- 32 -
and odd parity.3 = Two stop bits and no
parity. Requires a restart to become
effective.
Length : 4 byte
Data Format : Float
40021
11
Network Node
00
14
Write the network port node address:
1 to 247 for MODBUS Protocol, default 1.
Requires a restart to become effective.
Length : 4 byte
Data Format : Float
r/w
40023
12
Pulse 1 Divisor
00
16
Write pulse divisor index: n
= 1 to 6
1--0.01kwh/imp
2--0.1kwh/imp
3--1kwh/imp
4-10kwh/imp
5-100kwh/imp
6-1000kwh/imp
Length : 4 byte
Data Format : Float
r/w
40025
13
Password
00
18
Write password for access to protected
registers. Default password is 1000.
Length : 4 byte
Data Format : Float
r/w