PVI13KW Installation and Operation Manual
DOC-020028 rev 006
23
Unit over heating, power derating, or unit not putting out power
•
Check insect screens in front louver grill on main enclosure door for clogging from dust,
pollen and debris. The louver/grill can be removed with 8 Philips screws holding it on
and insect screen can be cleaned or replaced (Solectria Renewables P/N HDW-150005-
001)
•
Fan not running, blocked or slow
o
Check fan fuse inside main enclosure (1A) AC
o
Check fan relay inside main enclosure
o
Check the fan, make sure it spins freely (when unit turned off)
•
No grid sensing
o
Grid sensing fuses blown (0.1A) AC inside main enclosure. Contact Solectria
Renewables (Do not replace fuses, as this represents an abnormal failure).
•
No LED indications when sun is shining. If grid voltage and DC (PV) voltage is present
and no response from inverter is evident
o
Verify AC & DC (PV) voltages are within proper ranges
o
Verify fuses in AC & DC (PV) disconnect (If equipped with PV Combiner) are
good
If at some point it is determined that the unit or any part of the unit should be shipped to
Solectria Renewables for repair or replacement, be sure to get an RMA# from Solectria
Renewables and use the same packing method as when it was shipped to you, or request
instruction on packing and/or packing materials from Solectria Renewables to help insure a safe
shipment.
Opening the Main Enclosure
Normally the main enclosure (or disconnects) will not have to be opened for any reason by the
user. If opening the unit is necessary follow these guidelines:
WARNING:
The inverter should only be opened by qualified service technician.
WARNING:
Only open the inverter when clear and dry outside if the inverter is
outdoors.
WARNING:
Both DC and AC disconnects must be in the off position and wait 60
seconds after the LED indicators are off before opening as electrolytic capacitors on
the internal DC “bus” are discharging during this time.
•
Switch off DC disconnect
•
Switch off AC disconnect (and AC building panel circuit breaker if desired)
•
Watch until all LED indicators have been off for 60 seconds (if not already off)
•
Use a large flat screwdriver or coin to turn latches ¼ turn counter-clockwise
See Fig. 9 and “Inside the Main Enclosure You Will See” section.