SOFTLINK Sigfox WS868-PLE-I Manual Download Page 26

All manipulation with the WS868-PLE-I module during installation is in principle the same, as handling with
any other type of authorized remote reading module for Elster BK-G series gas-meter (e.g. IN-Z61). View of
WS868-PLE-I module installed to gas-meter is displayed in the figure

1

.

After module installation make sure the right module is mounted to right gas-meter and fill in the prescribed
documentation.

4.7

Module replacement

When there is necessary to replace the module due to the module failure or due to battery discharging follow this
procedure:

check the antifraud seal before dismantling – the antifraud seal damage must be solved according to the
internal rules of the customer/project;

remove connecting element (screw, wire...) between the module sealing protrusion and matching protrusion
on the gas-meter;

cautiously pull the module out of gas-meter slot;

unscrew a screw on the module back cover and remove front lid;

switch-off battery by removing of shortening connector from shortening pins and mark the module visibly as

defective”. Alternatively, just mark the module as defective, it can be opened and switched off later in the

workshop;

prepare a new module in the same way as described in paragraph

4.6

above. Switch on battery, perform

diagnostics and setting as described in pargraph

4.9

Functional check of the module”. Especially check

and set counter initial value as descrobed in paragraph

??

Commands for setting of input counters” and

broadcasting period as described in paragraph

3.5.3

Commands for setting of timers”. Alternatively, alls

these settings (excepting

downlink” mode) can be performed via optical converter after mounting to gas-

meter;

place front lid to the module base and affix it by screw. Mount the assembled module onto the gas-meter and
seal by antifraud seal;

write down the new module ID, gas-meter counter status and seal number. Fill in the prescribed service
documentation. If possible, arrange making of all appropriate changes in the database of the remote reading
system immediately.

4.8

Module dismantle

When dismantling from gas-meter, remove sealing connection and detach the module from gas-meter. Remove front
lid from the base and switch the battery off (alternatively, this could be done later in the workshop). Mark the
module as

dismantled” and fill in the relevant documentation, prescribed for this situation by the internal rules.

If possible, arrange deactivation of the module in the database of remote reading system immediately. Take off an
external antenna (if used).

4.9

Functional check of the module

After putting the module into operation (or after each repair and replacing of the module) it is recommended to
check its basic functionality:

before installation check setting of module and examine availability of Sigfox network radio-signal by sending
of several messages with using of ”T” command as described in paragraph

3.5.5

Commands for module

activation and diagnostics” and receiving them in the central system.

Alternatively, examination of the

network signal can be performed by using of Sigfox signal tester;

after installation to the gas-meter check correctness of reading system by repetitive inspection of counter
current value (”Value1”) by using of optical converter. If there is a real gas consumption in progress, counter
value should change in correspondence with changing of mechanical counter value. Values of physical quantities
(temperature, voltage..) should correspond with reality;

check setting of broadcasting period;

perform complex (end-to-end) check of implementation of the module into the remote reading system by
inspection of data rendered by module in reading system database. If the module broadcasting period is quite
long, set shorter period for testing.

After testing don’t forget to set correct value of broadcasting

period (in accordance with service contract!

.

WS868-PLE-I

23

Summary of Contents for Sigfox WS868-PLE-I

Page 1: ...WIRELESS COMMUNICATION SYSTEM Sigfox WS868 WS868 PLE I Revision 1 0 SOFTLINK s r o Tomkova 409 278 01 Kralupy nad Vltavou Czech Republic Phone 420 315707111 e mail sales softlink cz www softlink cz...

Page 2: ...of WS868 PLE I module parameters by configuration cable 13 3 5 1 List of WS868 PLE I module configuration parameters and commands 13 3 5 2 Commands for saving of configuration parameters and reset 13...

Page 3: ...erter 6 7 Displaying of the optical converter in the Windows Device Manager 7 8 Displaying of WACO OptoConf configuration window 7 9 List of variables in the working window of WACO OptoConf program 7...

Page 4: ...network server to the application servers of authorized users through the unified data interface via public Internet 1 2 Module usage The WS868 PLE I module can be used for remote reading of Elster BK...

Page 5: ...ynchronous Transmission parameters 8 data bits 1 stop bit none parity Signal level TTL CMOS Optical configuration interface Transmission speed 115 200 Baud Optical interface specification IrPHY 1 4 st...

Page 6: ...e to computer Configuration can be performed by using of common USB port of the computer For the interconnection with a USB port of computer it is necessary to use a manufacturer s original configurat...

Page 7: ...nal setting for serial line communication PuTTY software runs after clicking on the downloaded file putty exe There will open a window of the terminal communication see Figure 4 For switching the prog...

Page 8: ...ers HELP enter question mark or and press ENTER key when entering characters distinguish strictly the capital and small letters according to the documentation or HELP Do not enter other characters tha...

Page 9: ...ow 3 2 2 Connection of USB IRDA optical converter to computer Before starting of the WACO OptoConf program connect the USB IRDA converter to USB port of the computer When the converter is connected to...

Page 10: ...ystem communication systems can be found on the producer s WEB site NEP Page By clicking to Read device button the textbfconfiguration table with all the relevant parameters of the module is displayed...

Page 11: ...n between module and converter is reliable When working directly at the installation site always use a special holder that is designed for attaching of converter to the module Put the holder to the WS...

Page 12: ...s either bad position of the module long distance wrong orientation dirty cover obstacle in the beam or the module s battery was switched off NOTE WACO OptoConf program contains specific data and sett...

Page 13: ...ce see figure 13 left Figure 13 Displaying of the device without driver in Device Manager window By right clicking to USB Serial port open the context menu and choose Update driver software item Click...

Page 14: ...d Boot Options appears choose Disable Driver Sig nature Enforcement option in this window after launching the system install the driver according the above mentioned instructions Deactivation of the e...

Page 15: ...g to the above described procedure Deactivation of the enforcement of signed driver function of the Windows 10 operating system is functional only until the next restart of the system 3 4 3 Support of...

Page 16: ...M enable mode setup on startup ppm set Xtal ppm s sec set sending time in seconds m sec set measure time in seconds d n n th uplink message has downlink capability 0 no downlink i index value set init...

Page 17: ...broadcasting period The period is set in seconds and the module broadcasts its INFO messages spontaneously with this period Example of setting of broadcasting period to 1 hour 3600 seconds and corres...

Page 18: ...utput value counter value multiplier i index d value setting of divisor output value counter value divisor Important note The first input with index 0 that registers revolving of gas meter pivotal whe...

Page 19: ...initialization mode Mode setup Do not use Only for factory setting ppm enteering of XTAL correction constant Do not use Only for factory setting D number debug statement switch on Do not use Only for...

Page 20: ...t based on suspension cause 2 means Watchdog reset reset by watchdog system 3 means Error reset incorrect instruction or inconsistent data 4 means Power reset caused by low power voltage The parameter...

Page 21: ...nf program window View of configuration table is depicted in figure 16 Figure 16 The WS868 PLE I module configuration table In the upper section of the table there are read only type of parameters fac...

Page 22: ...ontract that is valid for configured device The Measure periode parameter is used for setting of analog quantities temperature voltage measurement interval in seconds More detailed description of this...

Page 23: ...7 Structure of module data messages The WS868 PLE I module is intended for reading of data from Elster gas meters of BK G series and broadcasting of measured data through the Sigfox RF network Maximu...

Page 24: ...capacity reduces frequency of broadcasting 4 2 The condition of modules on delivery Modules are delivered in standard cardboard boxes The modules are commonly delivered in fully operating status with...

Page 25: ...de of the module should be locked inside the gas meter lock connect module sealing protrusion with matching protrusion on the gas meter by sealing screw or sealing wire or other prescribed way and sea...

Page 26: ...as meter counter status and seal number Fill in the prescribed service documentation If possible arrange making of all appropriate changes in the database of the remote reading system immediately 4 8...

Page 27: ...y batteries used in the wacoSystem modules that have been carefully selected and properly tested In case of battery replacement by user the new battery parameters should meet same technical requiremen...

Page 28: ...ce these elements for the spare ones with proven functionality check correctness of module settings and perform the check of module overall functionality as described in paragraph 4 9 replace the modu...

Page 29: ...nfiguration options of WS868 PLE I RF modules designed for operation in Sigfox IoT network in868 MHz frequency band that are a part of the Softlink s wacoSystem product family More information about a...

Reviews: