                SM1635B-1    Us er Ma nual                   

http://www.sonbus.com/ 

Sha nghai Son

best Industrial Co., Ltd                                                                             Page4

 

effect immediately, at which point the device will lose its response and the baud rate of the device should 

be queried accordingly. Modified. 

        5 Read Correction Value 
        (1) Read Correction Value 

        When there is an error between the data and the reference standard, we can reduce the display error 

by adjusting the correction value. The correction difference can be modified to be plus or minus 1000, t hat 

is, the value range is 0-1000 or 64535 -65535. For example, when the display value is too small, we can 

correct it by adding 100. The command is: 01 03 00 6B 00 01 F5 D6 . In the command 100 is hex 0x64 If 
you need to reduce, you can set a negative value, such as -100, corresponding to the hexadecimal value of 

FF 9C, which is calculated as 100-65535=65435, and then converted to hexadecimal to 0x FF 9C. The 

correction value starts from 00 6B. We take the first parameter as an example. The correction valu e is read 

and modified in the same way for multiple parameters. 

Device ID 

Function id 

Start Address 

Data Length 

CRC16 

01 

03 

00 6B 

00 01 

F5 D6 

        For the correct query command, the device will respond, for example the response data is: 01 03 02 

00 64 B9 AF, the format of which is as shown in the following table: 

Device ID 

Function id 

Data Length 

Data value 

CRC16 

01 

  03 

02 

00 64 

B9 AF 

        In the response data, the first byte 01 indicates the real address of the current device, and 00 6B is the 

first state quantity correction value register. If the device has multiple parameters, other parameters 

operate in this way. The same, the general temperature, humidity have this parameter, the light generally 

does not have this item. 

        (2)Change correction value 

        For example, the current state quantity is too small, we want to add 1 to its true value, and the current 

value plus 100 correction operation command is:01 06 00 6B 00 64 F9 FD .   

Device ID 

Function id 

Start Address 

Destination 

CRC16 

01 

06 

00 6B 

00 64 

F9 FD 

        After the operation is successful, the device will return information: 01 06 00 6B 00 64 F9 FD, the 
parameters take effect immediately after successful change. 

        Disclaimer 

        This document provides all information about the product, does not grant any license to intellectual 

property, does not express or imply, and prohibits any other means of granting any intellectual property 

rights, such as the statement of sales terms and conditions of this product, other issues. No liability is 
assumed. Furthermore, our company makes no warranties, express or implied, regarding the sale and use 

of this product, including the suitability for the specific use of the product, the marketability or the 

infringement liability for any patent, copyright or other intelle ctual property rights, etc. Product 

specifications and product descriptions may be modified at any time without notice.  

        Contact Us 

        Company: Shanghai Sonbest Industrial Co., Ltd   

        Address:Building 8,No.215 North east road,Baoshan District,Sha nghai,China 

        Web: http://www.sonbest.com  

        Web:    http://www.sonbus.com   

        SKYPE:  soobuu   
        Email: [email protected] 

Summary of Contents for SM1635B-1

Page 1: ...ODBUS RTU protocol easy access to PLC DCS and other instruments or systems for monitoring 4 20MAcurrent state quantities The internal use of high precision sensing core and related devices to ensure high reliability and excellent long term stability can be customized RS232 RS485 CAN 4 20mA DC0 5V 10V ZIGBEE Lora WIFI GPRS and other output methods Technical Parameters Technical parameter Parameter ...

Page 2: ...exadecimal sending example Query 1 device 1 data the host computer sends the command 01 03 00 00 00 01 84 0A Device ID Function id Start Address Data Length CRC16 01 03 00 00 00 01 84 0A For the correct query frame the device will respond with data 01 03 02 00 79 79 A6 the response format is parsed as follows Device ID Function id Data Length 数据 1 Check Code 01 03 02 00 79 79 A6 Data Description T...

Page 3: ...2 E8 27 Response should be in the data after the modification is successful the first byte is the new device address After the general device address is changed it will take effect immediately At this time the user needs to change the query command of the software at the same time 4 Read and Modify Baud Rate 1 Read baud rate The device default factory baud rate is 9600 If you need to change it you...

Page 4: ... the current device and 00 6B is the first state quantity correction value register If the device has multiple parameters other parameters operate in this way The same the general temperature humidity have this parameter the light generally does not have this item 2 Change correction value For example the current state quantity is too small we want to add 1 to its true value and the current value ...

Page 5: ...SM1635B 1 User Manual http www sonbus com ShanghaiSonbest Industrial Co Ltd Page5 Tel 86 021 51083595 66862055 66862075 66861077 ...

Reviews: