28
SOCOMEC - Ref. : 875 092A
4096
1000
1
Recording pointer
Pulse
4097
1001
1
1
st
value
4098
1002
1
2
nd
value
...
...
...
...
5296
14B0
1
Last value
Address
INPUT 1
IMPULSE METERS DISPLAY FOR POWER DEMAND STORING (INPUT 1 TO 4)
Decimal
Hexadecimal
N° of words (1)
Description
Unity
COMMUNICATION (continued)
8192
2000
1
Recording pointer
Pulse
8193
2001
1
1
st
value
8194
2002
1
2
nd
value
...
...
...
...
9392
24B0
1
Last value
INPUT 2
12288
3000
1
Recording pointer
Pulse
12289
3001
1
1
st
value
12290
3002
1
2
nd
value
...
...
...
...
13488
34B0
1
Last value
INPUT 3
16384
4000
1
Recording pointer
Pulse
16385
4001
1
1
st
value
16386
4002
1
2
nd
value
...
...
...
...
17584
44B0
1
Last value
INPUT 4
Zone size: 9604 words in decimal or 2584 in hexadecimal
Example: 100 pulses with 100 kWh scale with 30-minute synchronisation: P = 100 x 100000/2 = 5 MWh.
PULSE METERS FOR POWER DEMAND STORING (INPUTS 1 to 4 ONLY)
Method of calculation:
The Countis Ci is switched on 10/03/2000 at 10.00h with automatic reading program-
med for the first of each month at 02.00h.
These meters enable an average integrated value to be created using a number of
pulses over a period of 8, 10, 15, 20 or 30 minutes.
Values 1, 2 and 3
0
Value 4
consumption from 10/03/2000 at 10.00h to 01/04/2000 at 2.00h
Value 5
consumption from 01/04/2000 at 2.01h to 01/05/2000 at 2.00h
Value 6
consumption from 01/05/2000 at 2.01h to 01/06/2000 at 2.00h
And so on for the values 7 to 12.
NB:
Product code 4852 can be accessed
at address 1280 (decimal) in one
word, and with function 3.