socomec ATyS g M Installation And Operating Manual Download Page 9

ATyS g M - 542933D - SOCOMEC

9

EN

quick start

40 - 160A (2P)

EN

ATyS 

g

 M

Automatic

Transfer Switching Equipment

Printing informations:

 1 color Black. White paper 90g/m

2

Printing size: 420x297. Final size 210x297. This page visible first.

A separate sheet for each language.

Non contractual document.

Subject to change without notice.

 Preliminary operations 

Check the following upon delivery and after removal of the 

packaging:

n

  

Packaging and contents are in good condition.

n

  

The product reference corresponds to the order.

n

  

Contents should include:

Qty 1 x ATyS M
Qty 1 x Emergency handle extension ROD
Qty 1 x Set of terminals
Quick Start instruction sheet

 Warning 

 

Risk of electrocution, burns or injury to persons and / 

or damage to equipment.
This Quick Start is intended for personnel trained in the 

installation and commissioning of this product. For further 

details refer to the product instruction manual available on 

the SOCOMEC website.

n

  

 This product must always be installed and commissioned 

by qualified and approved personnel.

n

  

 Maintenance and servicing operations should be 

performed by trained and authorised personnel.

n

  

Do not handle any control or power cables connected to 

the product when voltage may be, or may become present 

on the product, directly through the mains or indirectly 

through external circuits.

n

  

Always use an appropriate voltage detection device to 

confirm the absence of voltage.

n

  

Ensure that no metal objects are allowed to fall in the 

cabinet (risk of electrical arcing).

Failure to observe good enginering practises as well as to 

follow these safety instructions may expose the user and 

others to serious injury or death.

 

Risk of damaging the device

n

  

In case the product is dropped or damaged in any way it 

is recommended to replace the complete product.

 Accessories 

n

  

 Bridging bars and 125A or 160A.

n

  

 Control voltage transformer (400Vac -> 230Vac).

n

  

Voltage sensine and power supply TAP.

n

  

Terminal shrouds.

n

  

Additionnal aux contact block.

n

  

Polycarbonate enclosure.

n

  

Polycarbonate extension box.

n

  

Power Connection Terminals.

n

  

Sealable cover.

STEP 1

 

Cabinet / Back 

Plate Installation

STEP 3

 

CONTROL /  

AUX POWER 

terminal 

connections

STEP 2

 

Connecting the 

POWER section

STEP 4

 

CHECK

STEP 5

 

Programming

Installation and Commissioning

STEP 6A

 

Automatic Operation

STEP 6C

 

Padlocking

STEP 6B

 

Emergency Manual 

Operation

STEP 3

CONTROL / AUX POWER Terminals and wiring

Ensure that the product is in Manual 

Mode (front cover open).

Slotted head 3mm 0,5 Nm

0,5  to  2,5 mm²

0,5  to  1,5 mm²

6 mm

5 A AC1
250 Vac

22 24 21

11 14 12

01 04 02

5 A AC1
250 Vac

22 24 21

11 14 12

01 04 02

1309  1001

5 A AC1
250 Vac

22 24 21

11 14 12

01 04 02

5 A AC1
250 Vac

22 24 21

11 14 12

01 04 02

1309  1011

2

4

6

8

1

3

5

7

2

4

6

8

1

3

5

7

207208209210 63 64 73 74

6 mm /

Capacité de raccordement

 0,236 "

# 20 to  # 14 AWG

0,5  to  2,5 mm

0,5  to  1,5 mm

2

2

# 20 to # 16 AWG

Slotted head  3 mm

3,97 lb-in  0,5 Nm

2

4

6

8

1

3

5

7

2

4

6

8

1

3

5

7

2

4

6

8

1

3

5

7

2

4

6

8

1

3

5

7

/

I1 I2 I3

O1 O2

207208209210 63 64 73 74

/

I1 I2 I3

O1 O2

5 A AC1
250 Vac

22 24 21

11 14 12

01 04 02

5 A AC1
250 Vac

22 24 21

11 14 12

01 04 02

LOAD

www.socomec.com

www.socomec.com/operating-instructions

To download, brochures, catalogues and technical manuals.

STEP 1

  

The ATyS M is delivered with 

padlocking configured to the 

O position.

  

To allow padlocking in all 

positions (I - O - II), configure 

the ATyS M as follows before 

installation. (Screw is located 

at the back of the product).

Posidriv  PZ2 

OK

OK !

!

STEP 1

STEP 2

STEP 3

STEP 4

Posidriv  PZ2 

Posidriv  PZ2 

2,2 lb-in

  0,25 Nm

2 X

Posidriv  PZ2 

OK

OK !

!

STEP 1

STEP 2

STEP 3

STEP 4

Posidriv  PZ2 

Posidriv  PZ2 

2,2 lb-in

  0,25 Nm

2 X

Posidriv  PZ2 

OK

OK !

!

STEP 1

STEP 2

STEP 3

STEP 4

Posidriv  PZ2 

Posidriv  PZ2 

2,2 lb-in

  0,25 Nm

2 X

Posidriv  PZ2 

OK

OK !

!

STEP 1

STEP 2

STEP 3

STEP 4

Posidriv  PZ2 

Posidriv  PZ2 

2,2 lb-in

  0,25 Nm

2 X

Posidriv  PZ2 

OK

OK !

!

STEP 1

STEP 2

STEP 3

STEP 4

Posidriv  PZ2 

Posidriv  PZ2 

2,2 lb-in

  0,25 Nm

2 X

Posidriv  PZ2 

OK

OK !

!

STEP 1

STEP 2

STEP 3

STEP 4

Posidriv  PZ2 

Posidriv  PZ2 

2,2 lb-in

  0,25 Nm

2 X

Installation

Padlocking configuration

Caution: Ensure that the product is installed on a flat rigid surface.

Recommended orientation

Recommended

Ok

Ok

Ok

Ok

Ok

OK

OK

OK

OK

OK

OK

OK

OK

OK

OK

OK

OK

OK

OK

OK

OK

OK

OK

2 clips de verrouillage

Posidriv  PZ1

1 Nm

 Tighten to avoid 

movement on the DIN rail.

2x

2x

!

2 clips de verrouillage

DIN RAIL
IEC 60715

MAX : 2

235

26

116

53

46

73,5

245

143

350

18

45

13

222

235

131,5

131,5

47

52

176

224

MAX : 2

235

26

116

53

46

73,5

245

143

350

18

45

13

222

4 mounting brackets

6x M6 screw - 2,5 Nm

STEP 2

Power Terminal Connections

Source supply side

Hexagonal Metric

Allen size 4

5,0 Nm

  It is essential to tighten all used 

terminals, with cables and/or 

bridging bars, before use.

Voltage taps provide 2x ≤ 1.5mm

2

 connections. 

They can be fitted in any terminals on the source 

supply side. Do not use on the load side when 

equipped with a bridging bar.

Load side 

bridging bar.
125A: 1309 2006
160A: 1309 2016

Slotted head  3,5 mm

0,45 Nm

0,5  to  2,5 mm²

0,5  to  1,5 mm²

6 mm

10 to 
70 mm²

15mm

Type

Terminal no. Status of 

the contact

Description

Output 

characteristics

Recommended 

connection 

cross-section

Auxiliary contact 
block

1309  1001

11/12/14

11

14

12 Changeover switch in position I

250V AC 5A AC1
30 Vdc 5 A

0.5 to 2.5 mm²
(rigid)

0.5 to 1.5 mm²
(stranded)

21/22/24

21

24

22 Changeover switch in position II

250V AC 5A AC1
30 Vdc 5 A

01/02/04

01

04

02 Changeover switch in position 0

250V AC 5A AC1
30 Vdc 5 A

Auxiliary contact 
block

1309  1011

11/12/14

11

14

12

21

24

22

01

04

02

Changeover switch in position I

250V AC 5A AC1
30 Vdc 5 A

21/22/24

Changeover switch in position II

250V AC 5A AC1
30 Vdc 5 A

01/02/04

Changeover switch in position 0

250V AC 5A AC1
30 Vdc 5 A

Type

Terminal no.

Application

Status of the 

contact

Description

Output 

characteristics

Recommended 

connection  

cross-section

Inputs

I1: 207 / 208

Network/Network

With priority 

Dry potential free 
contact

0.5 to 2.5 mm²
(rigid)

0.5 to 1.5 mm²
(stranded)

Without priority

Network-Genset.

Automatic retransfer

Manual Retransfer

I1: 207 / 209

Network/Network

Source priority 1

Dry potential free 
contact

Source priority 2

Network-Genset.

Stop the test on load

Test on load

I3: 207 / 210

Network-Network or 
Network-Generating 
set

AUTO mode

Dry potential free 
contact

Automatic mode inhibition

Outputs O1: 63 / 64

Network-Network or 
Network-Generating 
set

Product not available : 
- Manual mode 
- Command default 
- Electronic default 
- No source

Resistive load
2A 30 Vdc
0.5A 230Vac
Pmax : 60W or 125VA
Umax : 30Vdc or 
230Vac

Product available

O2: 73 / 74

Network-Genset.

No start command genset

Resistive load
2A 30 Vdc
0.5A 230Vac
Pmax : 60W or 125VA
Umax : 30Vdc or 
230Vac

Generating set starting

Pozidriv PZ2 - 1 Nm

Use 20mm 

screws for 

1 module

Use 35mm 

screws for 

2 modules

!

Auxiliary contacts: 

Fitting of auxiliary contacts: 

1309  1001 or 1309  1011

To fit an AC, the switch must first be put in position 0. An auxiliary contact module comprises: one NO/

NC changeover contact for each position (I-0-II). To install use the long screws supplied with the module. 

OK

OK

OK

OK

Allen size 4

Hexagonal Metric

44.1 lb-in

  5,0 Nm

15 mm /

 0,59 "

# 8 to # 00 AWG

10  to  70 mm

2

10  to  70 mm

2

*

# 8 to # 00 AWG

!

X4

OK

OK

OK

OK

Allen size 4

Hexagonal Metric

44.1 lb-in

  5,0 Nm

15 mm /

 0,59 "

# 8 to # 00 AWG

10  to  70 mm

2

10  to  70 mm

2

*

# 8 to # 00 AWG

!

X4

Step 1

Step 2

Step 3

CORPORATE HQ CONTACT:  

SOCOMEC SAS, 1-4 RUE DE WESTHOUSE, 67235 BENFELD, FRANCE

542955E

Summary of Contents for ATyS g M

Page 1: ...Automatic Transfer Switching Equipment ATyS g M INSTALLATION AND OPERATING MANUAL EN...

Page 2: ...N 19 8 1 Changing the padlocking configuration 19 8 2 Recommanded orientation 19 8 3 Dimensions of the single phase 19 8 4 Back plate mounted single phase 19 8 5 Dimensions of the three phase 20 8 6 B...

Page 3: ...s designation 31 12 2 Auxiliary contact operating schedule 32 13 OPERATION 33 13 1 Presentation of the product interface 33 13 1 1 2P product interface 33 13 1 2 4P product interface 33 13 1 3 Reset 3...

Page 4: ...age to equipment This instruction manual must be made accessible so as to be easily available to anyone who may need to read it in relation with the ATyS The ATyS meets the European Directives governi...

Page 5: ...ible position indication I 0 II An inherent failsafe mechanical interlock Stable positions I 0 II non affected by typical vibration and shocks Constant pressure on the contacts non affected by network...

Page 6: ...RANSITION MOTORISED CHANGEOVER SWITCH DUAL POWER SUPPLY BUILT IN ATS CONTROLLER COMMUNICATION Specific version Return to zero without external energy source TRIPPING A product for virtually all power...

Page 7: ...switch By screen keyboard Vn Fn V threshold F threshold Driving with or without priority Adjustable operating timers Preset configuration Control type impulse or switch contactor DISPLAY Position ful...

Page 8: ...dropped or damaged in any way it is recommended to replace the complete product Accessories n Bridging bars and 125A or 160A n Control voltage transformer 400Vac 230Vac n Voltage sensine and power su...

Page 9: ...il 2x 2x llage DIN RAIL IEC 60715 MAX 2 235 26 116 53 46 73 5 245 143 350 18 45 13 222 235 131 5 131 5 47 52 176 224 MAX 2 235 26 116 53 46 73 5 245 143 350 18 45 13 222 4 mounting brackets 6x M6 scre...

Page 10: ...ing Source 1 available Source 1 not available or out of range a timer is counting down test mode Source 2 available Source 2 not available or out of range a timer is counting down Source availability...

Page 11: ...ATyS g M 542933D SOCOMEC 11 EN...

Page 12: ...ting informations 1 color Black White paper 90g m2 Printing size 420x297 Final size 210x297 This page visible first A separate sheet for each language Non contractual document Subject to change withou...

Page 13: ...elivered with padlocking configured to the O position To allow padlocking in all positions I O II configure the ATyS M as follows before installation Screw is located at the back of the product Posidr...

Page 14: ...he Auto Manual cover Commissioning must always result in having at least 1 LED source available on Therefore the voltage and frequency must be within the defined thresholds Any action on the potentiom...

Page 15: ...ATyS g M 542933D SOCOMEC 15 EN...

Page 16: ...o the top of the switch with the motorisation on the right hand side as shown 4 2 Specifications and advantages 1 Power section A fully integrated and interlocked transfer switch with high electrical...

Page 17: ...9 9006 Extension unit Combined with the polycarbonate enclosure the extension box creates extra space for routing cables with a larger diameter Ref 1309 9007 Single phase residential enclosure Dedicat...

Page 18: ...fuses Fuse protected short circuit withstand kA eff 50 50 50 50 50 40 Associated fuses gG DIN 40 63 80 100 125 160 Short circuit capacity Rated short term withstand current Icw 1s kA eff 4 4 4 4 4 4 R...

Page 19: ...0 C with de rating see Technical Characteristics Altitude Up to 2000m Correction factors 2 000 m A 3 000 m 3 000 m A 4 000 m UE 0 95 0 80 Ie 0 85 0 85 Storage 1 year maximum Maximum storage temperatur...

Page 20: ...w at the back of the product as shown below STEP2 slide the screw upwards STEP3 tighten the screw in the top position as shown 2 2x 3 Posidriv PZ2 2 2 lb in 0 25 Nm Posidriv PZ2 2x 1 Posidriv PZ2 2x 8...

Page 21: ...three phase MAX 2 53 46 73 5 245 18 45 MAX 2 340 26 116 53 46 73 5 245 143 350 18 45 13 324 340 326 131 5 131 5 52 104 176 47 6 mounting brackets 6x M6 screw 2 5 Nm 8 7 DIN rail mounted 2 clips de ver...

Page 22: ...al cages without reducing the cage connection capacity 2 parts ref Do not use in case of use of the bridging bar 6 mm Slotted head 3 5 mm 0 45 Nm 0 5 to 2 5 mm 0 5 to 1 5 mm 9 3 Bridging bars 2P Ratin...

Page 23: ...I Source I Source II Source II Allen size 4 Hexagonal Metric 44 1 lb in 5 0 Nm 15 mm 0 59 8 to 00 AWG 10 to 70 mm2 6 to 70 mm2 10 to 00 AWG X Allen size 4 Hexagonal Metric 44 1 lb in 5 0 Nm 15 mm 0 59...

Page 24: ...sions and mounting for 2P ATyS M products only The enclosure must be wall mounted using screws not supplied Recommended size M6 50 mm minimum Weight between 8 and 10 kg depending on the accessories On...

Page 25: ...um Weight between 8 and 10 kg depending on the accessories Only 1 aux contact block may be installed when using this enclosure 193 mm 225 mm M6 275 mm M6 385 mm 385 mm 10 2 1 Wiring in a polycarbonate...

Page 26: ...25 35 50 50 Max cable size recommended mm2 50 50 50 50 70 70 With extension unit Maximum cable size for rigid cable is 50 mm2 For larger terminations use the power connection terminals ref 1399 4017...

Page 27: ...TEST PRIORITY AUT 63 64 73 74 207208209210 63 64 73 74 2A 30Vdc 1A 125Vac 0 5A 230Vac resistive max 60W or 250VA 2A 30Vdc 1A 125Vac 0 5A 230Vac resistive max 60W or 250VA START STOP OK NOK 2 4 6 8 1...

Page 28: ...30Vdc 1A 125Vac 0 5A 230Vac resistive max 60W or 250VA START STOP FAULT OK 2 4 6 8 1 3 5 7 2 4 6 8 1 3 5 7 2 4 6 8 1 3 5 7 2 4 6 8 1 3 5 7 AUT 5 A AC1 250 Vac 12 14 11 21 24 22 01 04 02 OK OK OK OK T...

Page 29: ...below shows the wiring for a product configured with neutral on the left A new product must have the neutral configuration pre programmed as on the left or on the right at the first start up using a...

Page 30: ...c resistive max 60W or 250VA 2A 30Vdc 1A 125Vac 0 5A 230Vac resistive max 60W or 250VA START STOP OK NOK 2 4 6 8 1 3 5 7 2 4 6 8 1 3 5 7 2 4 6 8 1 3 5 7 2 4 6 8 1 3 5 7 AUT 5 A AC1 250 Vac 12 14 11 21...

Page 31: ...head 3 mm 3 97 lb in 0 5Nm 2 4 6 8 1 3 5 7 2 4 6 8 1 3 5 7 2 4 6 8 1 3 5 7 2 4 6 8 1 3 5 7 I1 I2 I3 O1 O2 207208209210 63 64 73 74 I1 I2 I3 O1 O2 5 A AC1 250 Vac 22 24 21 11 14 12 01 04 02 5 A AC1 250...

Page 32: ...d 2A 30 Vdc 0 5A 230Vac Pmax 60W or 125VA Umax 30Vdc or 230Vac Product available O2 73 74 Network Genset No start command genset Resistive load 2A 30 Vdc 0 5A 230Vac Pmax 60W or 125VA Umax 30Vdc or 23...

Page 33: ...t operating schedule Position I Position 0 Position II C A Position I C A Position 0 C A Position II 11 14 Closed 11 12 Open 01 04 Closed 01 02 Open 21 24 Closed 21 22 Open Position I Position 0 Posit...

Page 34: ...3 Auto LED 4 Dip switchs 5 Adjustment potentiometers of the rated voltage and frequency and voltage thresholds 6 Potentiometers to set timers 6 1 5 5 6 6 2 3 1 2 5 3 4 1 Locking Option to padlock usin...

Page 35: ...Changeover switching Manual DIP switch programmation MANUAL MODE 13 2 1 Manual switching Use the handle situated on the front panel under the cover to manoeuvre the changeover switch To simplify the...

Page 36: ...dlocking to all positions before installation as access to configuration is at the back of the product Refer to section 7 1 Changing the padlocking configuration page 19 Locking is only possible in ma...

Page 37: ...equency Auto Configurationsettings Stop in 0 position E F E No stop in O position F 2s stop in O position Type of application G H G Network Genset H Network Network HYST 20 U F U 5 20 F 3 10 Loss of p...

Page 38: ...osition Type of application G H G Network Genset H Network Network Loss of priority source timer FT FT 0 60 sec U F HYST HYST Return of priority source timer RT RT 0 30 min U F 127 230 Vac version Un...

Page 39: ...Make sure that the changeover switch is in automatic mode AUT LED lit 13 5 1 Sealable Auto Manual cover Auto Manu mode can be protected by sealing the standard Auto Manu cover as shown 13 6 Possible a...

Page 40: ...he power reserves Mode settings G H 207 208 207 208 MODE 1 MODE 3 MODE 2 MODE 4 AUT Priority MODE AUT Priority 13 7 1 Mode 1 Automatic retransfer Network Genset applications Contact 207 208 open autom...

Page 41: ...application Source 1 available Product in position I Contact 207 208 open Contact 207 209 open Genset start order Genset available Transfert I II Transfert I I I Genset stop Return of source 1 Loss o...

Page 42: ...5 sec 4 min 5 sec 5 sec RT 5 sec FT 207 208 207 208 NORMAL PRIORITY II TEST Transfer from I to II Product in position I Source available Source missing Timer is counting down Genset available Genset m...

Page 43: ...pplication Source 1 available Product in position I Contact 207 208 closed Contact 207 209 open Genset start Transfert I II Transfert I I I Genset stop Return of source 1 Opening of contact 207 208 Lo...

Page 44: ...twork Genset Source 1 available Product in position I Contact 207 208 open or closed Contact 207 209 open Transfert I II Loss of genset Opening of contact 207 209 Transfert I I I Genset stop End of CD...

Page 45: ...nctioning with priority NORMAL PRIORITY II TEST Transfer from I to II Product in position I Source available Source missing Timer is counting down 207 209 207 209 TEST PRIORITY PRIORITY TEST 5 sec 5 s...

Page 46: ...of source 1 Loss of source 2 Network Network application Sources 1 and 2 available Product in position I Contact 207 208 open Contact 207 209 open Transfert I II Transfert I I I Return of source 1 Re...

Page 47: ...Sources 1 and 2 available Product in position I Contact 207 208 open Contact 207 209 open Transfert I II Opening of contact 207 209 Closing of contact 207 209 Priority source 2 Transfert I I I Transf...

Page 48: ...ng Timer is counting down 207 209 207 209 TEST TEST 5 sec 5 sec FT FT ou ou Transfer from I to II Product in position I Source available Source missing Timer is counting down NORMAL PRIORITY II TEST Y...

Page 49: ...Network application Sources 1 and 2 available Product in position I Contact 207 208 closed Contact 207 209 open Transfert I II Impulsion of contact 207 209 Impulsion of contact 207 209 Transfert I I...

Page 50: ...the critical level and application where the product is installed should form an essential and integral part of the maintenance plan Good engineering practice is imperative whilst all necessary preca...

Page 51: ...is detected upon first switching on Step 2 Connect the autotransformers Warning Neutral must be connected on the same side as in step 1 How to reset the neutral position Step 1 Open the cover Step 2...