Solair J17A2 Installation Instructions Manual Download Page 25

Manual 2100-588A 

Page 

25 of 29

TABLE  7

RECOMMENDED AIRFLOW

TABLE  8

INDOOR BLOWER PERFORMANCE

TABLE  9

MAXIMUM ESP OF OPERATION 

ELECTRIC HEAT ONLY

Values shown are for units equipped with standard 1-inch throwaway filter or 1-inch washable filter.

Derate ESP by .15 for 2-inch pleated filters.

Model

Nominal 

Rated 

CFM  *

Nominal 

Rated 

ESP  *

Recommended 

Airflow Range

Factory Speed 

Connection

J17A, J17L

600

.40

550 - 725

Low

J24A, J24L

800

.30

700 - 950

Single

J30A, J30L

1000

.30

850 - 1300

High

J36A, J36L

1100

.20

930 - 1350

High

J42A, J42L

1400

.45

1600 - 1150

High

J48A, J48L

1550

.30

1750 - 1285

High

J60A, J60L

1700

.40

1950 - 1375

High

J70A, J70L

1700

.20

1950 - 1375

High

Speed

J17

J24

J30

J36

J42/48

J60

J70

High

Low

Single

High

Low

High

Low

High

Low

High

Low

High

Low

ESP

(Inch 

H20)

Dry 

Coil

Wet 

Coil

Dry 

Coil

Wet 

Coil

Dry 

Coil

Wet 

Coil

Dry 

Coil

Wet 

Coil

Dry 

Coil

Wet 

Coil

Dry 

Coil

Wet 

Coil

Dry 

Coil

Wet 

Coil

Dry 

Coil

Wet 

Coil

Dry 

Coil

Wet 

Coil

Dry 

Coil

Wet 

Coil

Dry 

Coil

Wet 

Coil

Dry 

Coil

Wet 

Coil

Dry 

Coil

Wet 

Coil

0.0

1045 1025

760

745

990

970

1370 1285 910

885

1415 1275 955

925

1850 1800 1605 1555 2080 2015 1505 1460 2050 1845 1490 1400

0.1

1010 970

730

715

945

925

1305 1225 885

860

1350 1215 945

915

1775 1725 1545 1500 2020 1960 1450 1405 1970 1770 1425 1340

0.2

940

905

700

685

890

870

1225 1135

850

815

1265 1125

925

900

1685 1640 1460 1415 1925 1865 1395 1355 1905 1700 1375 1295

0.3

860

830

670

655

820

800

1115 1020 790

755

1190 1060 875

850

1590 1550 1390 1345 1870 1815 1340 1300 1830 1645 1225 1150

0.4

780

750

610

595

735

720

1005 910

695

660

1085 975

780

755

1495 1460 1310 1270 1755 1705 1225 1185 1725 1550 1140 1070

0.5

665

640

485

455

605

590

865

775

590

560

970

865

640

615

1400 1365 1225 1185 1660 1610 1125 1085 1500 1350 1050 985

Model

J17A/L,

J24A/L

J30A/L, J36A/L

J42A/L, J48A/L

J60A/L, J70A/L

Outlet

FRONT

FRONT

TOP

FRONT

FRONT

Speed

Single

High

Low

High

Low

High

Low

High

Low

-A0Z

-A04

-A05

-A08

-A10

-A15

-A20

.50

.50

.50

.50

.50

.50

.50

.40

.50

.50

.50

.45

.35

.50

.50

.50

.50

.45

.35

.50

.50

.50

.50

.50

.50

.50

.50

.50

.45

.50

.50

.50

.50

.50

.50

.50

.50

.50

.40

-B0Z

-B06

-B09

-B15

-B18

.50

.50

.50

.50

.50

.45

.50

.40

.50

.30

.50

.45

.50

.40

.50

.50

.50

.50

.50

.50

.50

.50

.50

.50

.50

.50

.50

.50

.50

.50

-C0Z

-C06

-C09

-C15

.50

.50

.50

.45

.50

.50

.40

.35

.50

.45

.50

.40

.50

.50

.50

.50

.50

.50

.50

.50

.50

.50

.50

.50

* Rated CFM and ESP on factory speed connection.

Summary of Contents for J17A2

Page 1: ...LLATION INSTRUCTIONS WALL MOUNTED PACKAGE AIR CONDITIONERS MODELS J17A2 J17L2 J24A2 J24L2 J30A2 J30L2 J36A2 J36L2 J42A2 J42L2 J48A2 J48L2 J60A2 J60L2 J70A2 J70L2 Manual 2100 588A Supersedes 2100 588 F...

Page 2: ...flow 25 Table 8 Indoor Blower Performance 25 Table 9 Maximum ESP Electric Heat Only 25 Table 10 Electric Heat 26 Table 11A Optional Accessories Right Hand 27 Table 11B Optional Accessories Left Hand 2...

Page 3: ...ter and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning...

Page 4: ...rticularly Starting Procedure and any tags and or labels attached to the equipment While these instructions are intended as a general recommended guide they do not supersede any national and or local...

Page 5: ...ch Any grille that meets with 5 8 inch louver criteria may be used It is recommended that Bard Return Air Grille Kit RG2 through RG5 or RFG2 through RFG5 be installed when no return duct is used Conta...

Page 6: ...ING THE UNIT 1 These units are secured by wall mounting brackets which secure the unit to the outside wall surface at both sides A bottom mounting bracket attached to skid for shipping is provided for...

Page 7: ...ce Electrical Built In Ventilation Air models Electrical 4 Pitch Filter Access Panel Top Rain Low Voltage Electrical Entrance Standard flush vent door for Access Panel Lockable non ERV Econ Disconnect...

Page 8: ...IME OF INSTALLATION OPENING MIS 3157 ENTIRE LENGTH OF TOP RETURN AIR DUCT Wall Opening and Hole Location View Right Side View OF CAULKING ALONG PANEL FOAM AIR SEAL WALL STRUCTURE WALL HEATER ACCESS RA...

Page 9: ...TES 1 4 CLEARANCE ON ALL HEATER ACCESS TOP FLASHING AT TIME OF INSTALLATION THE SIDE MOUNTING FLANGES AND UNDER SILICONE CAULKING BE PLACED BEHIND IS ON OPPOSITE LEFT SIDE OPENING CONTROLS AND HEATER...

Page 10: ...1 4 1 1 4 29 3 4 32 12 5 1 2 2 NOTES WALL STRUCTURE 1 SUPPLY AIR IT IS RECOMMENDED THAT A BEAD OF OPENING Right Side View RAIN FLASHING SILICONE CAULKING BE PLACED BEHIND RECOMMENDED 1 CLEARANCE FROM...

Page 11: ...ir duct and combustible materials This is required for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could resu...

Page 12: ...FACTORY SUPPLIED RAIN FLASHING SUPPLY AIR MIS 548 A SIDE VIEW I A C K E 1 000 B 1 000 SUPPLY DUCT OVER FRAME INTERIOR FINISHED WALL ALL AROUND DUCT FRAMING MATERIAL EXTERIOR FINISH WALL OPENING FOR AC...

Page 13: ...WALL OPENING W GRILLE SUPPLY DUCT MAYBE LOCATED IN AN ATTIC OR BELOW CEILING RAFTERS AS SHOWN CEILING RAIN RETURN AIR SLEEVE WALL SUPPLY AIR DUCT RAFTERS RAFTERS RETURN AIR OPENING W GRILLE RAIN FALSE...

Page 14: ...ot in the door When shut a padlock may be placed through the hole in the tab preventing entry See Start Up section for important information on three phase scroll compressor start ups See Tables 5 6 f...

Page 15: ...EAT STAGE 2 ECONOMIZER STAGE 1 VENTILATION IF EQUIPPED N O CONTACT COMPRESSOR OPEN OR SPECIAL USE AS REQUIRED 24V HOT FAN BLOWER ALARM RELAY N C CONTACT ELECTRIC HEAT STAGE 1 J MODULE REFRIGERANT IF E...

Page 16: ...TO R AND RT TERMINALS OPEN OR SPECIAL USE AS REQUIRED N C CONTACT COMPRESSOR ECONOMIZER STAGE 1 BLUE COMMON BLACK ALARM RELAY ELECTRIC HEAT STAGE 1 ORANGE FACTORY INSTALLED JUMPER REMOVE FOR 2 STAGE...

Page 17: ...INPUT USED IF MINIMUM YELLOW RED 2 1 POSITION REQUIRED FOR VENTILATION BLACK PINK BROWN WHITE ORANGE 24V TRANSFORMER OUTPUT YELLOW FACTORY INSTALLED JUMPER REMOVE FOR 2 STAGE OPERATION RED PURPLE BLU...

Page 18: ...ple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be u...

Page 19: ...rrect phasing is determined for a specific system or installation connecting properly phased power leads to the same Fusite terminal should maintain proper rotation direction The direction of rotation...

Page 20: ...e manual lockout Low Pressure Switch Bypass and Lockout Sequence If the low pressure switch opens for more than 120 seconds the compressor contactor will de energize and go into a soft lockout Regardl...

Page 21: ...T CHARGE TABLE 3 REFRIGERANT CHARGE The suction line temperatures in Table 4 above are based upon 80 F dry bulb 67 F wet bulb 50 R H temperature and rated airflow across the evaporator during cooling...

Page 22: ...35 356 138 380 141 405 143 431 145 457 147 484 149 512 151 540 152 569 154 599 J36A L 75 62 Low Side High Side 120 339 122 366 124 392 126 418 129 446 130 473 132 501 134 529 135 558 136 586 80 67 Low...

Page 23: ...or 2 24 32 47 58 84 35 35 50 60 90 8 8 8 6 4 10 10 10 10 8 58 26 60 30 6 10 10 10 J30A2 B00 B0Z B06 B09 B15 230 208 3 1 1 1 1 18 24 33 51 20 25 35 60 12 10 8 6 12 10 10 10 J30A2 C00 C0Z C06 C09 C15 4...

Page 24: ...56 30 30 50 60 10 10 8 6 10 10 10 10 J24L2 B00 B0Z B06 230 208 3 1 1 15 22 20 25 12 10 12 10 J24L2 C00 C0Z C06 460 3 1 1 9 11 15 15 14 14 14 14 J30L2 A00 A0Z A05 A08 A10 A15 230 208 1 1 1 1 1 1 or 2 2...

Page 25: ...85 1415 1275 955 925 1850 1800 1605 1555 2080 2015 1505 1460 2050 1845 1490 1400 0 1 1010 970 730 715 945 925 1305 1225 885 860 1350 1215 945 915 1775 1725 1545 1500 2020 1960 1450 1405 1970 1770 1425...

Page 26: ...Amps BTUH Amps BTUH Amps BTUH 4 16 7 13650 14 4 10240 5 20 8 17065 18 1 12800 6 14 4 20500 12 5 15360 7 2 20500 8 33 3 27300 28 8 20475 9 21 7 30600 18 7 23030 10 8 30700 10 41 6 34130 36 2 25600 12...

Page 27: ...8 X X EHWA03 A10 X X EHWA03 A15 X X EHWA03 B06 X EHW36A B06 X EHWA03 B09 X X EHWA37 B15 X X EHWC03A C06 X X EHWC03A C09 X X EHWA03A C12 X X EHWA03A C15 X X EHWA05 A05 X X EHWA05 A10 X X X X EHWA05 A15...

Page 28: ...WA03 A05L X X EHWA03 A08L X EHWA03 A10L X X EHWA03 A15L X X EHWA03 B09L X X EHWA37 B15L X X EHWC03 C09L X X EHWA03 C15L X X EHWA05 A05L X X X EHWA05 A10L X X X X EHWA05 A15L X X X X EHWA05 B09L X X EH...

Page 29: ...Bldg Equipment Enthalpy Economizer Bldg Equipment DB Temp X X X BFAD 3 Barometric Fresh Air Damper Standard X ECONWMS E3 ECONWMT E3 ECONWMT T3 Economizer School Version Enthalpy Economizer Bldg Equipm...