SIDER - 546 418 A - SOCOMEC
4. CONNECTIONS
4.1.
Cable or bar connections
Recommended tightening torque:
• M12 : 40 N.m
Maximum tightening torque:
• M12 : 45 N.m
4.1.1. Power connection terminals
1250A
1600A
2000A
2500A
3200A
Minimum bars
section Cu (mm
2
), Ith
2x80
x5
2x100
x5
3x100
x5
4x100
x5
3x100
x10
Maximum cables
section Cu (mm
2
)
4x185
6x185
-
-
-
Maximum bars width
Cu (mm)
63
100
100
100
100
5. TROUBLE SHOOTING GUIDE
It is not possible to
manually operate the
switch
• Make sure that the product is not padlocked
• Verify the rotation direction of the handle
• Apply a sufficient progressive action in the direction as indicated on the
handle
Impossible to padlock
• Verify that the SI
D
ER is in 0 position
(Padlocking is only possible in 0 position for standard products)