Rapid Shutdown Combiner Installation and Operation Guide (Rev B)
DOCR-070566-B
Fig.2 Front View of Solectria RSD Combiner
When the inverter loses utility power, the DC output conductors between the RSD
Combiner and the inverter become de-energized below 30V within 10 seconds. The
utility power can be cut off at any point upstream of the inverter to allow the
contactors to open inside the RSD Combiner, ensuring there is no high voltage DC
between the inverter and the RSD Combiner.
The PV system with rapid shutdown ability shall be properly labeled according to NEC
690.56 (C). The sign/label should be right at the service entrance and match the sample
below (text and color scheme).
PHOTOVOLTAIC SYSTEM
EQUIPPED WITH
RAPID SHUTDOWN
Sealing Cap
PV
Connector
PV Wire
Cable Gland
Hole Plug
M4 Torx Scews × 4
Equipment
Ground
Bracket
Mounting Holes
Output
Terminal Block
5V Signal
Terminal Block
Hole Plug
Fuse & Fuse Housing
Ground Stud
Inside the Box