Note: The inverter terminal communication lines are carried out in strict accordance with the color sequence of the above lines. If you use it with SolaX's
X1-Hybrid G4 /X3-Hybrid G4 series, please pay attention to the communication control of pins 3, 6, 7 and 8; For use with SolaX grid-connected inverter series,
please pay attention to pin 3 and 6 communication control.
Connect the Adapter box to the inverter
1. Insert the cables through the glands.
2. Make cables
, insert it into the RJ45 connecter in the box and tighten the waterproof terminal.
(
Conventional
Communication cable
,
Stripping cable length: L = 15.00mm)
3
.Press the wire on the other side according to the inverter quick installation requirements and insert it into the inverter port.
(Refer to the quick installation manual of the corresponding inverter for speci c details)
Connect the Adapter box to the Heat pump
4. First remove the green terminal block in the adapter box,the connect the cables to the through-hole terminals and tighten them.
( Wire speci cations: outer diameter(3.5-5.5) mm, stripping cable length: L = 7.00mm).
5.The wiring on the other side is inserted into the port according to the quick installation requirements of the heat pump.
(Please refer to the quick installation manual of the corresponding heat pump)
Setting
614.00620.00
COM/RS485 PIN Definition
Ø
1
2
3
4
5
6
7
8
1
8
GND
X
Drycontact_A(out) Drycontact_B(out)
+13V
X
X
X
IV
User settings
Settings
Dry Contact
Load Managemment
Menu
Manual
Disable
Smart
Save
Switch
Feedin Power
... ...
Thresholds on
Feedin Power
3000W
Load Management
>
Thresholds off
Battery Soc
40%
Work Period 1
Start Time
Work Period 1
End Time
Work Period 2
Start Time
Work Period 2
End Time
-
To use the heat pump function, users need to set the inverter LCD screen, press the following menu to enter:"Load Management",select
"Smart save" to set.
Load Management
Load Management
>
Maximum duration
per day
900min
Load Management
>
Minimum duration
per on-signal
5min
Load Management
>
Schedule
Disable/Enable
Load Management
>
Thresholds off
Consumption
500W
Load Management
>
Load Management
>
Load Management
>
Load Management
>
(b)
(d)
(e)
(f )
(h-1)
(h-3)
(h-4)
(a) If you want to turn off the adapter box function, you can set "Disable" here to turn it off.
Manual setting: (b) Manual mode switch, you can set it to on or off here.
Smart save settings: (c) User can set the feed-in power threshold here. Once the feed-in power is greater than or equal to the set value, the adaptor box will turn
on to make the heat pump work in mode 3.
(d) User can set the consumption power threshold here. Once the power consumption is greater than or equal to the set value, Adapter box will turn off to
make heat pump work in mode 2.
(e) User can set the battery capacity threshold here. Once the battery capacity drops to the set value, the adapter box will turn off to make the heat pump work
in mode 2.
(f ) User can set the minimum duration time that the heat pump will continue to run in mode 3 once the condition (c)is triggered.
(g) User can set the cumulative time of operation mode 3 in one day. If this value is exceeded, the adapter box will not turn on even if condition (c) is met.
(h) Users can set two working
time periods for the operating mode 3.( In other time periods, the adapter box will be turned on/off according to the
( c)/(d)/(e))
(h-1)/(h-2)/(h-3)/(h-4) Here you can set the start time and end time of operation mode 3.
(c)
(h-2)
1
)
2)
N
O
1
2
3
N
O
1
2
3
-
All Smart Grid Ready heat pumps have four controllable operating modes. SolaX recommends switching between operating modes 2
and 3.
The switching is realized by an external relay, which is controlled by the SolaX inverter.
Operating mode
4
)
02
>
Switch
ON/OFF
Load Management
>
(a)
NO
1
2
3
Finally,
assemble the upper cover of the SolaX Adapter Box.
(g)
CAN
Meter/CT
COM/LCD
DRM
B
MS
Upgrade
Meter/CT
COM/LCD
3)
Heat
pump
NO
1
2
3
1 2 3 4 5 6 7 8
1) White with orange stripes
2) Orange
3) White with green stripes
4) Blue
5) White with blue stripes
6) Green
7) White with brown stripes
8) Brown
NO
1
2
3
Slotted screwdriver
torque:
0.4
±
0.1Nm
Figure A: If used with SolaX X1-Hybird G4 / X3-Hybrid G4 series, please set the
three DIP switches to the "OFF" position, which is usually the factory default state;
Figure B: If it is used in the SolaX grid-connected machine series, please
turn the three DIP switches to the "ON" position. If you need to match inverter and adapter box, please contact our SolaX team.
Switch settings
A
:
B
:
Ø
5
)
Slotted screwdriver
torque:
0.5
±
0.1Nm
Mode Select
Disable
Load Management
>
(h)
In this operating mode, the heat pump runs in standard operation. To activate this operating state, the external relay for controlling the
heat pump remains open.
In this operating mode, the heat pump operates within the regulator in the intensi ed operation for hot water generation and / or room
heating. This is not a direct start-up command, but an activation recommendation corresponding to the available PV power. In order to
activate this operating state, the external relay is closed.
Operating mode 3
– increasing temperature mode
Operating mode 2
–
standard operation