SPECIFICATIONS & DIMENSIONS
Specifications may be subject to change without notice.
INDOOR UNIT
SPECIFICATIONS
Ventilation Type:
Static plate, heat and humidity transfer
Typical Airflow Range:
40-110 CFM
Unit is HVI Tested/Certified per CSA C439
Protocol:
Using one L-100 G5 Core
Standard Features:
White painted cabinet
Line-cord power supply
Low-voltage circuit for controls
Unit may be mounted in any orientation
Cross-core differential pressure ports
Controls:
Onboard 24 VAC transformer/relay package
with switched dry contacts
Filters:
Total qty. 2, MERV 8, spun-polyester media:
21 3/4" x 10 1/2" x 1"
Unit Dimensions & Weight:
22 1/2" L x 24" W x 23 3/4" H
51 lbs.
Max. Shipping Dimensions & Weight (in carton):
33" L x 22" W x 29" H
65 lbs.
Motor(s):
Qty. 2, Standard motorized impeller blowers
Accessories:
Backdraft damper 6", 8"
Automatic balancing damper 4", 5", 6"
Louvered wall vent 6" - white, brown
Carbon dioxide sensor/control - wall mount (CO2-W)
IAQ sensor - wall mount (IAQ-W)
Motion occupancy sensor/control -
ceiling mount (MC-C), wall mount (MC-W)
Percentage timer control (PTL)
Push-button point-of-use controls (PBL), PTL req’d.
Percentage timer control with furnace interlock (FM)
MERV 13 filter - OA airstream
Electric duct heater - RH series (1-11.5 kW);
designed for indoor ductwork installation only
11 5/8" Typ.
24 1/4" Overall (with Hanging
Bracket)
18" Case
22 1/2"
Overall
2 1/4" Typ.
24V AC
Control
Terminal
6 1/4" Typ.
11 3/4" Typ.
5 3/4" Typ.
OA
EA
RA
FA
34" Line Cord
Pressure Ports
(4) Typ.
23 3/4" Overall
23 5/8"
Case
22 1/4" Minimum
Service Area
(Door can be
Removed from
Hinges.)
22 1/4" Minimum
Service Area
Door
Swing
8" Nominal
Typ.
6" Nominal
Typ.
7/8" Typ.
2 5/8"
21 7/8" Case
25 1/2" Overall
(with Hanging Bracket)
Formed
Inlet Ring
LEFT VIEW
FRONT VIEW
RIGHT VIEW
TOP VIEW
Model: EV90P
Drawing Type: Unit Dimension
Version: JUN18
ABBREVIATIONS
EA: Exhaust Air to outside
OA: Outside Air intake
RA: Room Air to be exhausted
FA: Fresh Air to inside
INSTALLATION ORIENTATION
Unit may be installed in any
orientation.
NOTE
1.UNLESS OTHERWISE SPECIFIED,
DIMENSIONS ARE ROUNDED TO THE
NEAREST EIGHTH OF AN INCH.
2.SPECIFICATIONS MAY BE SUBJECT
TO CHANGE WITHOUT NOTICE.
UNIT DIMENSIONS
AIRFLOW ORIENTATION
Available as shown in dimension drawing.
UNIT MOUNTING & APPLICATION
Can be mounted in any orientation. RA/EA airstream
can be switched with OA/FA airstream.
ELECTRICAL DATA
HP
Volts
HZ
Phase
Input Watts
FLA
0.03
120
60
Single
44 @ 90 CFM
0.35
CORE PERFORMANCE
Airflow CFM
Temp EFF%
Total EFF%
Winter/Summer*
42
86
83/71
56
85
82/70
73
84
80/68
87
83
79/67
99
82
78/66
108
82
78/65
Note:
Indirect Gas-Fired Duct Furnace is not available on the EV90P.
90P
EV
Energy Recovery Ventilator
Standard
Download specification at:
renewaire.com/specifications
UNIT PERFORMANCE
Airflow CFM
ESP in H
2
0
42
0.60
56
0.50
73
0.40
87
0.30
99
0.20
108
0.10
Note:
These are core-only ratings and are not HVI certified.
HVI ratings apply to complete units only.
See HVI certification ratings on pg. 24 of Single/Multi-Family Catalog.