Manual 2100-729
Page
32 of 40
TABLE 13
Electrical Specifications
Model
Rated Volts
& Phase
No.
Field
Power
Circuits
Single Circuit
Dual Circuit
j
Minimum
Circuit
Ampacity
k
Maximum
External
Fuse or
Ckt. Brkr.
n
Field
Power
Wire
Size
n
Ground
Wire
j
Minimum
Circuit
Ampacity
k
Maximum
External Fuse
or Ckt. Breaker
n
Field Power
Wire Size
n
Ground
Wire Size
Ckt. A Ckt. B Ckt. A Ckt. B Ckt. A Ckt. B Ckt. A Ckt. B
J18HB-A00, A0Z
A04
A08
230/208-1
1
1
1
15
36
57
20
40
60
12
8
6
12
10
10
J24HB-A00, A0Z
A04
A08
230/208-1
1
1
1 or 2
19
39
60
25
45
60
10
8
6
10
10
8
42
25
45
25
8
10
10
10
J24HB-B00, B0Z
B06
230/208-3
1
1
13
31
15
35
12
8
12
10
J24HB-C00, C0Z
C05
460-3
1
1
8
15
10
15
14
12
14
12
J30HB-A00, A0Z
A05
A10
230/208-1
1
1
1 or 2
24
50
76
35
60
80
8
8
4
10
10
8
50
26
50
30
8
10
10
10
J30HB-B00, B0Z
B05
B09
230/208-3
1
1
1
18
33
45
25
35
45
10
8
8
10
10
10
J30HB-C00, C0Z
C05
C09
C15
460-3
1
1
1
1
9
17
23
26
15
20
25
30
14
12
10
10
14
12
10
10
J36HB-A00, A0Z
A05
A10
m
A15
230/208-1
1
1
1 or 2
1 or 2
27
55
79
84
40
60
90
90
8
6
4
4
10
10
8
8
53
53
26
52
60
60
30
60
6
6
10
6
10
10
10
10
J36HB-B00, B0Z
B05
B09
B15
230/208-3
1
1
1
1
19
36
47
51
25
40
50
60
10
8
8
6
10
10
10
10
J36HB-C00, C0Z
C05
C09
C15
460-3
1
1
1
1
11
19
25
26
15
25
25
30
14
12
10
10
14
12
10
10
j
These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electrical code (latest version), Article 310
for power conductor sizing.
CAUTION
: When more than one field power circuit is run through one conduit, the conductors must be derated. Pay special
attention to note 8 of Table 310 regarding Ampacity Adjustment Factors when more than three (3) current carrying conductors are in a raceway.
k
Maximum size of the time delay fuse or circuit breaker for protection of field wiring conductors.
Maximum KW that can operate with the heat pump on is 9KW. Full heat available during emergency heat mode.
m
Maximum KW that can operate with the heat pump on is 10KW. Full heat available during emergency heat mode.
n
Based on 75°copper wire. All wiring must conform to the National Electrical Code and all local codes.
IMPORTANT:
While this electrical data is presented as a guide, it is important to electrically connect properly sized fuses and conductor wires in
accordance with the National Electrical Code and all local codes.