9
SS004V2
Specification
Wiring Test
Detects missing E or N (>15k
Ω)
Detects L-E or L-N swap
Detects Network Supply Live - Earth/Neutral reversal by use of Polarity Test
Pad.
Phase - Neutral voltage measurement accuracy to 1% and displayed on 3
LED’s
< 207 VAC
LOW
207- 253 VAC
STANDARD
< 253 VAC
HIGH
Loop Test
(No trip mode, 3 wire testing, Phase - Neutral - Earth all connected)
Test current <15mA at 253V AC
Range
Accuracy
<1
Ω
Each breakpoint has an accuracy of + 10%
<2Ω
Each breakpoint has an accuracy of + 10%
<20Ω
Each breakpoint has an accuracy of + 10%
<200Ω
Each breakpoint has an accuracy of + 10%
>200Ω
Each breakpoint has an accuracy of + 10%