID 

Function id 

Start Address 

Destination 

CRC16 

01 

06 

00 66 

00 02 

E8 14 

        After the change is successful, the device will return information: 02 06 00 66 00 02 E8 27 , its format 

is parsed as shown in the following table: 

Device ID 

Function id 

Start Address 

Destination 

CRC16 

01 

  06 

00 66 

00 02 

E8 27 

        Response should be in the data, after the modification is successful, the first byte is the new device 

address. After the general device address is changed, it will take effect immediately. A t this time, the user 

needs to change the query command of the software at the same time.   

        4 Read and Modify Baud Rate 
        (1) Read baud rate 

        The device default factory baud rate is 9600. If you need to change it, you can change it according to 

the following table and the corresponding communication protocol. For example, read the current device's 

baud rate ID, the command is:01 03 00 67 00 01 35 D5 , its format is parsed as follows.  

Device ID 

Function id 

Start Address 

Data Length 

CRC16 

01 

  03 

00 67 

00 01 

35 D5 

        Read the baud rate encoding of the current device. Baud rate encoding: 1 is 2400; 2 is 4800; 3 is 9600; 

4 is 19200; 5 is 38400; 6 is 115200. 

        For the correct query command, the device will respond, for example the response data is: 01 03 02  

00 03 F8 45, the format of which is as shown in the following table:  

Device ID 

Function id 

Data Length 

Rate ID 

CRC16 

01 

  03 

02 

00 03 

F8 45 

        coded according to baud rate, 03 is 9600, ie the current device has a baud rate of 9600.  

        (2)Change the baud rate 

        For example, changing the baud rate from 9600 to 38400, ie changing the code from 3 to 5, the 

command is: 01 06 00 67 00 05 F8 1601 03 00 66 00 01 64 15 .  

Device ID 

Function id 

Start Address 

Target Baud Rate 

CRC16 

01 

03 

00 66 

00 01 

64 15 

        Change the baud rate from 9600 to 38400, changing the code from 3 to 5. The new baud rate will take 

effect immediately, at which point the device will lose its response and the baud rate of the device should 

Summary of Contents for SM6901B

Page 1: ...n sulfide carbon monoxide eight in one hundred leaf box sensor User Manual File Version V21 3 24 SM6901B using the standard RS485 bus MODBUS RTU protocol easy access to PLC DCS and other instruments or systems for monitoring temperature humidity Illuminance carbon dioxide conductivity methane conductivity carbon monoxide state quantities The internal use of ...

Page 2: ...st 5 Illuminance detection chip Import digital Wavelength range 380nm 730nm CO2 range 0 5000ppm CO2 accuracy 100ppm Smoke measuring range 0 5000ppm Smoke allow deviation 7 Smoke Repeatability test 5 Smoke detection chip Import digital Temperature characteristics 0 5 CH4 measuring range 0 5000ppm CH4 allow deviation 7 CH4 Repeatability test 5 Temperature characteristics 0 5 H2S range 0 100ppm H2S a...

Page 3: ... 00 7C 00 7D 00 7E Data Description The data in the command is hexadecimal Take data 1 as an example 00 79 is converted to a decimal value of 121 If the data magnification is 100 the actual value is 121 100 1 21 Others and so on 2 Data Address Table Address Start Address Description Data type Value range 40001 00 00 1 temperatureregister Read only 0 65535 40002 00 01 2 temperatureregister Read onl...

Page 4: ...irst byte is the new device address After the general device address is changed it will take effect immediately At this time the user needs to change the query command of the software at the same time 4 Read and Modify Baud Rate 1 Read baud rate The device default factory baud rate is 9600 If you need to change it you can change it according to the following table and the corresponding communicati...

Page 5: ...ster If the device has multiple parameters other parameters operate in this way The same the general temperature humidity have this parameter the light generally does not have this item 2 Change correction value For example the current state quantity is too small we want to add 1 to its true value and the current value plus 100 correction operation command is 01 06 00 6B 00 64 F9 FD Device ID Func...

Page 6: ...SM6901B User Manual http www sonbus com ShanghaiSonbest Industrial Co Ltd Page6 ...

Reviews: