Solaris photo catalyst module.
• Four self tapping screws
• 24VAC Power cord (attached)
•
UVC warning label
•
Replacement lamp log sheet
•
Warranty card
•
Ductboard plate / sealing tape
• Product gasket
Package Contents:
Safety Precautions:
It is recommended that this unit be installed and maintained by a trained technician.
WARNING:
UV Hazard. Always protect eyes from ultraviolet light. NEVER look at UV lamps in
operation. Unplug or disconnect power before re-lamping or servicing.
WARNING:
Severe eye damage or temporary blindness may occur.
WARNING:
DO NOT operate outside of air handler. Mount product in preferred
location first.
WARNING:
No openings should be allowed which would give direct line-of-sight to the UV light.
Note:
In the event of accidental breakage or replacement of the ultraviolet lamp, please ensure that
the lamp is disposed of in accordance with local and state environmental laws regarding fluores-
cent lamps containing mercury.
Notice:
All wiring inside of the air handler in direct line of site of the UV lamp must be shielded
with aluminum foil tape or equivalent non-combustible material. When installing this unit, select
a mounting location that prevents ultraviolet light exposure to synthetic or other plastic com-
ponents with unknown resistance to ultraviolet light. Ultraviolet light may cause color shift or
structural degradation of plastic internal components.
Mechanical installation
1.
Determine a location for the Solaris system. Mount the unit on the exit or supply side of the
HVAC system and before the ductwork branches off.
2.
Separate the module cover from the mounting plate.
3.
Note the orientation of the power module as it connects in only one direction.
4.
Mark a 4” round opening (or use the end of the PCO chamber to mark the area) on the air duct
and cut the hole needed for the insertion of the advanced photocatalytic chamber.
5.
(optional) attach supplied gasket over PCO module and attach to mounting plate. (Seals against
air duct.)
6.
Insert the mounting plate / PCO module into opening and attach to duct with two supplied self
-tapping screws in the lower left and upper right
(only).
7.
Adjust purification level. (See next page);
8. plug the lamp connector on to the lamp (note: the pattern of the lamp pins is a rectangle not a
square)
9.
Place the module cover on the unit aligning holes in tabs with holes in mounting plate (upper
left /lower right).
10..
Secure the power module to the mounting plate with the remaining two self-tapping screws.
Adjusting the Purification level
The Solaris is a universal air purifier with a patented design that provides adjustability to
the advanced photocatalytic process for a variety of treated space sizes. When setting up
your equipment, adjust the purification level (under electronics cover) to the appropriate
position based on the square footage Fine adjustments may be required depending upon
household living characteristics.
Lamp Replacement Procedure:
The UV lamp is shipped installed in the equipment and should
be replaced during an annual service. To replace the UV lamp
follow the steps below
:
1.
Unplug power cord and remove power module.
(See Fig. 1)
2.
Note the position of the Photon Clarifier and pull adjustment
bar to its full-out position.
(See Fig. 2)
3.
Remove lamp screws and pull lamp out of PCO module.
(See Fig. 3)
4.
Install new lamp and fasten with lamp screws.
5.
Set the Photon Clarifier to its noted setting.
6.
Place the power module on the unit and fasten.
7.
Plug in power cord.
Fig. 1
Fig. 2
Fig. 3
Installation
This product must be connected to a Solaris IAQ Module to operate.
1. Disconnect power supply before beginning installation to prevent electrical shock or
equipment damage.
2. plug the two leads from the photocatalytic module to the proper ports
3.. Check installation and reconnect power supply for proper operation.