background image

5

COUNTIS E13/E14

 - Ref.: 542 101 A

COUNTIS E13/E14 MODBUS

5. Installation

5.1. Recommendations

•   avoid proximity to systems which generate electromagnetic interference,
•   avoid vibrations with accelerations in excess of 1 G for frequencies below 50 Hz.

5.2. Dimensions (mm)

64

45

6

90

44

L1

N

L1

1 2 3 4

6

5

54

5.3. Terminals

64

45

6

90

44

L1

N

L1

1 2 3 4

6

5

54

0.61 in/15.5 mm

PZ2

flexible or rigid  
7 to 50 mm

2

2 Nm

0.35 in/9 mm

PZ2

flexible 1.5 to 2.5  
rigid 1 to 4 mm

2

0.8 Nm

Summary of Contents for 4850 3031

Page 1: ...COUNTIS E13 E14 Single phase active energy meter 80 A direct MODBUS Operating instructions EN ...

Page 2: ... 3 TERMINALS 5 5 4 CONNECTIONS 6 5 4 1 2 WIRE CONNECTION 1 WIRE LOAD MONITORING 6 5 5 SEALABLE COVERS 6 6 MODBUS COMMUNICATION 7 6 1 GENERAL POINTS 7 6 2 RECOMMENDATIONS 7 6 3 COMMUNICATION STRUCTURE 7 6 4 COMMUNICATION TABLE 7 7 PROGRAMMING 8 7 1 NAVIGATION PRINCIPLE 8 7 2 PROGRAMMING MENU OVERVIEW 8 7 3 DETAILED VIEW OF MODBUS PROGRAMMING MENU 9 8 OPERATION 10 8 1 DETAILED VIEW OF MENUS 11 9 DIA...

Page 3: ... turning on power to this equipment Always supply the device with the correct rated voltage Failure to take these precautions could cause serious injuries 2 2 Risk of damaging device Check the following the mains frequency 50 Hz the maximum voltage at the voltage input terminals is 276 VAC phase neutral a maximum current of 80 A 3 Preliminary operations For personnel and product safety please care...

Page 4: ... Active power P1 P1 Reactive power Q1 Q1 Apparent power S1 Power factor PF1 PF1 Total active energy Ea Ea Total positive reactive energy Er Positive active energy per tariff Ea Positive reactive energy per tariff Er MODBUS communication MID version according to reference Description Reference COUNTIS E13 4850 3031 COUNTIS E14 MID 4850 3032 4 2 Display views COUNTIS E13 ref 4850 3031 COUNTIS E14 MI...

Page 5: ... electromagnetic interference avoid vibrations with accelerations in excess of 1 G for frequencies below 50 Hz 5 2 Dimensions mm 64 45 6 90 44 L1 N L1 1 2 3 4 6 5 54 5 3 Terminals 64 45 6 90 44 L1 N L1 1 2 3 4 6 5 54 0 61 in 15 5 mm PZ2 flexible or rigid 7 to 50 mm2 2 Nm 0 35 in 9 mm PZ2 flexible 1 5 to 2 5 rigid 1 to 4 mm2 0 8 Nm ...

Page 6: ...DBUS 1 Activation of 120 ohm terminating resistors by connecting terminals 1 and 2 2 3 4 NC not connected Tariff 5 6 Change of tariff only for COUNTIS E14 0 VAC Tariff 1 230 VAC Tariff 2 change of tariff via MODBUS for COUNTIS E13 Mains L1 Phase input L1 Phase output N Neutral connection 5 5 Sealable covers COUNTIS E14 MID Label scaled between front and rear faces Plastic seal Terminal covers ...

Page 7: ...ork in terms of length we recommend the use of a shielded twisted pair type LIYCY CY A repeater should be used to connect additional products if the distance of 1200 m and or maximum number of 32 products is exceeded A 120 ohm resistor must be fixed at both ends of the link 6 3 Communication structure The product communicates via a MODBUS protocol which involves a dialogue using a master slave str...

Page 8: ...programming mode is described in the following steps Access to item to set 4 sec Enter programming mode press button for 4 seconds Value to be modified 4 sec Validate the value 7 2 Programming menu overview By pressing for 4 seconds the device will enter the programming mode The various screens are accessible according to the sequence Programming mode Address Communication speed ...

Page 9: ...9 COUNTIS E13 E14 Ref 542 101 A COUNTIS E13 E14 MODBUS 7 3 Detailed view of MODBUS programming menu x 10 Address 4 sec 4 sec x 1 Communication speed 4 sec 4 sec x 1 ...

Page 10: ...scribed in the following diagram Tariff T1 Ea kWh P kW ______________ Tariff T1 Ea kWh P kW ______________ Tariff T1 Er kvarh Q kvar ______________ Tariff T1 Er kvarh Q kvar ______________ Tariff T2 Ea kWh P kW ______________ Tariff T2 Ea kWh P kW ______________ Tariff T2 Er kvarh Q kvar ______________ Tariff T2 Er kvarh Q kvar ______________ MODBUS address ______________ Communication speed Note ...

Page 11: ...T2 or Ea kWh P kW Tariff T1 T2 Depending on the current tariff and energy x 1 Ea kWh Tariff T1 Ea kWh Tariff T1 Er kVarh Tariff T1 Er kVarh Tariff T1 Ea kWh Tariff T2 Ea kWh Tariff T2 Er kVarh Tariff T2 Er kVarh Tariff T2 P kW and Q kvar power values are only displayed for the current tariff x 7 MODBUS x 1 ...

Page 12: ...13 E14 Ref 542 101 A 9 Diagnostic message When these messages are displayed the meter has malfunctioned and should be replaced 10 Assistance Causes Solutions Error message Check that the meter is working correctly ...

Page 13: ...tive power and energy E13 Class 1 IEC 62053 21 Reactive power and energy Class 2 IEC 62053 23 Active power and energy E14 Class B EN 50470 3 Input measurement Connection type direct phase N Voltage measurement range 110 276 VAC phase N Current Iref 5 A Current Imin 0 25 A Current measurement range Ist Imax 0 020 80 A Certified frequency 50 Hz Start up current for energy measurement Ist 20 mA Optic...

Page 14: ...tic seals supplied with the product see 5 5 Sealable covers page 6 If the terminal covers must be removed ensure that seal part number 4850 304U is used The information given via the communication bus is only sent by way of information and has no legal value The assigned operating conditions guaranteeing MID compliance are available in the technical specifications tables The MID declaration of con...

Page 15: ...15 COUNTIS E13 E14 Ref 542 101 A COUNTIS E13 E14 MODBUS ...

Page 16: ... info si socomec com SPAIN Critical Power Power Control Safety Energy Efficiency Solar Power Tel 34 93 540 75 75 Fax 34 93 540 75 76 info es socomec com TURKEy Critical Power Power Control Safety Energy Efficiency Solar Power Tel 90 216 540 71 20 21 22 Fax 90 216 540 71 27 info tr socomec com UNITED KINGDOM Critical Power Tel 44 1285 863 300 Fax 44 1285 862 304 info ups uk socomec com Power Contro...

Reviews: