                SD2100B    Us er Ma nual                   

http://www.sonbus.com/ 

Sha nghai Son

best Industrial Co., Ltd                                                                             Page2

 

Temperature measuring range 

-30

~80

 

Temperature measuring accuracy 

±

0.5

  @25

 

Communication Interface 

RS485 

Default baud rate 

9600 8 n 1 

Power 

DC9~24V 1A 

Display 

LCD 

Running temperature 

-40~80° C 

Working humidity 

5%RH~90%RH 

        Wiring instructions 

        Any incorrect wiring can cause irreversible damage to the product. Please carefully wire the cable as 

follows in the case of power failure, and then connect the cable to confirm the correctness and then use it 

again.   

ID 

Core color 

Identification 

Note 

Red 

V+ 

Power + 

Green 

V- 

Power - 

Yellow 

A+ 

RS485 A+ 

Blue 

B- 

RS485 B- 

                                     

        In the case of broken wires, wire the wires as shown in the figure. If the product itself has no leads, the 

core color is for reference. 

        Communication Protocol 

        The product uses RS485 MODBUS-RTU standard protocol format, all operation or reply commands 

are hexadecimal data. The default device address is 1 when the device is shipped, the default baud rate is 

9600, 8, n, 1   

        1. Read Data (Function id 0x03) 

        Inquiry frame (hexadecimal), sending example: Query 1# device 1 data, the host computer sends the 

command:01 03 00 00 00 01 84 0A . 

Device ID 

Function id 

Start Address 

Data Length 

CRC16 

01 

03 

00 00 

00 01 

84 0A 

        For the correct query frame, the device will respond with data:01 03 02 00 79 79 A6 , the response 

format is parsed as follows:   

Device ID 

Function id 

Data Length 

data 1 

Check Code 

01 

03   

02 

00 79 

79 A6 

        Data Description: The data in the command is hexadecimal. Take data 1 as an example. 00 79 is 

converted to a decimal value of 121. If the data magnification is 100, the actual value is 121/100=1.21. 

Others and so on. 

        2. Data Address Table 

Address 

Start Address 

Description 

Data type 

Value range 

40001 

00 01 

temperature 

read 

0~65535 

40101 

00 64 

model code 

read/write 

0~65535 

40102 

00 65 

total points 

read/write 

1~20 

40103 

00 66 

Device ID 

read/write 

1~249 

40104 

00 67 

baud rate 

read/write 

0~6 

Summary of Contents for SD2100B

Page 1: ...ODBUS RTU protocol easy access to PLC DCS and other instruments or systems for monitoring temperature state quantities The internal use of high precision sensing core and related devices to ensure high reliability and excellent long term stability can be customized RS232 RS485 CAN 4 20mA DC0 5V 10V ZIGBEE Lora WIFI GPRS and other output methods Technical Parameters Technical parameter Parameter va...

Page 2: ...eration or reply commands are hexadecimal data The default device address is 1 when the device is shipped the default baud rate is 9600 8 n 1 1 Read Data Function id 0x03 Inquiry frame hexadecimal sending example Query 1 device 1 data the host computer sends the command 01 03 00 00 00 01 84 0A Device ID Function id Start Address Data Length CRC16 01 03 00 00 00 01 84 0A For the correct query frame...

Page 3: ...Function id Start Address Destination CRC16 01 06 00 66 00 02 E8 14 After the change is successful the device will return information 02 06 00 66 00 02 E8 27 its format is parsed as shown in the following table Device ID Function id Start Address Destination CRC16 01 06 00 66 00 02 E8 27 Response should be in the data after the modification is successful the first byte is the new device address Af...

Page 4: ...ample the response data is 01 03 02 00 64 B9 AF the format of which is as shown in the following table Device ID Function id Data Length Data value CRC16 01 03 02 00 64 B9 AF In the response data the first byte 01 indicates the real address of the current device and 00 6B is the first state quantity correction value register If the device has multiple parameters other parameters operate in this wa...

Page 5: ...anghaiSonbest Industrial Co Ltd Page5 Address Building 8 No 215 North east road Baoshan District Shanghai China Web http www sonbest com Web http www sonbus com SKYPE soobuu Email sale sonbest com Tel 86 021 51083595 66862055 66862075 66861077 ...

Reviews: