NOTE:
This function is for technicians use only.
Press the UP/DOWN keys to select the standard (AS4777, VDE4105, VDE0126, UL-240V-A,
UL-208V-A, UL-240V, UL-208V, MEX-CFE, G83/2 (for 1-3.6kW models), G59/3 (for 4-5kW
models), EN50438 DK, EN50438 IE, EN50438 NL and “User-Def” function). Press the
ENTER key to confirm the setting. Press the ESC key to cancel changes and returns to
previous menu.
Selecting the “User-Def” menu will access to the following submenu (see Figure 6.16),
Figure 6.16
Below is the setting range for “User-Def”. Using this function, the limits can be changed
manually.
NOTE:
The " User-Def" function can be only used by the service engineer and
must be allowed by the local energy supplier.
OV-G-V1: 220---290V OV-G-F1: 50.2-53Hz(60.2-64Hz)
OV-G-V1-T: 0.1---9S OV-G-F1-T: 0.1---9S
OV-G-V2: 220---290V OV-G-F2: 50.2-53Hz(60.2-64Hz)
OV-G-V2-T: 0.1---1S OV-G-F2-T: 0.1---9S
UN-G-V1: 90---210V UN-G-F1: 47-49.5Hz(56-59.8Hz)
UN-G-V1-T: 0.1---9S UN-G-F1-T: 0.1---9S
UN-G-V2: 90---210V UN-G-F2: 47-49Hz(56-59.8Hz)
UN-G-V2-T: 0.1---1S UN-G-F2-T: 0.1---9S
OV-G-V1: 260V
OV-G-V1-T: 1S
Press the UP/DOWN keys to scroll through items. Press the ENTER key to edit the
highlighted item. Press the UP/DOWN keys again to change the setting. Press the ENTER
key to save the setting. Press the ESC key to cancel changes and returns to the previous
menu.
6.5.2 Grid ON/OFF
This function is used to start up or stop the power generation of Solis Mini Single Phase
4G Inverter (see Figure 6.17).
Grid ON
Grid OFF
Figure 6.17 Set Grid ON/OFF
Screens can be scrolled manually by pressing the UP/DOWN keys. Press the ENTER key
to save the setting. Press the ESC key to return to the previous menu.
This function is used to set the new password for menu “Advanced info.” and “Advanced
information” (see Figure 6.18).
Enter the right password before set new password. Press the DOWN key to move the
cursor, Press the UP key to revise the value. Press the ENTER key to execute the setting.
Press the ESC key to return to the previous menu.
6.5.4 New Password
Figure 6.18 Set new password
YES=<ENT> NO=<ESC>
Password: 0000
6.5.3 Clear Energy
Clear Energy can reset the history yield of inverter
These two functions are applicable by maintenance personnel only, wrong
operation will prevent the inverter from working properly.
6.5.5 Power control
Active and reactive power can be set through power setting button.
There are 5 item for this sub menu:
1. Set output power 2. Set Reactive Power 3. Out_P With Restore
4. Rea_P With Restore 5. Select PF Curve
This function is applicable by maintenance personnel only, wrong operation
will prevent the inverter from reaching maximum power.