                SM2130-CH4    Us er Ma nual                   

http://www.sonbus.com/ 

Sha nghai Son

best Industrial Co., Ltd                                                                             Page1

 

 

SM2130-CH4 

RS485 interface protection type methane sensor 

User Manual   

 

File Version: V21.3.24

   

        SM2130-CH4 using the standard    RS485 bus MODBUS-RTU protocol,easy access to PLC

DCS and 

other instruments or systems for monitoring methane state quantities.The internal use of high -precision 

sensing core and related devices to ensure high reliability and excellent long-term stability,can be 
customized RS232,RS485,CAN,4-20mA,DC0~5V\10V,ZIGBEE,Lora,WIFI,GPRS and other output 

methods. 

        Technical Parameters 

Technical parameter 

Parameter value 

Brand 

SONBEST 

CH4 measuring range 

0~5000ppm 

CH4 allow deviation 

±

7% 

CH4 Repeatability test 

±

5% 

Temperature characteristics 

±

0.5%/

 

Communication Interface 

RS485 

Default baud rate 

9600 8 n 1 

Power 

DC9~24V 1A 

Dimensions 

110mm×85mm×42mm 

        Wiring instructions 

        Any incorrect wiring can cause irreversible damage to the product. Please carefully wire the cable as 

follows in the case of power failure, and then connect the cable to confirm the correctness and then use it 

again.   

ID 

Core color 

Identification 

Note 

Red 

V+ 

Power + 

Green 

V- 

Power - 

Yellow 

A+ 

RS485 A+ 

Blue 

B- 

RS485 B- 

                                     

        In the case of broken wires, wire the wires as shown in the figure. If the product itself has no leads, the 

core color is for reference. 

        Communication Protocol 

        The product uses RS485 MODBUS-RTU standard protocol format, all operation or reply commands 
are hexadecimal data. The default device address is 1 when the device is shipped, the default baud rate is 

9600, 8, n, 1   

        1. Read Data (Function id 0x03) 

        Inquiry frame (hexadecimal), sending example: Query 1# device 1 data, the host computer sends the 

Summary of Contents for SM2130-CH4

Page 1: ...stics 0 5 Communication Interface RS485 Default baud rate 9600 8 n 1 Power DC9 24V 1A Dimensions 110mm 85mm 42mm Wiring instructions Any incorrect wiring can cause irreversible damage to the product Please carefully wire the cable as follows in the case of power failure and then connect the cable to confirm the correctness and then use it again ID Core color Identification Note 1 Red V Power 2 Gre...

Page 2: ...re is only one device on the bus you can use the command FA 03 00 64 00 02 90 5F Query device address Device ID Function id Start Address Data Length CRC16 FA 03 00 64 00 02 90 5F FA is 250 for the general address When you don t know the address you can use 250 to get the real device address 00 64 is the device model register For the correct query command the device will respond for example the re...

Page 3: ...4 15 Change the baud rate from 9600 to 38400 changing the code from 3 to 5 The new baud rate will take effect immediately at which point the device will lose its response and the baud rate of the device should be queried accordingly Modified 5 Read Correction Value 1 Read Correction Value When there is an error between the data and the reference standard we can reduce the display error by adjustin...

Page 4: ...al property does not express or imply and prohibits any other means of granting any intellectual property rights such as the statement of sales terms and conditions of this product other issues No liability is assumed Furthermore our company makes no warranties express or implied regarding the sale and use of this product including the suitability for the specific use of the product the marketabil...