ATyS Controller A15 - 549779A - SOCOMEC

ATyS r

ATyS r products are 3 or 4 pole remotely operated motorised transfer switches 
with  positive  break  indication.  They  enable  the  on-load  transfer  of  two  three-
phase  power  supplies  via  remote  volt-free  contacts,  from  either  an  external 
automatic controller, using pulse logic, or a switch. They are intended for use in 
low voltage power systems where interruption of the load supply is acceptable 
during transfer. 

References

Rating (A) /

Frame size

No. of poles

ATyS r

Bridging bars

Terminal 

shrouds

Terminal 

screens

Auxiliary 

contact

3 position 

padlocking

Auto 

transformer

125 A / B3

3 P

9523

 3012

3 P

4109

 3019

4 P

4109

 4019

3 P

2694

 3014

(2)

4 P

2694

 4014

(2)

3 P

1509

 3012

4 P

1509

 4012

1599

 0502

9599

 0003

(3)

400/230 VAC

1599

 4064

4 P

9523

 4012

160 A / B3

3 P

9523

 3016

4 P

9523

 4016

200 A / B3

3 P

9523

 3020

4 P

9523

 4020

250 A / B4

3 P

9523

 3025

3 P

4109

 3025

4 P

4109

 4025

3 P

2694

 3021

(2)

4 P

2694

 4021

(2)

3 P

1509

 3025

4 P

1509

 4025

4 P

9523

 4025

315 A / B4

3 P

9523

 3031

3 P

4109

 3039

4 P

4109

 4039

4 P

9523

 4031

400 A / B4

3 P

9523

 3040

4 P

9523

 4040

500 A / B5

3 P

9523

 3050

3 P

4109

 3050

4 P

4109

 4050

3 P

2694

 3051

(2)

4 P

2694

 4051

(2)

3 P

1509

 3063

4 P

1509

 4063

4 P

9523

 4050

630 A / B5

3 P

9523

 3063

3 P

4109

 3063

4 P

4109

 4063

4 P

9523

 4063

800 A / B6

3 P

9523

 3080

3 P

4109

 3080

4 P

4109

 4080

3 P

1509

 3080

4 P

1509

 4080

1599

 0532

9599

 0004

(3)

4 P

9523

 4080

1000 A / B6

3 P

9523

 3100

4 P

9523

 4100

1250 A / B6

3 P

9523

 3120

3 P

4109

 3120

4 P

4109

 4120

4 P

9523

 4120

1600 A / B7

3 P

9523

 3160

3 P

4109

 3160

4 P

4109

 4160

3 P

1509

 3160

4 P

1509

 4160

4 P

9523

 4160

2000 A / B8

3 P

9523

 3200

(1)

3 P

1509

 3200

4 P

1509

 4200

included

4 P

9523

 4200

2500 A / B8

3 P

9523

 3250

4 P

9523

 4250

3200 A / B8

3 P

9523

 3320

4 P

9523

 4320

(1) See “Copper bar connection pieces”.
(2)  To fully shroud front, rear, top and bottom 4 references required. 

To shroud front switch top and bottom 2 references required (Whenever a bridging beam is fitted, it is then only possible to fit 3 times the reference for the terminal cover).

(3) Factory mounting only.

Summary of Contents for ATyS A15

Page 1: ...www socomec com To download brochures catalogues and technical manuals ATS Controller ATyS A15 INSTRUCTION MANUAL EN...

Page 2: ...6 4 ATYS A15 ACCESSORIES AND COMPATIBLE PRODUCTS 12 7 CONTENT OF PACKAGING 12 8 INSTALLATION 13 8 1 PRODUCT DIMENSIONS 13 8 2 MOUNTING 13 8 2 1 DOOR MOUNTING 13 8 2 2 DIN RAIL MOUNTING 14 9 CONNECTION...

Page 3: ...5 2 CONNECTION DIAGRAMS 31 15 2 1 CONNECTIONS WITH ATYS S 31 15 2 2 CONNECTIONS WITH ATYS DM 32 15 2 3 CONNECTIONS WITH STANDARD CC TYPE BASED TSE 33 15 3 PHASE ROTATION CHECK 34 15 4 VOLTAGE FREQUENC...

Page 4: ...ge to equipment This instruction manual must be made accessible so as to be easily available to anyone who may need to read it in relation with the ATyS A15 The ATyS A15 meets the European Directives...

Page 5: ...LVD Low voltage directive 2014 35 UE EMC according to IEC EN 60947 6 1 and GB T 14048 11 including annex C IEC EN 61326 1 standard Vibration according to IEC 60068 2 6 GB T 2324 10 Shock test accordi...

Page 6: ...compatible with use with PC and CC type RTSE ATyS A15 ATS Controller Ensures Monitoring of the availability of a Normal and Alternate source Supply to the controller and switch from the Normal or Alt...

Page 7: ...er only For all other ATyS family of products please refer to the specific instruction manual related to that product Available for download on www socomec com An overview of the complete ATyS range i...

Page 8: ...uency hysteresis value is 20 of U F B Overvoltage setting at 20 of nom voltage overfrequency setting 10 of nominal frequency hysteresis value is 20 of U F 5 0DT A Load supply down time of 2 second 0DT...

Page 9: ...A15 549779A SOCOMEC 6 GENERAL OVERVIEW 6 1 Product identification 1 2 3 4 5 6 1 AUTO Manual selector 2 Controller state LED 3 Remote position order selector 4 ATSE Synoptic 5 Test function selector 6...

Page 10: ...y information Green fixed when source 2 is present and available within threshold limits green blinking when source 2 is present but outside of threshold limits off when under 50VAC 7 Auto LED indicat...

Page 11: ...sation at 40 C according to IEC 61010 1 95 humidity without condensation 50 C according to GB14 11 Annex Q 6 3 4 EMC IEC EN 60947 6 1 and GB T 14048 11 including annex C standards IEC EN 61326 1 6 3 5...

Page 12: ...S The ATyS A15 is compatible and compliant according to IEC 60947 6 1 when used with the following IEC 60947 6 1 SOCOMEC RTSE and specific product connection harness ATyS S from 40 125A ATyS dM from 4...

Page 13: ...sions in mm 5 93 96 8 2 Mounting 8 2 1 Door mounting Door cut out of 93 0 8 x138 1 mm door thickness 1 5 3mm Remove all connectors and clip before inserting the controller in the cut out then fix the...

Page 14: ...COMEC 8 2 2 DIN RAIL mounting Install on IEC 60715 Standard Din RAIL When mounting make sure both clips are pushed up then clip on the DIN Rail To remove from the DIN Rail drag the two mounting clips...

Page 15: ...rks 1P N The A15 is suitable for single phase networks for with voltages within 184 300 V a c Ph N In these networks the phase must be connected to the L1 input terminal 104 for source 1 and 204 for s...

Page 16: ...1 N 1 3 2 N Voltage sensing Source 1 V1 U12 U23 U31 V1 V2 V3 Source 2 V1 U12 U23 U31 V1 V2 V3 Source presence source available a a Source in ranges U V F a a CAUTION In 3 phases with Neutral balanced...

Page 17: ...5 BOTTOM 6 7 8 9 1 RTSE position feedback input 2 24 V d c fire input 3 Enable control when closed disable control when open 4 Not used 5 Genset Start relay 6 RTSE position control outputs 7 Source 1...

Page 18: ...316317 63A64A 24 14 04 13 64A63A 51 54 52 F1 73 72 F2 71 70 14 15 16 17 103 102 101 302 301202 201 104105106 203 204205206 L1 L2 L3 N L1 L2 L3 N 318 520 ph ph 184 300 ph n 318 520 ph ph 184 300 ph n 0...

Page 19: ...m common point 0 5 1 5mm 0 2 Nm M2 64A Return of information from RTSE Position inputs 70 Common point for position inputs Do not use external voltage Power from common point 71 Position I RTSE 72 Pos...

Page 20: ...d that the fault LED 12 or the TEST LED 8 are not activated and then press the button for 3 seconds the LED 7 should then turn ON Manual mode In this mode the manual orders buttons enable manual order...

Page 21: ...as well as the ATyS A15 automation The parameters monitored through the sensing are the following Phase rotation When both sources are available the controller will check that the phase rotation is id...

Page 22: ...um 5s and are stopped when either 5s has expired or the controller received feedback that the RTSE has reached the requested position If 5s expire and the RTSE has not reached the requested position t...

Page 23: ...that the position input corresponding to this order has closed If this is not the case the controller fault LED will blink and the buzzer will be on to clear the fault expected position input should b...

Page 24: ...back to the original position without pressing the button the Fault LED will also stop blinking and the configuration will remain the same DIP Switch 1 Network A Three phase network B Single phase net...

Page 25: ...appropriate protection equipment It is recommended to verify at least once a year the tightening torque of all connections and to operate the product in a full operating cycle I 0 II 0 I Auto and Man...

Page 26: ...onfigured through DIP switch or communication Verify that the sources are cabled correctly Verify that the phase rotation Alarm LED is blinking Verify that the input 63 64 is closed Verify that there...

Page 27: ...stream protection please order 2x for the single phase version please order the part just 1x 2 1 NO NC contact block for positions I 0 and II ATyS S ATyS S products are 4 pole re motely operated trans...

Page 28: ...2 4 P 2694 4021 2 3 P 1509 3025 4 P 1509 4025 4 P 9523 4025 315 A B4 3 P 9523 3031 3 P 4109 3039 4 P 4109 4039 4 P 9523 4031 400 A B4 3 P 9523 3040 4 P 9523 4040 500 A B5 3 P 9523 3050 3 P 4109 3050...

Page 29: ...position 2 6 Source 2 availability information Green fixed when source 2 is present and available within threshold limits green blinking when source 2 is present but outside of threshold limits off w...

Page 30: ...ition II Load is connected to source 1 RTSE is not in position II Load is not connected to source 1 6 Source 2 availability Source 2 present but not available for following possible reason Source unde...

Page 31: ...64A63A 51 54 52 F1 73 72 F2 71 70 14 15 16 17 103 102 101 302 301202 201 104105106 203 204205206 L1 L2 L3 N L1 L2 L3 N 318 520 ph ph 184 300 ph n 318 520 ph ph 184 300 ph n 0 II I C II II I I 0 0 C II...

Page 32: ...22 24 21 I 11 14 12 O 01 04 02 13091011 64A63A 51 54 52 F1 73 72 F2 71 70 14 15 16 17 103 102 101 302 301202 201 104105106 203 204205206 318 520 ph ph 184 300 ph n OR 0 II I C II 81 82 I 0 C Auxsupply...

Page 33: ...54 52 F1 73 72 F2 71 70 14 15 16 17 103 102 101 302 301202 201 104105106 203 204205206 L1 K1 K2 L2 L3 N L1 L2 L3 N 318 520 ph ph 184 300 ph n 329 520 ph ph 190 300 ph n 0 II I C K2 II 81 82 I 0 C Aux...

Page 34: ...ed value The default value for nominal voltage is 230 V a c and the default value for nominal frequency is 50Hz To reboot the product press the button for 30s this will restart the product and take in...

Page 35: ...1 in this case when source 1 is available the controller will give the order to switch to position I No prio if both sources are available the controller will give the order to remain in the current p...

Page 36: ...36 EN ATyS Controller A15 549779A SOCOMEC 15 8 A15 Operating sequence Controller operating sequence with source 1 priority DPS Output operating sequence...

Page 37: ...37 EN ATyS Controller A15 549779A SOCOMEC...

Page 38: ...Non contractual document 2020 Socomec SAS All rights reserved CORPORATE HQ CONTACT SOCOMEC SAS 1 4 RUE DE WESTHOUSE 67235 BENFELD FRANCE www socomec com 549779A...

Reviews: