animeo IB+
4 Zone/8 Zone TouchBuco BACnet
2020/04/30
Seite 29
Outside temperature On/Off
The "Cooling" function is enabled when the outside temperature has reached the defined "On" value and
deactivated when the outside temperature has reached the defined "Off" value.
Adjustment range from -40 °C to +40 °C.
Inside Temperature
If the inside temperature is above the "Inside Temperature On" threshold, the selected position is
approached (typically: 100 % = open).
If the inside temperature is below the "Inside Temperature Off" threshold, the function is deactivated. Adjust-
ment range from 0 °C to 40 °C.
Delta Temperature
The "Cooling" function is enabled when the difference in temperature (outside < inside) exceeds the value
set under "Delta Temperature On".
The "Cooling" function is deactivated when the difference in temperature (outside < inside) falls below the
value set under "Delta Temperature Off".
Note: The "Delta Temperature On" value must be greater than the "Delta Temperature Off" value.
Adjustment range from 1 °C to 40 °C.
Delay time
Adjustment range from 0 to 255 minutes.
Cooling On
Setting the position in % (100 % = open).
Cooling Off
Setting the position of the motorized product after enabling the function:
•
No Action
: The end products/motorized products remain stationary in position.
•
Standard
: The end products/motorized products move to the standard position. The standard
position needs to be defined once (s. chapter 6.5.1 System Settings).
•
Position
: The end products/motorized products move to a set position. In the case of Venetian
blinds, the defined angle is set.
•
My Position
: The motorized products move to the intermediate position programmed in the motor
controller.
6.3.6 Reset to Auto
If the motorized product is operated locally when working in "Manual" or "Comfort" mode, the automatic func-
tion is deactivated for the corresponding motorized product. This function allows you to re-enable automatic
mode via "Reset" either manually or via three timers.
If you enable the "Update Position/Angle" function, the current position of the end product/motorized product
is also transmitted and approached in addition to the reset.
Use the "Right arrow" button to access the individual timers, via which you can also perform a reset.
H
Smoove Uno IB+ control units are not reset when the automatic system is switched off manually. Only
when an energy mode is received.