background image

Reset to Factory Default Instructions

Mounting Instructions

SOLO temperature controllers can be mounted through a cutout in an enclosure or panel by using the dimen-

sions shown in Section 5. The directions for mounting the controller through a cutout are:
1. Insert the temperature controller through the panel cutout.
2. Slide the M3X0.5 nut into the opening in the top of the mounting bracket and insert the M3X0.5 X 30mm 

mounting screw in the mounting bracket.
3. Insert the mounting brackets into the mounting groove at the top and bottom of the controller, and push the 

mounting bracket forward until the bracket stops.
4. Tighten top and bottom screws evenly to secure temperature controller in place.

2

1

3

4

6

WARNING! Electric shock danger

To prevent electric shock, do not connect AC power to your device until all input and output 

connections are completed.

SL9696-RRE

SL9696-LRE & SL9696-VRE

SL9696-CRE

Terminal Identification

7

Display, LED and Key Pad

9696

PV

SOLO

SV

SET

OUT1 OUT2 ALM1

AT

ALM2 ALM3

F

C

PV Display: To display the process value or parameter type.
SV Display:  

To display the set point, parameter operation read value 

manipulated variable or set value of the parameter.

AT: Auto-tuning LED, flashes when the Auto-tuning operation is ON.
OUT1 / OUT2: Output LED, lights when the output is ON.
ALM1 / ALM2 / ALM3: Alarm output LED, lights when that alarm is on.
°C, °F: Temperature unit LED. °C: Celsius  °F: Fahrenheit

8

10

All of the following set up instructions are for setting up a controller from the factory defaults. If the 

application for a controller needs to be changed, reset the controller to factory default using the following 

steps.

1. Press the

 

 button until the parameter 

loC

 

appears. Use the 

.

 button to select 

loC1

. Press the 

;

 button.

2. Press and hold the 

,

 and 

.

 buttons simultaneously for one second and release.

3. Press the 

 button repeatedly until the PV display shows 

pass

. Use the 

,

 button to change the value 

on the SV display to 

1357

. Press the 

;

 button.

4. Cycle power on the Controller to reset to factory default mode. All user set values are erased.

Key Pad Operation

Operation Mode

SET

Hold for 3 sec.

SET

Initial Setting

Mode

Regulation

Mode

SET

Press for less

than 3 sec.

Initial Setting

Parameters

Operation

Parameters

Regulation
Parameters

SET

The SOLO temperature controller has three function modes: Initial Setting mode, Operation mode and Regulation 

mode. When power is first applied to the temperature controller, the module information splash screen appears. 

This screen shows the firmware version on the PV display and the two output types for that particular model on 

the SV display. After three seconds, the controller will automatically proceed to the Operation mode main screen. 

Press and hold the 

;

 button for three seconds to go into the Initial Setting mode. Press the 

;

 button for less 

than three seconds to access the Regulation mode. Press the 

 button while inside any of the three function 

modes to access the individual parameters for each function mode. Use the 

.

 and 

,

 buttons to change the 

individual parameter values. Pressing the 

;

 button saves the parameter values. Press the 

;

 button again 

to return the controller to the Operation mode.

9

SL9696-LVE

SL9696-CVE

SL9696-VVE

Set Button: Press this key to select the desired function mode and 

confirm the setting value.

Rotate Button: Press this key to select parameters within the function 

mode.

Down Button: Press this key to decrease values displayed on the SV 

display. Hold down this key to speed up the decrement.

Up Button: Press this key to increase values displayed on the SV 

display. Hold down this key to speed up the increment.

1. Access the Initial Setup mode by pressing and holding the 

;

 button for three seconds. In the parameter 

inpt

, use the 

,

 and 

.

 buttons to select the value that corresponds to the thermocouple or RTD type 

that will be attached to the controller. See the table below for specifications. Press the 

;

 button to save the 

selected value. The controller will display the module information splash screen for three seconds and then 
return to the main screen.
2. Press the 

;

 

button for three seconds again. Press the 

 button to access the 

tpun

 parameter. Use 

the 

,

 and 

.

 buttons to select either 

C

 for Centigrade or 

f

 for Fahrenheit display. Press the

 

;

 button 

to save the selected value. The controller will display the module information splash screen for three seconds 
and then return to the main screen.
3. Press the 

;

 

button for three seconds again. Press the 

 button repeatedly until the 

tp-H

 parameter 

appears. Use the 

,

 and 

.

 buttons to set the maximum value of the operational temperature range. In 

operation, if the PV value is higher than the TP-H value, the PV display flashes to indicate an error and the 
controller outputs shut off. The SV value cannot exceed the TP-H value. Press the 

;

 button to save the 

selected value. Press the 

 button to access the 

tp-l

 parameter. Use the 

,

 and 

.

 buttons to set 

the minimum value of the operational temperature range. In operation, if the PV value is lower than the TP-L 
value, the PV display flashes to indicate an error and the controller outputs shut off. The SV value cannot be set 
lower than the TP-L value. Press the 

;

 button twice to save the selected value and return to the controller 

main screen.
4. Press the 

 button repeatedly until the parameter 

sp

 

appears. Use the 

,

 and 

.

 

buttons to select 

either 

0

 

for a whole degree or 

1

 for a tenth degree temperature display.* Press the 

;

 button twice to save 

the selected value and return to the controller main screen.
5. If the input temperature from the thermocouple or RTD needs to be adjusted, press the 

;

 button for less 

than 3 seconds. Press the 

 button repeatedly until the parameter 

tpof

 appears. Use the 

,

 and 

.

 

buttons to adjust a positive or negative offset to the PV value displayed on the controller. Press the 

;

 button 

twice to save the selected value and return to the controller main screen.

*Note: The decimal point display cannot be adjusted for B, S, and R type thermocouples.

Thermocouple or RTD Input

Thermocouple* Type and Temperature Range

Input Temperature Sensor Type

LED Display

Temperature Range

Thermocouple TXK type

txk

-328 ~ 1472°F (-200 ~ 800°C)

Thermocouple U type

u

-328 ~ 932°F (-200 ~ 500°C)

Thermocouple L type

l

-328 ~ 1562°F (-200 ~ 850°C)

Thermocouple B type

b

-212 ~ 3272°F (100 ~ 1800°C)

Thermocouple S type

s

32 ~ 3092°F (0 ~ 1700°C)

Thermocouple R type

r

32 ~ 3092°F (0 ~ 1700°C)

Thermocouple N type

n

-328 ~ 2372°F (-200 ~ 1300°C)

Thermocouple E type

e

32 ~ 1112°F (0 ~ 600°C)

Thermocouple T type

t

-328 ~ 752°F (-200 ~ 400°C)

Thermocouple J type

j

-148 ~ 2192°F (-100 ~ 1200°C)

Thermocouple K type

k

-328 ~ 2372°F (-200 ~ 1300°C)

RTD Type and Temperature Range

Input Temperature Sensor Type

LED Display

Temperature Range

Platinum Resistance (Pt100)

pt

-328 ~ 1112°F (-200 ~ 600°C)

Platinum Resistance (JPt100)

jpt

-4 ~ 752°F (-20 ~ 400°C)

*Note: Use only ungrounded thermocouples.

11-1

Sensor Input

Power Input

0 – 10 VDC

4 – 20 mA

2-wire RTD

Thermocouple

3-wire RTD

AC Powered 

Models

DC Powered 

Models

24 VDC power for models with 

–D suffix only

Summary of Contents for SL9696-RRE

Page 1: ...ungrounded thermocouples Analog input impedance 1 8MΩ Safety Information WARNING To minimize the risk of potential safety problems you should follow all applicable local and national codes that regulate the installation and operation of your equipment These codes vary from area to area and it is your responsibility to determine which codes should be followed and to verify that the equip ment insta...

Page 2: ...e Down Button Press this key to decrease values displayed on the SV display Hold down this key to speed up the decrement Up Button Press this key to increase values displayed on the SV display Hold down this key to speed up the increment 1 Access the Initial Setup mode by pressing and holding the button for three seconds In the parameter inpt use the and buttons to select the value that correspond...

Page 3: ...ange 0 50mV Analog Input mv 999 9999 0V 10V Analog Input v10 999 9999 0V 5V Analog Input v5 999 9999 11 3 12 1 12 2 Cooling Loop with ON OFF Control 1 Access the Initial Setup mode by pressing and holding the button for three seconds Press the button repeatedly until the parameter Ctrl appears Use the and buttons to select onof for ON OFF control Press the button to save the value Press the button...

Page 4: ...e the and buttons to change this value if desired Press the button to save the selected value Press the button to access the parameter dead Use the and buttons to enter a deadband zone value around the setpoint where the output is not effected by the proportional control value As long as the PV remains within the deadband zone the output is not affected by the proportional control The integral and...

Reviews: