SOCOMEC - Ref. : 875 645 D

TECHNICAL CHARACTERISTICS

ENCLOSURE

Connection

via 1 to 6 mm

2

terminal shrouds

Weight

300 g

Size

modular: 4 modules of 17.5 mm

Protection class (front)

IP40

FRONT PANEL

Green LCD/7 digits
Digit height

8 x 4 mm

INPUTS

CURRENT
Via transformer with
• configurable primary

5 to 6000 A

• secondary

5 A

Input consumption

10 mA to 7 A (secondary)

Consumption

1 VA

TENSION
Measurement range (Line / Line)

230 V AC - 15 % to 400 V AC + 20 %

Consumption

0,5 VA

AUXILIARY POWER SUPPLY

Type

auto-powered

Consumption

1 VA

ACCURACY

Accuracy index

IEC 61036 class 1

PULSE OUTPUT

Reed relay (100 V DC - 0.5 A - 12 VA)
Pulse duration

60 to 900 ms

Maximum tripping number

5 x 10

7

at 10 V DC/10 mA

OPERATING CONDITIONS

Operating temperature

- 5 °C up to 45 °C

Storage temperature

- 20 °C up to 70 °C

Relative humidity

85 %

STANDARDS

CE marking

IEC 61000-4/2-3-4-5-6-8-11

EN 50081-1
EN 50082-2

Operating conditions

IEC 60068-2-6

IEC 60068-2-11
IEC 60068-2-30

Note:
The current inputs are insulated on
the ATiv2.

Note:
The Countis ATv2 and ATiv2 are auto-
powered from the V1 et V2 voltage
inputs.

Summary of Contents for COUNTIS ATiv2

Page 1: ...Industrial Switching Protection Systems COUNTIS ATv2 ATiv2 Operating instructions GB...

Page 2: ...2 SOCOMEC Ref 875 645 D...

Page 3: ...ATIONS ___________________ 4 GENERAL INFORMATION ______________________ 4 PRESENTATION _______________________________ 4 INSTALLATION ________________________________ 5 CONFIGURATION _________________...

Page 4: ...on balanced 3 or 4 wire network This system comprises two products ATv2 a non insulated three phase active energy meter which does not allow earthing CT of secondary ATiv2 a three phase insulated sing...

Page 5: ...To avoid damaging the device take care to observe the following before connecting the device indications on the casing network frequency 50 or 60 Hz maximum permanent voltage at voltage input terminal...

Page 6: ...2 1 L1 L2 L3 P1 S1 P1 S1 2 4 6 8 1 3 5 7 9 11 ATiv2 1 L1 L2 L3 P1 S1 ATiv2 2 4 6 8 1 1 3 5 7 9 11 L1 L2 L3 P1 S1 P1 S1 2 4 6 8 1 3 5 7 9 11 ATiv2 1 L1 L2 L3 N P1 S1 P1 S1 P1 S1 2 4 6 8 1 3 5 7 9 11 AT...

Page 7: ...network programming nET To select the network type 1bL single phase 2bL two phase 3 4 nbL unbalanced three phase and 3 4 bL balanced three phase To validate the network programming and go on to the c...

Page 8: ...AC 20 Consumption 0 5 VA AUXILIARY POWER SUPPLY Type auto powered Consumption 1 VA ACCURACY Accuracy index IEC 61036 class 1 PULSE OUTPUT Reed relay 100 V DC 0 5 A 12 VA Pulse duration 60 to 900 ms Ma...

Page 9: ...SOCOMEC Ref 875 645 D 9 ENGLISH...

Page 10: ...CE Tel 33 0 3 88 57 41 41 Fax 33 0 3 88 57 78 78 SOCOMEC 95 rue Pierre Grange F 94132 Fontenay sous Bois Cedex FRANCE Tel 33 0 1 45 14 63 40 Fax 33 0 1 48 77 31 12 scp dcm socomec com SALES MANAGEMENT...

Reviews: