EN
A
MOUNTING
[1]
Choose the optimal location: flat and large surface
[2]
Mount the LON 4 DC Motor Controller WM
[3]
Use cable tie!
[4]
Keep to minimum distance
B
CABLING
[1] Tool for all terminals
[2] Wiring diagram
[3]
Check the correct running direction of the end product
UP: the end product goes up ( C +
)
STOP: the end product stops ( C +
+
)
DOWN: the end product goes down ( C +
)
m
To close window press UP, to open window press DOWN.
[4]
Possible switches
1.
Smoove Origin IB, Ref. 1811272
2.
Double push button
C
COMMISSIONING AND OPERATING
[1]
Attach the Motor Controller address label in accordance with the motor
output in a plan or a list.
[2] Reset/Prog button
Factory reset of the LON Motor Controller.
CHARACTERISTICS
Supply voltage
24 V DC (min. 21.5 V - max. 28 V DC)
Power Supply
Regulated and short circuit proof power supply, certified and suitable for the connected motors
Stand-by current / Stand-by power (IEC 62301)
37 mA@24 V DC / 890 mW@24 V DC
LON transceiver
FTT
Max. motor current consumption
4 x 2.5 A@24 V DC
Supply voltage of group control input
SELV, 16 V DC
Supply voltage of local push buttons
SELV, 16 V DC
Terminals
Spring connectors
Relay micro-gap
μ
Terminal LON
LON bus terminal (green)
Running time per output
Max. 5 minutes
Operating temperature
0 ° C ... 45 ° C
Relative humidity
Max. 85 %
Material of housing
PC-ABS
Housing dimensions (w x h x d)
180 x 255 x 61 mm
Weight
710 g
Degree of protection
IP 20
Protection class
Pollution degree
2
Conformity
www.somfy.com/ce
We care about our environment. Do not dispose of the appliance with usual household waste. Give it to an approved collection point for recycling.
CABLE
Connection to ...
Cable
Twisted pair
Max. length
Stripping length
Motors
Min.: 2 x 0.6 mm/22 AWG / Max.: 2 x 2.5 mm
2
/13 AWG –
6 mm/0.24"
Switch
Min.: 3 x 0.6 mm/22 AWG / Max.: 3 x 2.5 mm
2
/13 AWG Recommended
100 m/330 ft
6 mm/0.24"
Group control
Min.: 3 x 0.6 mm/22 AWG / Max.: 3 x 1.5 mm
2
/15 AWG Recommended
100 m/330 ft
6 mm/0.24"
LON bus
2 x 0.8 mm/20 AWG
Required, following LON topology guidelines
6 mm/0.24"
24 V DC
Min.: 2 x 1.5 mm
2
/15 AWG / Max.: 2 x 2.5 mm
2
/13 AWG –
10 m/33 ft
6 mm/0.24"
m
Control of non Somfy motors only on request and after approval by Somfy
animeo
LON 4 DC Motor Controller WM. Ref. 5138036A -
8/20
CORRECTION LOOP 1