WIRING INSTRUCTIONS
1. Disconnect electrical service at the main fuse or circuit
breaker box.
2. Install any code required electrical disconnects to the
line service.
3. Remove the side panel and electrical service panel
from the dehumidifier. See
Figure 5
.
4. Disconnect the power cord connections from the
terminals in the electrical service box. See
Figure 6
.
5. Use pliers to pinch the strain relief and pull it out of the
dehumidifier cabinet along with the power cord. See
Figure 5
.
6. Route the service cable through the 7/8" diameter
hole where the power cord was removed. USE ONLY
COPPER SUPPLY WIRES.
7. Secure the cable/conduit to the dehumidifier using
fittings/connectors approved for the type of cable/
conduit used.
8. Connect the ground wire of the service cable to the
ground lug in the electrical service box. See
Figure 6
.
9. Connect the line voltage wires of the service cable to
the LINE BLK and NTRL WHT terminals. See
Figure 6
.
10. Reattach the electrical service panel and side panel.
11. Restore electrical service at the main fuse or circuit
breaker box.
SIDE PANEL
ELECTRICAL
SERVICE BOX
POWER CORD
STRAIN
RELIEF
90-1900
Figure 5. Electrical Service Box Location
Location Considerations
• Allow sufficient clearance for filter removal and to prevent
airflow obstruction
• Electrical service access will require the removal of the
side panel shown. Allow sufficient space for service on
this side of the unit.
• If locating the unit in an attic or crawl space, a Lennox
iComfort
®
S30 Thermostat, iComfort Wi-Fi
®
Thermostat,
ComfortSense
®
7000 Thermostat, or a Y6456 Control
mounted in the living space is recommended.
• For attic installations, it is recommended that the
dehumidifier be suspended.
• Always install the dehumidifier in a condensate pan when
locating in or over a finished space.
LINE
VOLTAGE
NEUTRAL
GROUND
115V AC WIRING
TERMINALS
GROUND LUG
FITTING AS
REQUIRED
LINE SERVICE
CABLE/CONDUIT
ELECTRICAL
SERVICE BOX
90-1902
Figure 6. Hard Wire to 115 VAC Service
Figure 7. Filter Access Clearance
TOP VIEW
FILTER
6" MINIMUM CLEARANCE
FOR PROPER AIR FLOW
ELECTRICAL SERVICE
ACCESS THIS SIDE
8 FT. POWER CORD
MINIMUM CLEARANCE
FOR FILTER (EITHER SIDE)
13"
FOR
HCWHD3-070
&
HCWHD3-095
20"
FOR
HCWHD3-130
90-1840
5