Solarwise SWF850 QuickStart/Troubleshooting Manual
10 / 73
Connector Type
Screw Type Terminal
Wire Size
AWG 12-30
,
length of exposed copper 6-7mm
Signal Type
Direct Voltage
Signal Range
0 – 5V
Accuracy
+1.0% Full Scale
The connection method for AI5 and AI6 is described as below.
SWF850
24V AI4 24V
24V AI1
+ -
AI3
AI2
24V
24VDC
4-Wire Type
Sensor
+
-
Sensor
Power Input
AI6
GND
GND AI5
2.4.4 Connecting to the Digital Input (DI)
SWF850 has a total of 6 digital inputs DI1 to DI6, DI_Vout is the built-in internal excitation voltage of
15V. DI input can be set to status input for monitoring the status of SPD or MCCB, also can be set to
pulse input for energy collection.
Connector Type
Screw Type Terminal
Wire Size
AWG 12-30
,
length of exposed copper 6-7mm
Signal Type
Digital Status Contact
Signal Range
15VDC
,
5mA
Isolation Capability 1000VAC, 1min.