Green Power Function
Ultima UPS is equipped with green power function. For saving power and protecting
battery, this method of deep discharging protection is adopted on inverter mode.
Free power monitoring software on CD
• Choose the operation system you need and follow the instructions described on the
CD to install the software.
Note
: If you find the communication unsuccessful after monitoring software installation,
you have to switch the Auto Search on and you can only do that if you go into 'Act as
Administrator'. Once selected, the software will hunt for and find the UPS.
Note
: The power switch must be kept in the ‘ON’ position, otherwise, the UPS will be
disabled and your equipment will not be protected during a power failure.
Note
: If you change your UPS model, please ensure you uninstall and reinstall the Software.
Troubleshooting guide:
©Sollatek (UK) Limited 1996 All Rights Reserved. SOLLATEK and the SOLLATEK device are the trade marks of the Sollatek group of companies.
Sollatek (UK) Ltd.
Unit 10, Poyle 14 Industrial Estate, Newlands Drive, Horton Road, Poyle, Slough, Berkshire SL3 0DX, UK
Tel: +44 (0) 1753 688300
Fax: +44 (0) 1753 685306
Technical support: [email protected]
Sales: [email protected]
www.sollatek.com
Rev. no. 1.0 April 07.
Problem
Possible Cause
Solution
No LED display on the front panel.
1. Battery weak.
1. Re-charge battery up to 8 hours.
2. Battery defect.
2. Replace with the same type of battery.
3. Power switch is not pressed.
3. Press the power switch again.
Alarm buzzer beeps continuously when AC supply is normal.
UPS overload.
Verify that the load matches the UPS capability specified in the
specs.
When power failure, back-up time is shortened.
1. Overload of the UPS.
1. Remove some noncritical load.
2. Battery voltage is too low.
2. Charge battery 8 hours or more.
3. Battery defect due to high temperature
operation environment, or improper
operation to battery.
3. Replace with the same type of battery.
Communication lost between UPS and computer
1. Software is not properly installed
1. Check the setting of the software
2. Interface cable is not properly connected
2. Check the interface cable is properly connected to the COM1/COM2 of
the computer and confirm the setting again
Mains normal but UPS is not working.
1. Circuit breaker has tripped.
1. Reset the circuit breaker.
2. Power cord is loose.
2. Reconnect the power cord properly.
Proper care of batteries
• Do not subject the battery to heavy vibration or mechanical shock.
• When you receive a new battery, charge fully before use.
• Full capacity will be reached after 2 or 3 full charge/discharge cycles.
• To obtain maximum life, always store batteries in a charged state.
• When storing batteries, re-charge every 6 months to prevent damage through self
discharge. This should be done more often if storage temperature exceeds 25ºC.
• Try to store / use in a cool, dry place. Do not expose to excessive hot
or cold (i.e. outside the range 10-35°C ambient temp).
• To prolong battery life, try to avoid the complete discharge
of your battery before recovery charge.
• Do not discharge a battery deeper than you have to.
• Do not attempt to dismantle a battery. They do not require topping up.
• Do not incinerate batteries. Always recycle old batteries.
• To avoid the risk of shock, do not touch the terminals.
• Keep terminals free from dirt and corrosion.
• Do not short the connections.
• Always charge in a ventilated area.
• Always use a suitable charging device. If unsure, contact your distributor.
• Replace only with Sollatek recommended replacement batteries.
If unsure, contact your distributor.
MODEL
Ultima 1000
Ultima 1400
Ultima 2000
CAPACITY
VA/W
1000VA/600W
1400VA/840W
2000VA/1080W
INPUT
Voltage
220/230/240VAC
220/230/240VAC
220/230/240VAC
Voltage range
89-145VAC/160-290VAC
166-280VAC
166-280VAC
Frequency
50 or 60 Hz
50 or 60 Hz
50 or 60 Hz
OUTPUT
Voltage
220/230/240VAC
220/230/240VAC
220/230/240VAC
Voltage regulation
(batt. mode)
+/-10% at load <50%
+/-10% at load <50%
+/-10% at load <50%
Frequency
50Hz or 60Hz
50Hz or 60Hz
50Hz or 60Hz
Frequency regulation
(batt. mode)
+/-1 Hz
+/-1 Hz
+/-1 Hz
Output waveform
modified sinewave
modified sinewave
modified sinewave
BATTERY
Battery type and number 12V/7AH x 2pcs
12V/9Ah x 2pcs
12V/9Ah x 2pcs
Recharge time
10 hours 6 hours (to 90% after complete discharge)
6 hours
TRANSFER TIME
Typical
4-6 ms
4-8 ms
4-8 ms
INDICATOR
AC mode
The first green LED lighting
The second to fifth green LEDs gradually lighting, indicating
load level
Battery mode
The first green LED flashing
The second to fifth green LEDs gradually lighting, indicating
battery capacity
FAULT
Red LED lighting
AUDIBLE ALARM Battery mode
sounding every 10 seconds
Low battery
sounding every second
Overload
sounding every 0.5 second
Battery replacement
sounding every 2 seconds
Fault
continuously sounding
PROTECTION
Full protection
overcharge
overcharge
overcharge
and overload protection
and overload protection
and overload protection
PHYSICAL
Dimension (mm)
D x W x H
405 x 145 x 205
405 x 145 x 205
405 x 145 x 205
WEIGHT
Net weight
9.6kgs
9.7kgs
9.8kgs
ENVIRONMENT
Operating environment
0- 40°C, 0-90 % relative humidity
(non-condensing)
Noise level
Less than 50dB
INTERFACE
RS-232 Windows family, Sun Solaris, IBM Aix, Compaq True64, UnixWare, FreeBSD, HP-UX, Linux, MAC
USB
Windows 98/2000/ME/XP
Specifications
Battery replacement
WARNING: Disconnect all sources of supply before replacing battery.
1. REMOVE THE FRONT
PANEL
Locate screw on under-
side of front fascia, and
remove. The front fascia
will now lift upwards.
2. REMOVE THE
METAL BATTERY
COVER PLATE
Slide it upwards
and outwards.
Put it to one side.
3. REMOVE THE BATTERY
After removing battery cover
plate, gently pull out the battery.
Disconnect the two wires that are
connected to the UPS.
Replacement battery installation
is the reversal of this procedure.
Ensure the wires on the battery
are connected back exactly
the way they were connected
originally. Caution! UPS may
get damaged if these wires are
connected incorrectly - if in
doubt, contact Sollatek.
• Replace only with Sollatek recommended replacement batteries.
If unsure, contact your distributor.
CHARGE THE UPS AT LEAST 8 HOURS BEFORE USE, ENSURING
THE BATTERY LEVEL INDICATOR IS FULL
TM
t h e p o w e r t o p r o t e c t
Ultima battery back-up times
(in minutes)
200VA
300VA
400VA
600VA
800VA
1000VA 1200VA
1400VA 1600VA 1800VA
Ultima1000
45
25
15
8
<5
3
Ultima 1400 58.5
37.3
25
13.5
8.25
4.7
3
1.5
Ultima 2000 58.5
37.3
25
13.5
8.25
4.7
3
1.5
0.5
<0.5