24VDC PRO-Verter 5000-220 Reprogramming Instructions
March 2020
|
Solar Stik
®
, Inc.
2
|
Entering the SETUP Menu When the PIN Is Set and Locked
A PIN has been set and the SETUP button menus are locked when the SETUP button is pressed and
the “Enter SETUP PIN = 0***” menu appears on the screen. The correct/original PIN (2014) must be
entered to access the menu. If the incorrect PIN is entered, “Invalid PIN” displays. There is no limit to
how many attempts can be made to enter the correct PIN.
To enter an existing PIN (from the Enter SETUP PIN = 0*** menu):
1. Rotate the SELECT knob to the correct digit, and then press the knob.
2. Repeat Step 1 to enter the remaining three digits of the existing PIN.
3. After pressing the SELECT knob for the last digit, access to the SETUP menu is permitted.
Info:
After the correct PIN has been entered, there is no need to reenter it to access another protected
menu—unless five (5) minutes have passed without any button push.
Changing an Existing PIN
The PIN can be changed at any time. First, go to the TECH: 05 SETUP PIN menu and then enter the
existing PIN to access the “Change PIN” menu item.
To change an existing PIN (from the 05 SETUP PIN menu):
1. Use the SELECT knob to enter the existing PIN (see procedure above).
2. After the existing PIN is entered and SELECT has been pressed for the last digit, the “Set SETUP”
options menu appears.
3. Rotate the SELECT knob to the “Change PIN” option, and then press the SELECT knob. The “Set
SETUP PIN” menu appears with the current PIN displayed and the first PIN digit blinking.
4. Enter a new four-digit PIN.
Note:
The number “0000” is not an option.
5. After pressing the SELECT knob for the last digit, the new PIN is set. The display will return to the
“Set SETUP PIN” menu where the SETUP button menus may be “locked/unlocked.
Resetting the PRO-Verter 5000 PIN
Access to critical PRO-Verter program settings is
protected by a personal identification number (PIN).
The PIN set at the Solar Stik Factory is the year
that is printed on the I-Plate, which corresponds
to the year that the PRO-Verter was manufactured.
The PIN can be changed to to any other suitable,
secure, four-digit number.
� 2016 Solar Sti� Inc. � rev 20161108
PSS-G Tower
PSS-G ALTERNATIVE ENERGY SYSTEM (AES) CONFIGURATION
NOTICE
DANGER
Electrical Hazard
Do not operate with lid open in wet environments. Keep in sheltered location with lid closed.
Do not operate on wet ground. Keep cables and Power Hub on dry surfaces.
24VDC Interconnect Strip 7
24VDC PRO-Verter 7000
24VDC Power Hub 2400
MEP-802A 5kW TQG
24VDC
Li Expander Pak 2400 (4)
PAMs (6)
(3) 24VDC Port
24VDC
Li Expander Pak 2400 (3)
24VDC Interconnect Strip 7
EMERGENCY STOP:
Turn off
POWER
switch on the
PRO-Verter 7000
and disconnect
both
Inter-
Connect Strips.
DO NOT STORE BATTERIES IN A DISCHARGED STATE!
Always recharge batteries completely
before storage or transport. Regular maintenance charging is critical.
DO NOT USE THE PRO-VERTER 7000 IN CONJUNCTION WITH A MODIFIED SINE WAVE AC
INPUT SOURCE.
The
AES
should be co-located next to the MEP-802A generators.
The
PAMs
should be positioned with a southern exposure and have an unobstructed view of the sky
to allow maximum direct sunlight onto the panel surfaces.
Use only the
FAVS
and
CRTL
menu
button on the
PRO-Verter 7000
control. The Setup menu might
be locked. Consult operations manual or contact Tech Support for unlocking instructions.
If the load requirement is at or close to the maximum rated output of the generator, the
PRO-Verter
7000
will not be able to properly charge the
Expander PAKs
, resulting in continuous generator
operation.
RESETTING FAULT CONDITIONS
Generator Fault:
Turn
GENERATOR CONTROL
to
OFF
and then
ON
or
AUTO
Over Current Condition:
Check CIRCUIT BREAKERS. If GREEN LED is not illuminated, press breaker to reset.
AC IN LED only is illuminated when generator is being used.
W116 Cable (Pr
ovided with PSS-G T
ower)
AC Input (P1)
SYSTEM INITIALIZATION AND CALIBRATION:
In order for the
AES
to operate properly and
at rated power, a minimum of 5 functioning
Expander Pak 2400 batteries need to be connected to the PRO-Verter 7000.
1. Set Clock
a. Rotate
SELECT
knob and press
SELECT
until proper time is programmed
2. Test the PRO-Verter and Generator operation:
a. Press
CTRL
button
b. Rotate
SELECT
knob to
�03 Gen Control�
and press
SELECT
c. Rotate
SELECT
knob until
"Generator ON"
appears on LCD and press
SELECT
i. �Remote Generator Start and Operation� sequence will begin (total process
may take up to 3 minutes).
NOTE:
The Audible �Start-�arning� Alarms will
sound when the PRO-Verter 7000 AGS is connected to an MEP-802A TQG. The
alarm will last for 10 seconds before the motor cranks
ii. Once the generator is operating, verify that the
AC IN
LED illuminates and that
the LCD displays
CHARGE MODE
within 90 seconds
iii. Verify that the generator stays operating for 5 minutes uninterrupted while the
CHARGE
mode is operating
d. Press
CTRL
button and rotate
SELECT
knob to
�03 Gen Control�
, press
SELECT
e. Rotate
SELECT
knob until
"Generator AUTO"
appears on LCD, press
SELECT
Initiali�ation complete � the generator will run until the batteries achieve full charge, and then
auto-stop. Normal cycling will begin with the generator operating only as necessary for
continuity of operation (keeping the batteries charged and the load functioning).
LOAD SUPPORT MODE
Load Support function can be used to provide higher power for raising the RAID/PSS-G tower.
In order for this function to work, the
GEN CONTROL
in the
CTRL
menu and the
INVERTER
mode must both be set to
ON
.
1. Press
CTRL
button
2. Scroll to
�03 Gen Control�
and press the
SELECT
a. Rotate SELECT knob until
ON
appears on the LCD and press
SELECT
3. Press
INVERTER
button to enable the inverter mode
Load Support function is now active. Deactivate
�03 Gen Control�
to disable Load Support.
MENU SETTINGS FOR NORMAL OPERATION
CTRL MENU
FAVS MENU
01 AC In Control
F1 - Battery Type
- Custom
- Auto Connect
02 CHG Control
- Set Absorb Volts = 29.0 V
- Set Float Volts = 29.0 V
- Multi-Stage
- Set EQ Volts = 29.0 V
03 Gen Control
- Set EQ Done Time = OFF
- AUTO
F2 - AmpHour size
- 700 Ah
F3 - AC Input
- Set Input Amps = 40 A
F4 -
LBCO
- Volts = 24.4 V
F5 - Gen Run VDC
- Set Start Gen Volts = 25.0 V
- Set Start Volts Delay = 15 sec
- Set Stop Gen Volts = Float
- Set Stop Volts Delay = 1 min
PN 10-1000443
Example of an Inset from the lower right corner
of the PRO-Verter I-Plate. This number may may
vary.
Please record the PIN chosen in a secure location for future reference.
Overriding an Unknown PIN
A previously-entered PIN can be overridden. When “PIN = 0***” displays, press and hold the SELECT
knob until “PIN = 0000” displays (approximately 7 seconds). Enter a new PIN number.