Reactive power control, Reactive standard curve cos
φ
= f(P)
0.5
0.2
1.0
0.95
0.95
cos
φ
capac
tive
induc
tive
f (P)
curve C
For VDE ARN 4105, curve cos
φ
= f(P) should refer to curve A. default value of setting is as
shown in curve A.
For E 8001, curve cos
φ
= f(P) should refer to curve B. default value of setting is as shown in
curve B.
For CEI 0-21, default value of PFLockInPoint is 1.05, when Vac > 1.05Vn, and Pac> 0.2 Pn,
curve cos
φ
= f(P) should refer to curve C. Default value of PFLockOutPoint is 0.98, when Vac
< 0.98 Vn, cos
φ
= f(P) will exit curve C.
Reactive power control, Reactive standard curve Q= f(V)
Q
V
Qmax
-Qmax
V2s
V1s
V1i
V2i
V2i=0.90Vn
V2s=1.10Vn
V1s=1.08Vn=QuVlowRate
V2i=0.92Vn=QuVlowRate
0.9
0.9
Upper limit
capac
tive
induc
tive
f (P)
Lower limit
Power Lower
Power Upper
curve A
0.3
0.7
0.9
0.9
Upper limit
capac
tive
induc
tive
f (P)
Lower limit
Power Lower
Power Upper
curve B
0.3
0.7
0.2
0.8
d-1-3) Grid
The enduser do not need to set the grid parameters. All default value has set on
factory according to safety rules.
If need to reset, any changes should according to the requirement of local grid.
Parameter
Comment
Normally
Vac upper
Voltage high protect
Vac lower
Voltage low protect
Vac upper slow
Voltage high slow protect
Vac lower slow
Voltage low slow protect
Fac upper
Frequency high protect
Fac lower
Frequency low protect
Fac upper slow
Frequency high slow protect
Fac lower slow
Frequency low slow protect
Vac 10m avg
10 min voltage high protect
Apply to Italy(CEI0-21) only.
Tuvp_Fast
Overvoltage protect fast time
Tovp_Fast
Undervoltage protect fast time
Tufp_Fast
Overfrequency protect fast time
Tofp_Fast
Underfrequency protect fast time
Tuvp_Slow
Tovp_Slow
Tufp_Slow
Tofp_Slow
FreDrpDlyTime
Overvoltage protect slow time
Undervoltage protect slow time
Overfrequency protect slow time
Underfrequency protect slow time
Frequency droop delay time
Apply to EN50438_NL only.
FreqSetPoint
FreqDropRate
Frequency set point
Frequency droop rate
Setting
Setting
52
53
d-1-4) Export control
This function allows the inverter able to control energy.There are user value and
factory value. The factory value is default which can not be charged by user. The
user value setting by installer must be less than the factory value.
Choose”Disable” means the function will be shut off.
User value:
Export Control
4000W