3. PREREQUISITES
3.1. INSTALLATION SITE CONDITIONS
The installation site must meet the following requirements:
- The inverter is designed for use within non-air-conditioned rooms in accordance with standard IEC 62109-1. Th inverter is not
designed for outdoor use.
- The foundations must be able to withstand the relevant weight (inverter, transportation device) and suited to the base. Stability
must also be guaranteed.
- The ambient temperatures, relative humidity and altitude of the installation site are indicated in the technical data table.
- Avoid environments which are dusty or which contain dust from conductive or corrosive materials (e.g. dust from metal or chemical
solutions).
- The inverter has front access for handling devices; nevertheless, a space of at least 1.5 metres should be left free at the front of
the inverter for any maintenance work required.
- The rear of the inverter must be at least 40 cm away from the wall or other obstacles to guarantee sufficient ventilation (see figure).
3.1-1
free area
SUNSYS
SUNSYS
SUNSYS
40 cm
1.5 m