Ad1:1st alarm mode setting;VL:low limit alarm of voltage

VH:high limit alarm of voltage,AL:low limit alarm of current

AH:high limit alarm of current

ex-factory setting is AH

SET

SET

3S

HY1:1st alarm hystersis setting;setting range-1999

9999

.

Eg:If alarm mode Ad1 be set to AH high limit alarm of current,

and AL1 set to 4.5,HY1 set to 0.1, when actual measured 

current value

(4.5-0.1), it will stop alarm

Note: other codes

alarm setting are similar to the above ,ex-factory setting is 0.100

bAd: baud rate , Baud rate option: 4.8Kbit

9.6Kbit , Ex-factory setting is 9.6Kbit,

SET

SET

SET

SET

SET

SET

SET

SET

SET

SET

SET

SET

SET

Ad2:Please refer to Ad1

AL2: Please refer to AL1

HY2:Please refer to HY1

ex-factory setting is AL

ex-factory setting is 0.500

ex-factory setting is 0.100

KKEH8E01-A/0-3

SET

SET

Measuring status

AL1:1st alarm setting menu ,setting range:-1999~9999 .
eg.If the first alarm mode Ad1 set to AH (high limit alarm 
of current) and the AL1 set to 4.5 , when the measured 

current value

4.5 ,

the meter will alarm automatically . 

Ex-factory value is 4.500 

Ct: Current transform setting: 
settable range is 1.0-1999, only for current channel. E.g.,  
if the meter need to measure 20A current, the CT value  
should be set as 4.000 (20/5=4.000), since the max. 
current that can be input to the meter is 5A. Ex-factory 
setting of CT is 1.00 .   
Note: A CT (current transformer) should be equipped with  
the meter if the measured current is higher than 5A. 

LCK:Menu lock:setting value 000 or 010
when it is 000 , the parameters could be
modified , when it is 010 , all the parameters
couldn

t be modified. Ex-factory value is 000

APS:Current Amendment value . the range is 
-1999 to 9999. It is to amend the measured  
current, Display value=Measured value+APS  
value, Ex-factory setting value is 0.000. 

VPS:Voltage Amendment.value . the range is 
-1999 to 9999. It is to amend the measured  
voltage, Display value=Measured value+VPS 
value, Ex-factory setting value is 0.000. 

rL:Analog output low limit setting value,value 

range is-1999 to 9999 . If it is set as current 

analog output, the value is to be low limit of  

measured  current . Ex-factory setting is 0.000  

rH:Analog output high limit setting, value 

range is-1999 to 9999. If it is set as current  

analog output, the value is to be high limit of 

measured current . Ex-factory setting is 5.000

brm:Analog output mode selection is as below: 

A: Current analog
V: Voltage analog
Ex-setting is A

Add:Commnunication address.  

Settable range is 0-255.  

Ex-factory setting is 000. 

2.Press SET key to select the parameter needing modified ,press     to make the parameter flick ,and press             to set needed value

   and press SET key to confirm the modifying .Press     to make the needing modified parameter flick, press 

+      to shift the decimal 

   point, press SET key to go on for another menu. 

3.Under setting status

long press SET>3s can return to measuring status .

   

The instruction for the above menu operation and settings are as below: 

1. Press SET key for 3 seconds

the meter will show the parameter setting menu. 

 /

Summary of Contents for EH8

Page 1: ...o not touch wire connectors when the power is on otherwise you may get an electric shock 4 Do not dismantle or modify the product If you have to do so please contact with us first Otherwise it may cau...

Page 2: ...V 3A or DC 30V 5A Input impedance Voltage input impedance 2M 450V current input impedance 0 02 when direct input is 0 5A Direct input range Displaying mode CT Measuring accuracy Sampling speed Power s...

Page 3: ...the measured current is higher than 5A LCK Menu lock setting value 000 or 010 when it is 000 the parameters could be modified when it is 010 all the parameters couldn t be modified Ex factory value i...

Page 4: ...elative humidity is below 85 2 It should be adjusted every year 3 Avoid 4 If it is stored for a long time and unused connect on power for more than 4 hours once every 3 months 5 Don t explose it in th...

Page 5: ...1 0x03 0x04 0x00 0x80 0x71 0x43 0x9E 0x7A Meter address Function code Data byte number Data 1 High bit Data 1 Low bit Slave unit abnormal answer Read multi register 1 2 3 8 9 0x01 0x84 0x01 0x82 0xC0...

Page 6: ...mode Ad1 1 0 9 R W Note Note 21 0x0015 2nd alarm mode Ad2 1 0 9 R W 22 0x0016 Analog mode brM 1 0 3 R W 23 0x0017 Menu lock LCK 1 0 255 R W 24 0x0018 Baud rate bAd 1 0 1 R Note Note 25 0x0019 Address...

Page 7: ...AL2 AL1 mA A KV V The program of decimalist float data converts to 4 byte character code as IEEE 754 standards Program of obtaining 16 digits CRC checking code The program of 4 byte character code flo...

Reviews: