l
If installing a single inverter:
o
20 cm (8") to the top of the inverter.
o
10 cm (4") to the bottom of the StorEdge Connection Unit.
o
10 cm (4") to the right and left of the inverter.
l
If installing multiple inverters:
o
When installing inverters one above the other, leave at least 20 cm(8") between the top of an
inverter and the bottom of the StorEdge Connection Unit.
o
When installing inverters side by side, leave 20 cm( 8") between inverters.
2. Position the mounting bracket against the wall/pole and mark the drilling hole locations :
o
Ensure that the flat side of the bracket is at the bottom, as in
o
Use at least two bracket holes. Additional holes can be used to fix the bracket. Determine which
and how many holes to use according to mounting surface type and material.
3. Drill the holes and mount the bracket. Verify that the bracket is firmly attached to the mounting
surface.
NOTE
When mounting an inverter on an uneven surface, you may use spacers/ washers behind the top
mounting hole of the bracket (see ). Depending on the angle, use the appropriate size and number of
spacers so that the bracket is perpendicular to the ground. Recommended: a stainless steel 3/4" long
screw, with a 1/4" socket button head , two jam nuts and three washers.
4. Hang the inverter on the bracket (see
): Lift the inverter from the sides, or hold it at the top
and bottom of the inverter to lift the unit into place. Do not lift holding the StorEdge Connection
Unit as it may be damaged
l
Align the two indentations in the inverter enclosure with the two triangular mounting tabs of the
bracket, and lower the inverter until it rests on the bracket evenly.
Figure 8: Hanging the inverter on the bracket
SolarEdge
StorEdge
-Single
Battery/High
Capacity
Installation
MAN-01-00283-
1.1
20
Mounting the Inverter