2.0 Specifications
Table 2: Technical Specifications
Parameters
Model
STV25K-10S
STV25K-24S
Nominal Input Voltage
120 V ac
240 V ac
System Configuration
Single-phase, 2W + G
Single-phase, 2W + G
Maximum Continuous Operating
Voltage (MCOV)
150 V ac
275 V ac
Operating Frequency Range
47–63 Hz
Input Current Rating
20 A
Short Circuit Current Rating
(SCCR)
5 kAIC when protected by a listed Class G
fuse rated at 25 A, 480 V ac minimum
Surge Current Rating
25 kA per phase
Nominal Discharge Current (I
N
)
3 kA
Response Time
<0.5 ns
Modes of Protection
All Modes: L–N, L–L, L–G, N–G
EMI/RFI Noise Rejection
Normal mode: 50 dB minimum
Common mode: 40 dB minimum
Operating Temperature
-40°C to +60°C (-40°F to +140°F)
Operating Humidity
0 to 95% non-condensing
Dimensions, D x W x H
4.35 in. x 2.56 in. x 4.84 in.
(110.5 mm x 65.0 mm x 122.9 mm)
Net Weight
3.0 lb. (1.36 kg)
Enclosure
Metal, IP20
Mounting Type
DIN rail mounting
NOTE:
Optional chassis mounting bracket is available, P/N SDN-PMBRK2
Connections
Screw terminals, #12 AWG
Status Indication
Green LED, Form C relay contacts
Safety Approvals
UL 1449 3
rd
edition
Warranty
10 year limited warranty
UL 1449 3
rd
Edition Type 4 Voltage Protection Ratings (VPRs)
Line to Neutral
500 V
N/A
Line to Line
N/A
900 V
Line to Ground
500 V
900 V
Neutral to Ground
500 V
N/A