                SM2130B-CH2O    Us er Ma nual                   

http://www.sonbus.com/ 

Sha nghai Son

best Industrial Co., Ltd                                                                             Page1

 

 

SM2130B-CH2O 

RS485 interface formaldehyde sensor 

User Manual   

 

File Version: V21.3.24

   

        SM2130B-CH2O using the standard    RS485 bus MODBUS-RTU protocol,easy access to PLC

DCS 

and other instruments or systems for monitoring formaldehyde state quantities.The internal use of 

high-precision sensing core and related devices to ensure high reliability and excellent long-term 

stability,can be customized RS232,RS485,CAN,4-20mA,DC0~5V\10V,ZIGBEE,Lora,WIFI,GPRS and 

other output methods. 

        Technical Parameters 

Technical parameter 

Parameter value 

Brand 

SONBEST 

CH2O range 

0~5ppm 

CH2O accuracy 

±

0.1ppm 

CH2O response time 

≤ 60 seconds 

CH2O recovery time 

≤ 60 seconds 

Communication Interface 

RS485 

Default baud rate 

9600 8 n 1 

Power 

DC9~24V 1A 

Running temperature 

-40~80° C 

Working humidity 

5%RH~90%RH 

        Wiring instructions 

        Any incorrect wiring can cause irreversible damage to the product. Please carefully wire t he cable as 

follows in the case of power failure, and then connect the cable to confirm the correctness and then use it 

again.   

ID 

Core color 

Identification 

Note 

Red 

V+ 

Power + 

Green 

V- 

Power - 

Yellow 

A+ 

RS485 A+ 

Blue 

B- 

RS485 B- 

                                     

        In the case of broken wires, wire the wires as shown in the figure. If the product itself has no leads, the 

core color is for reference. 

        Communication Protocol 

        The product uses RS485 MODBUS-RTU standard protocol format, all operation or reply commands 

are hexadecimal data. The default device address is 1 when the device is shipped, the default baud rate is 

9600, 8, n, 1   

        1. Read Data (Function id 0x03) 

Summary of Contents for SM2130B-CH2O

Page 1: ...econds CH2O recovery time le 60 seconds Communication Interface RS485 Default baud rate 9600 8 n 1 Power DC9 24V 1A Running temperature 40 80 C Working humidity 5 RH 90 RH Wiring instructions Any incorrect wiring can cause irreversible damage to the product Please carefully wire the cable as follows in the case of power failure and then connect the cable to confirm the correctness and then use it ...

Page 2: ...e address If you don t know the current device address and there is only one device on the bus you can use the command FA 03 00 64 00 02 90 5F Query device address Device ID Function id Start Address Data Length CRC16 FA 03 00 64 00 02 90 5F FA is 250 for the general address When you don t know the address you can use 250 to get the real device address 00 64 is the device model register For the co...

Page 3: ...tion id Start Address Target Baud Rate CRC16 01 03 00 66 00 01 64 15 Change the baud rate from 9600 to 38400 changing the code from 3 to 5 The new baud rate will take effect immediately at which point the device will lose its response and the baud rate of the device should be queried accordingly Modified 5 Read Correction Value 1 Read Correction Value When there is an error between the data and th...

Page 4: ...the product does not grant any license to intellectual property does not express or imply and prohibits any other means of granting any intellectual property rights such as the statement of sales terms and conditions of this product other issues No liability is assumed Furthermore our company makes no warranties express or implied regarding the sale and use of this product including the suitabilit...