The ports 5-6, 7-8 and 9-10 are the CT cable connections. Please ensure 

the CTs are connected with the correct polarity and the corresponding 

grid phase. Also, please note the small arrow inside the CTs, as shown in 

Figure 5, shall be pointed towards the Grid (5-6 to La, 7-8 to Lb, 9-10 to 

Lc) as shown in Figure 4.

Step 1: 

1,2,3 and 4 are the voltage detection ports. Please connect the ports with 

the corresponding grid phases (1 to La, 2 to Lb, 3 to Lc, 4 to N) as shown in 

Figure 4.

Step 2: 

Figure 5: CT directional arrow

12 and 13 are the auxiliary power source of the meter, 13 should be 

connected to the Neutral Wire(N) while the 12 should be connected to 

line La on the inverter backup output as shown in Figure 4 and Figure 3. 

Step 3: 