Meter type: Solar-Log™ PRO2

Connection diagramm

Connection diagram for different operating modes

Solar-Log™ PRO2 (RS485 oder S

0

) connection assignments

The meter connections are labeled IN (bottom) and OUT (bottom).

As consumption or sub-consumption meter: Connection to the grid (IN) – connection for appliances (OUT)

As inverter /production meter: Connection for the production (IN) – connection to the grid (OUT)

Solar-Log™ PRO2 connection assignments (only RS485)

As battery meter (bi-directional): IN = connection to the grid – OUT = connection to the battery 

Please note that only Solar-Log™ PRO2-Mod meters can operate on the RS485 interface (one or several). It 

is not possible to combine the operation with other components.

If the meter is the last device on the bus, it has to be terminated at connection block10 and 11 with a 

resistor (120 ohm / 0.25W). 

All display values of the meter

Change the meter from the automatically rotating display to the manual display by pressing the keys. 

Pressing on the keys here allows all of the available display values to be accessed in sequence. Please refer 

to the attached table for the menu navigation. If no keys are pressed after a short time, the meter reverts 

back to the automatic display mode.

Technical data

Nominal voltage

230 V AC

Current

5 (100) A

Frequency

50 Hz 

± 

10 %

Measurement

Active- and Reactive energy in forward and reverse direction

Accuracy class

B

Power consumption

≤ 10VA/Phase - ≤ 2W/Phase

Width

2 TE (35,8 mm)

Pulse Output LED

10 000 Imp/kWh

S

0

–pulse output:

1 000 Imp/kWh, 31ms

Temperature range

-40°C to +70°C

Max. rel. humidity

75 % average, 95 % short term

Registered harmonics:

0,05 – 0,25 kHz

LED blinking red

Consumption >4W, pulsrate= consumption

Display

5 + 2 Digits (99.999,11 kWh)

Max diameter

Mainclamps:  

max. 35 mm

2

Additional clamps:  

max. 2,5 mm

2

Baud rate ModBus

9.600 baud

Connection diagramm 1000 (DIN 43856)

Clamp 1

Input Phase „L1“

Clamp 3

Output Phase „L1“

Clamp 4

Neutral connection N (Input)

Clamp 6

Neutral connection N

Clamp 10, 11

ModBus-Connection

Clamp 12, 13

(Unallocated)

Clamp 18, 19

S

0

- pulse output „Forward“

Clamp 20, 21

S

0

- pulse output „Reverse“

Terminal block connector Solar-Log™ (RS485)

Solar-Log Base

PRO2

Terminal

Terminal

Terminal

1 ->

(A) 6 or (B) 10 (Data+)

10 (A)

4 ->

(A) 9 or (B) 13 (Data-)

11 (B)

Reviews: