4.4. Connecting AC Output Power Cables
Connect the SOFAR 3K~6KTLM-G3 to the AC power distribution frame
or power grid using AC output power cables.
It is not allowed for several inverters to use the same circuit breaker.
It is not allowed to connect loads between inverter and circuit
breaker.
AC breaker used as disconnect device,and the disconnect device
shall remain readily operable.
Caution
Context
All the AC output cables used for the inverters are outdoor three-core
cables. To facilitate the installation, use flexible cables. Table 4-2 lists the
recommended specifications for the cables.
Figure 4-8 NOT allowed: connect loads between inverter and circuit breaker
Table4-2 Recommended AC output cable specifications
Model
3KTLM-
G3
3.6KTL
M-G3
4KTLM-
G3
4.6KTLM
-G3
5KTLM-
G3
5KTLM-
G3-A
6KTLM-
G3
Cable
(Copper)
≧
6mm
²
≧
6mm
²
≧
6mm
²
≧
10mm
²
≧
10mm
²
≧
10mm
²
≧
10mm
²
Breaker
20A
25A
25A
32A
32A
32A
32A
Multi core copper wire