20
ITYS
1-10 kVA - Ref.: IOMITYTWXX05-GB 00
11. TECHNICAL SPECIFICATION
Models
1
1 (LB)
2
2 (LB)
3
3 (LB)
Nominal Power
VA/W
1000/800
2000/1600
3000/2400
Input/Output phases
1/1
1/1
1/1
Electrical Specifications - Input
Mains voltage (Vin)
Vin
110 to 300 V Derating to 50 % @ 110 V input
Input frequency
Hz
45 to 55/54 - 66
Input power factor
≥
0.99
THDI
< 5 % with full load
Electrical Specifications - Output
Output Voltage
V
208/220/230/240 V ± 2 %
Output power must derating to 90 % when the output voltage rate be set with 208 V
Frequency
Hz
45-55/54 to 66 Hz (50/60 Hz ± 0.2 Hz in Battery Mode or Converter Mode)
Overload – Normal
Mode (@ 25°C)
1 m
30 s
10 s
1 s
%
105 to 110
110 to 125
125 to 150
> 150
Crest Factor
3:1
Voltage distortion
%
< 5 % Non Linear Load; < 3 % Linear Load
Electrical Specificationsn - Battery
Type
Sealed lead acid maintenance free-expected life 3/5 years
Voltage
36
96
96
BUT
> 5 min
-
> 9 min
-
> 5 min
-
Charger
-
8 A
-
8 A
-
8 A
Enviroment
Operating temperature
°C
0 to 40
1
Relative humidity
%
20 to 90 No Condensing
Max. altitude
m
< 1000 m without derating
Acoustic noise
dBA
up to 50 dB at front 1 m
Standards
Safety
EN 62040-1, EN 60950-1
EMC
EN 62040-2
Product Certification
CE
Protection Level
IP20
Mechanical Characteristics with standard batteries
Dimensions (W x D x H)
mm
145 x 400 x 220
192 x 460 x 347
192 x 460 x 347
Weight
kg
13
7
31
13
31
13
1. 15-25 °C for a longer battery life.