RM-DCM-2 Specifications
30
RM-DCM-2
SPECIFICATIONS
This section includes physical specifications and optimal operating
specifications for the RM-DCM-2.
NOTE
UL has evaluated the RM-DCM-2 for indoor use with a range of 0° C to
49°C (32°F to 120°F).
Software and Firmware
Support
Current versions of C•CURE 9000 and C•CURE 800/8000 system
software and firmware support the RM-DCM-2 components.
Power Requirements
and Specifications
Table 10 lists the power requirements and operating specifications of the
RM-4E board in the RM-DCM-2 enclosure.
TABLE 11.
RM-4E Power Requirements and Operating Specifications
Requirement
Specification
RM-4E Power requirements
+12/24 VDC
280 mA without reader and relays
Maximum input (with full load)
+12/24 VDC
550 mA maximum with reader and relays
Relay contact power limits
Up to 30 VAC/DC, 3.3 A maximum
Reader LED output control
4.0 VDC to 5.25 VDC, 20 mA maximum
Reader port output voltage
5 VDC
or
12 VDC
Reader port output maximum
current
125 mA (at 5V or 12V)
NOTE
Software House recommends local power when using the battery
charging circuit and when the RM-4E is used with high-power, long-
range readers.
See “Power In” on
page 9
for information.