1

 / 

53

 

 

 

User Manual

 

 

 

 

  Home Energy Storage System 

   

 

 

Soluna S12 EU 

 
 
 

 
 
 
 
 
 

 

Oct.2020| Revision A.1 

 

 

 

 

Summary of Contents for S12 EU-A36

Page 1: ...1 53 User Manual Home Energy Storage System Soluna S12 EU Oct 2020 Revision A 1 ...

Page 2: ...al contact Soluna immediately for advising and clarification The information included in this manual is accurate at the time of publication however with regards to the product design and technical specification updates our company reserves the right to make changes at any time without prior notice e In addition the illustrations in this manual are meant to help explain system configuration concept...

Page 3: ...ation tools 19 3 2 Installation spacing 20 3 3 Wire specifications 20 3 4 Installation step 20 3 4 1 Unpacking confirmation 20 3 4 2 Basic installation requirement 21 3 4 3 Installation procedures 22 4 How to operate Soluna 33 4 1Turn on or turn off Soluna S12 EU system 33 4 2 How to operate LCD screen user screen 34 4 2 1 Position of LCD 34 4 2 2 How to check the information of LCD screen 35 4 2 ...

Page 4: ...4 53 5 2 Grid parameters setting 45 5 3 Others 47 6 Caution 48 7 Troubleshoot 49 8 How to use the generator AC couple function 53 9 Contact us 53 ...

Page 5: ...ill not responsible for any consequence caused by any of the following events Damage caused by transportation The storage conditions do not meet the requirements specified in the manual resulting in damage Incorrect storage installation and use Unqualified personnel install and operate the machine Failure to comply with the operation instructions and safety precautions in this manual Operate in ex...

Page 6: ...in this manual Sign Name Description Danger Serious physical injury or even death may occur if related requirements are not followed Warning Physical injury or damage to the devices may occur if related requirements are not followed Electrostatic discharge Damage may occur if related requirements are not followed Hot sides Sides of the device may become hot Do not touch Note Note Steps to take for...

Page 7: ...und with proper technics before operation Do not open the surface cover of the machine unless authorized The electronic components inside the machine are electrostatic sensitive Do take proper anti electrostatic measures during authorized operation Do not touch the housing of the machine or the radiator to avoid scald as they may become hot during operation The machine needs to be reliably grounde...

Page 8: ...allation tools and take mechanical protection measures to protect personal safety such as wearing smashing shoes coverall and so on Only qualified electricians are allowed to install the machine Do not put and install the machine on or close to flammable or explosive materials Do not install the machine in a place where children and other people can easily touch it To avoid a risk of electric shoc...

Page 9: ... discharged Please follow the electrostatic protection norms and take correct protective measures because there are mostly electrostatic sensitive circuits and devices in the machine Do not use parts and components not provided by our company during maintenance Restart the machine after eliminating the faults and problems which may affect the safety and performance of the machine Do not get close ...

Page 10: ...m the grid but also improves the household energy self consumption and saves the electricity cost Soluna integrated energy storage solve solution help users with achieving maximize the self use of green energy 2 1 Features intelligent power management Simple user controls power data history analysis and programming Capacitive touch screen interface Secure battery access door height adjustable thre...

Page 11: ...11 53 2 3 Outline Dimensions Figure 2 1 outline dimension Width 750 mm Depth 565 mm Height 1335 mm Weight 240 kg ...

Page 12: ...12 53 2 4 Functional description 2 4 1 Basic principle of Soluna S12 EU Figure2 2 basic principle of Soluna S12 EU ...

Page 13: ...remaining power and grid sell power is adjustable Mode 7 UPS Function can ensure important loads still powered in case grid suddenly fail down 2 5 Technical data 2 5 1 Technical data of System Specifications table Model Soluna S12 EU A80 Soluna S12 EU A50 Soluna S12 EU A36 PV input Max recommended DC power W 8000 6500 4680 Max DC voltage V 500 500 500 Start up Voltage V 150 150 150 Nominal DC oper...

Page 14: ...150 100 60 Max discharge current A 150 100 60 DOD 80 Cycle life 6000 Regular parameters Protective class Class I Overvoltage category OVC II PV OVCIII AC main Grid Dimension mm W D H 750 565 1335 Weight kg 240 Display 7 graphic LCD Communication WIFI CAN Operating temperature range C 10 40 45 derating Storage stability range C 20 60 Relative humidity 0 95 Altitude m 2000 Cooling methods Forced air...

Page 15: ...arge Current 50A Max Continuous Discharge Current 50A DOD 80 Internal resistance 60 mΩ Cycle life 25 under standard charge and discharge conditions charge 0 2C discharge 0 2C 6000 DC Disconnect Contactor Fuse Warranty Please refer to SOLUNA WARRANTY CONDITIONS BMS Power consumption 3W work 100mW sleep Monitoring parameters System Voltage System Current Cell Voltage Cell temperature Communication C...

Page 16: ...mended 15 30 Storage Temperature 20 60 Humidity 5 95 Altitude Max 2 000 m Cooling Strategy Natural Convection Reliability Certification Certificates Cell UL1642 Battery Module IEC62619 UL1973 Transportation UN38 3 Ingress Rating IP20 2 6 Appearance Figure 2 3 Appearance Number Name Remark Soluna brand LCD panel ...

Page 17: ...17 53 Figure 2 4 Appearance Number Name Remark FAN outlet FAN outlet Emergency Stop Handle Entry port Label ...

Page 18: ...18 53 Figure 2 5 Appearance Number Name Remark Door lock of system Door key ...

Page 19: ...on tools Item Photo Remark 1 Marking pen 2 Impact drill φ12 mm 3 Steel tape 4 Torque wrench Opening size 13mm 5 Phillips screwdriver M6 M8 6 Straight screwdriver 7 Multimeter 8 Safety gloves 9 Safety goggles 10 Dust mask 11 Safety shoes ...

Page 20: ... wires of corresponding types of inverters Model GRID Load side PV Load Soluna S12EU A36 It is recommended to use 4 mm of wire It is recommended to use 4 mm of wire Soluna S12EU A50 It is recommended to use 6mm of wire It is recommended to use 6 mm of wire Soluna S12EU A80 It is recommended to use 10mm of wire It is recommended to use 6 mm of wire 3 4 Installation step 3 4 1 Unpacking confirmation...

Page 21: ...e following requirements The installation site should be well ventilated free from rain and direct sunlight The installation floor should be dry and flat It is strictly forbidden to have water on the ground ensure that the ground level is not shaken and can fully carry the weight of the energy storage integrated machine cabinet The temperature in the installation environment should range from 10 C...

Page 22: ...mechanical installation steps are as follows Step1 user can find 3units of battery module and 1unit of the case of soluna after opening the packing box Figure 3 1 Soluna system case Battery units Number Name Remark System case Battery module ...

Page 23: ...23 53 Step2 The system is installed against the wall Figure 3 2 Installation place Number Name Remark Wall Soluna System Expansion Screw Fixed Bracket Ground ...

Page 24: ...24 53 Step3 Open the door of soluna system and open the case of battery module System case Figure 3 3 System case Figure 3 4 Battery unit Number Name Remark System case Case of Battery module ...

Page 25: ...ush the battery module into the system and lock the battery cable and plug in the CAN communication Remote line Figure 3 5 Connection for battery cable CAN communication Remote line Position of adding RJ45 terminal ...

Page 26: ...s Figure 3 6 RJ45 terminal Number Name Remark Remote wire Battery cable CAN communication line Remark Connecting wire for communication line 1 All CAN1 lines are parallel for the internal communication of battery units 2 All CAN2 lines are parallel for the external communication between battery unit and hybrid inverter then CAN2 is connected to inverter Step 5 Fixed battery module and Close the do...

Page 27: ... circuit connection PV Grid Load Figure3 8 external circuit connection Number Name Remark Emergency Stop Load connector Back up load connector Grid connector GEN connector PV connector GEN control port CT connector Details ...

Page 28: ...6 N m Ensure that the maximum open circuit voltage of each PV string is not higher than the maximum input voltage of the energy storage integrated machine under any circumstances It is forbidden to connect the PE wire ground wire to the positive and negative poles of the PV strings otherwise it will cause damage to the energy storage integrated machine Ensure that the PV string polarity matches th...

Page 29: ...ended to use 10mm of wire It is recommended to use 10mm of wire Terminal crimping of wires L N and PE of the mains and load cables Terminal crimping torque 3 6 4 6 N m Note Before connecting the AC power grid cable to the energy storage integrated machine the lightning protection and short circuit protection measures must be taken in accordance with the local electrical safety regulations The PE c...

Page 30: ...30 53 Step7 Electrical connection 1 Soluna S12EU A36 2 Soluna S12EU A50 ...

Page 31: ...31 53 3 Soluna S12EU A80 ...

Page 32: ...32 53 4 CT connection Number Name Remark CT connector Connect to black wire of CT CT connector Connect to white wire of CT CT ...

Page 33: ...h of Load Grid Battery Remote Turn off Open the door and turn off all the switch of Load Grid Battery Remote Please find the following pictures for the position of switch Figure 4 1 Turn on Turn off system Number Name Remark PV Switch Grid breaker Load breaker Back up load breaker GEN breaker Battery breaker Remote switch ...

Page 34: ...ating information and perform simple charge and discharge settings on the user screen please find the following information for details 4 2 1 Position of LCD Figure 4 2 LCD Number Name Remark LCD panel Note The LCD is touch screen user can touch the screen to see the information of system ...

Page 35: ...rmation Battery Capacity Click each icon will see the relevant information Please find the following picture for the interface of LCD screen Figure 4 3 LCD Screen 4 2 3 How to check the information of Status icon User can find the following interface after clicking the icon of Status Figure 4 4 information of status icon ...

Page 36: ...36 53 Figure 4 5 PV information Figure 4 6 Load information Figure 4 7 Grid information ...

Page 37: ... to Setting parameters of Soluna system User find the following interface after clicking the icon of Setting Figure 4 9 Setting icon information User can find the following interface after clicking the icon of Power sources Figure 4 10 Power source ...

Page 38: ...38 53 Figure 4 11 Charging setting 1 Figure 4 12 Charging setting 2 Figure 4 13 Charging setting 3 ...

Page 39: ...harging is beneficial to prolong the battery life User can find the following interface after clicking the icon of power utilizations If user does not want the battery s energy to be fed back to the grid tick House load only Users can set the battery discharge time period according to their need User can find the following interface after clicking the icon of Languages ...

Page 40: ...and discharging time setting on the user s screen is directly related to the local time User can find the following interface after clicking the icon of Reset advanced Setting User need to enter password if the user wants to restore the parameters of Soluna system Remark Soluna will provide the password if user needs it The advanced settings are only opened to installers and it is not recommended ...

Page 41: ...53 4 2 5 How to check the information of Data icon User can find the following interface after clicking the icon of Data a User can find the following interface after clicking the icon of Solar generation ...

Page 42: ...lowing interface after clicking the icon of back to grid C User can find the following interface after clicking the icon of Equivalent tree Planting d User can find the following interface after clicking the icon of save the earth ...

Page 43: ...nformation after click the icon of production information 4 2 7 How to Check the fault information User can find the fault information after click the fault icon Remark User will find an icon blinking in the upper right corner of the LCD panel if there is any fault during Soluna system operation ...

Page 44: ...er setting The installer can set the Max charging and discharging current values according to actual needs Meanwhile Use Battery V charged Smart Lithium should be ticked 1 Shut down Soluna system will shutdown if the battery voltage below this value 2 Low Battery Soluna system will alarm if the battery voltage below this value 3 Restart Restart level after Soluna System shutdown ...

Page 45: ...ue that GEN charges the battery after started Grid charge start V Grid will start when the battery voltage is less than the start V in the condition of off grid mode Grid charge current Current value that Grid charges the battery after started 5 2 Grid parameters setting Select the correct Grid frequency accordingly Otherwise Soluna system will not Work ...

Page 46: ...tick Grid Sell Under House load Back to Grid Tick Grid Sell Grid sell The energy generated by PV supply house loads and battery in priority excess energy would feed back to Grid Limited Power to load Tick it means output power depends on actual loads Limited power to home Tick it means output power depends on CT position ...

Page 47: ...47 53 5 3 Others Installer can find the Version information of Inverter hardware Software Solar Arc Fault on this is only for US market ...

Page 48: ...le PV string Can t be connected to 2 or more Soluna systems 3 Back up side can t be connected to Grid 4 Soluna system must be grounded Otherwise there might be possible to hazard personal safety besides it is probably to affect LCD s display 5 Water pump is not recommended to connect with Soluna S12EU 6 Air conditioners is not recommended to connect with Soluna S12EU A36 ...

Page 49: ...04 Ground fault GFID battery end grounding F05 Read the memory error F06 Write the memory error F07 GFDI Blown Fuse F08 GFDI Grounding contact failure F09 IGBT damage by excessive drop voltage F10 Auxiliary switch power supply failure F11 Ac main contactor errors F12 Ac auxiliary contactor errors F13 Grid voltage surge F14 DC firmware over current malfunction F15 AC firmware over current malfuncti...

Page 50: ...r voltage F44 AC Line W V low voltage F45 AC Line U V over voltage F46 AC Line U V low voltage F47 AC Over frequency F48 AC Low frequency F49 Phase U grid current dc current high F50 Phase V grid current dc current high F51 Phase W grid current dc current high F52 AC inductor A Phase current dc current high F53 AC inductor B Phase current dc current high F54 AC inductor C Phase current dc current ...

Page 51: ... one minute then turn on the DC AC switch again 3 Seek help from us if cannot go back to normal state F23 AC leakage current is transient over current Leakage current fault 1 Check the cable of PV module and inverter 2 Restart inverter 3 Seek help from us if cannot go back to normal state F24 DC insulation impedance failure PV isolation resistance is too low 1 Check the connection of PV panels and...

Page 52: ...ncy out of range 1 Check the frequency is in the range of specification or not 2 Check whether AC cables are firmly and correctly connected 3 Seek help from us if cannot go back to normal state F56 DC busbar voltage is too low Battery voltage low 1 Check whether battery voltage is too low 2 If the battery voltage is too low using PV or grid to charge the battery 3 Seek help from us if cannot go ba...

Page 53: ... the user who want use the diesel generator AC function please contact to us following the engineers instruction to operate 9 Contact us If any questions for Soluna system please contact us SOLUNA Add No 3492 Jinqian Road Shanghai China 201406 Tel 86 21 57475835 Email sales solunabattery com Web www solunabattery com ...