5 Installation
5.12.1 Flue gas pipe: Hole for emission mea-
surement
►
Make the hole for the emission measurement
according to the following images (recom-
mendation according to standard).
►
If these specifications cannot be implemented,
then make the measuring point after a calming
section, i.e. after the longest straight section of
the pipe. The orientation of the pipe (horizontal,
vertical, angled) is of no significance here.
►
In any case, place the measuring point before
any existing draught stabilisers.
You can find the function for carrying out the emission
measurement in the boiler operation manual,
keyword:
Chimney sweep function
.
Flue gas pipe horizontal
Flue gas pipe vertical
5.13 Mounting ash container
Abb. 2-41
Check seal
►
Check that seal
1
is positioned correctly.
Abb. 2-42
i
Ensure that connection is correctly sealed.
Reliable measures must be taken to prevent
the intake of false air. Failure to observe this
can impair the performance of the burner.
Adjust height of ash container
Abb. 2-43: Latch in ash container
30
Installation manual
maximus L