Smith Cast Iron Boilers GB250 SERIES Installation & Operation Manual Download Page 3

VENTING REQUIREMENTS

When connecting to gas vents or chimneys, vent instal-
lations shall be in accordance with Part 7, Venting of
Equipment, of the National Fuel Gas Code, ANSI
Z223.1-latest edition, or applicable provisions of the
local building codes. For Canada, the provisions of
B149.1 and B149.2 shall apply.

Vent connectors serving appliances vented by natural
draft shall not be connected into any portion of mechani-
cal draft systems operating under positive pressure.

When two or more appliances vent into a common flue,
the area of the common flue should be at least equal to
the area of the largest flue plus 50% of the areas of the
additional flue or vent connectors.

When an existing boiler is removed from common
venting system, common venting system is likely to be
too large for proper venting of appliances remaining
connected to it. At time of removal of existing boiler, the
following steps shall be followed with each appliance
remaining connected to the common venting system
placed in operation, while other appliances remaining
connected to the common venting system are not in
operation:

1. Seal all unused openings in common venting system.

2. Visually inspect the venting system for proper size
and horizontal pitch and determine there is no blockage
or restriction, leakage, corrosion and other deficiencies
which could cause an unsafe condition.

3. Insofar as is practical, close all building doors and
windows and all doors between the space in which the
appliances remaining connected to the common venting
system are located and other spaces of the building.
Turn on clothes dryers and any appliance not connected
to the common venting system. Turn on any exhaust
fans, such as range hoods and bathroom exhausts, so
they will operate at maximum speed. Do not operate a
summer exhaust fan. Close fireplace dampers.

4. Place in operation the appliance being inspected. Fo-
llow the lighting instructions. Adjust thermostat so
appliance will operate continuously.

5. Test for spillage at draft hood relief opening after 5
minutes of main burner operation. Use the flame of a
match or candle, or smoke from cigarette, cigar or pipe.

6. After it has been determined that each appliance
remaining connected to common venting system proper-
ly vents when tested as outlined above, return doors,
windows, exhaust fans, fireplace dampers and any other
gas-burning appliance to previous conditions of use.

7. Any improper operation of the common venting sys-
tem should be corrected so the installation conforms
with National Fuel Gas Code, ANSI Z223.1-latest
edition. When resizing any portion of the common
venting system, the common venting system should be
resized to approach the minimum size as determined
using the appropriate tables in Appendix G in the
National Fuel Gas Code, ANSI Z223.1-latest edition.
For Canada, the provisions of B149.1 and B149.2 shall
apply.

CHIMNEY REQUIREMENTS

Chimney condition is of paramount importance for a
safe and efficient boiler installation. All new and replace-
ment installations must include a chimney inspection by
a qualified individual or agency. Chimney construction
materials must be compatible with the fuel being used.

Particular attention should be paid on all oil-to-gas con-
versions. Soot may have accumulated in chimney and/or
degraded chimney liner. Most utilities require complete
chimney cleaning. Others may require installation of new
liner, spill switches or other chimney upgrades. Check
with local utility for required safety precautions.

COMBUSTION AIR REQUIREMENTS

Provisions for combustion air must be in accordance
with the National Fuel Gas Code ANSI Z223.1 - latest
edition, as well as all applicable local codes. If the boiler
is installed in an unconfined space, adequate air will be
available via normal infiltration. However, if building
construction is unusually tight or the boiler is installed in
a confined space (a space whose volume is less than 50
cubic feet per 1000 Btu/hr of gas input for all fuel
burning equipment), adequate air for combustion must
be provided by two openings: one located about 6”
below the ceiling, the other about 6” above the floor.
When communicating directly with the outside or
through a vertical duct, each opening must have a
minimum free area of one square inch per 4000 Btu/hr
of gas input. Horizontal ducts to the outside must have a
minimum free area of one square inch per 2000 Btu/hr
of gas input. When ventilation is provided by openings in
doors, etc. to adjoining spaces having adequate
infiltration, each opening must have a minimum free
area of one square inch per 1000 Btu/hr of gas input.

3

DANGER: A chimney which does not meet modern
safety standards will result in a fire or deadly carbon
monoxide poisoning of the building residents.

Summary of Contents for GB250 SERIES

Page 1: ...pment of Boiler 4 SECTION 2 BOILER INSTALLATION Step 1 Locating Setting Boiler 5 Step 2 Installing Steam Piping 6 Step 3 Installing Hydronic Components 7 Step 4 Venting Boiler 7 Step 5 Installing Testing Gas Piping 10 Step 6 Wiring Boiler 11 SECTION 3 START UP OPERATION Sequence Of Operation 16 Prior To Start Up 16 Start Up Adjustments 16 SECTION 4 MAINTENANCE Before Each Heating Season 19 How To ...

Page 2: ... local codes 2 DANGER Indicates an imminently hazardous situation which if not avoided will result in death serious injury or substantial property damage WARNING Indicates a potentially hazardous situation which if not avoided could result in death serious injury or substantial property damage CAUTION Indicates a potentially hazardous situation which if not avoided may result in minor injury or pr...

Page 3: ...utlined above return doors windows exhaust fans fireplace dampers and any other gas burning appliance to previous conditions of use 7 Any improper operation of the common venting sys tem should be corrected so the installation conforms with National Fuel Gas Code ANSI Z223 1 latest edition When resizing any portion of the common venting system the common venting system should be resized to approac...

Page 4: ...rubber seals Water treatment chemicals and system cleaning chemicals must be compatible with this and all other construction materials SHIPMENT OF BOILER Each boiler is shipped in a single carton Draft hood is shipped in a separate carton on larger models Optional Vent Damper When ordered the vent damper is shipped in an individual carton packaged with the boiler Mounting of the damper is required...

Page 5: ...s are proper as shown Local requirements may specify greater clearances must be adhered to Boiler shall be install ed such that the gas ignition system com ponents are protected from water dripping spraying rain etc during appliance oper ation and service WARNING Never install boiler on combustible flooring without combustible flooring pan or on carpeting as heat damage and or fire may result FIGU...

Page 6: ...ing connections are shown in Figure 2 3 All external piping must be supported by hangers not by the boiler or its accessories Supply outlet must run full size from boiler to a header at least 24 above top of boiler Condensate return piping should be connected to boiler through a Hartford Loop Install gate valves in supply and return Proper steam piping practices must be followed at all times Maint...

Page 7: ... and GB250 6 boilers Applicable boiler is equipped with a factory mounted spill switch harness mounting bracket assembly spill switch is provided in plastic bag See Figure 2 5 Install mounting bracket on outside surface of draft hood shroud with screws provided HARNESS MUST BE ON OUTSIDE OF SHROUD Install spill switch in hole in shroud on outside surface with screws provided Plug wiring leads from...

Page 8: ...t force it closed as it may damage the gear train and void the warranty The blade should move freely and without obstruction Secure the vent damper housing to the drafthood outlet with sheet metal screws or pop rivets Refer to Figure 2 8 for fastener locations Install flue pipe over top of vent damper and secure to damper housing with sheet metal screws or pop rivets Attach vent damper cable to ca...

Page 9: ...t draft hood relief opening after 5 minutes of main burner operation Use the flame of a match or candle or smoke from cigarette cigar or pipe 6 After it has been determined that each appliance remaining connected to common venting system properly vents when tested as outlined above return doors windows exhaust fans fireplace dampers and any other gas burning appliance to previous conditions of use...

Page 10: ...0 990 1 600 2 800 5 800 90 10 22 40 84 160 320 490 930 1 500 2 600 5 400 100 9 21 38 79 150 305 460 870 1 400 2 500 5 100 125 8 18 34 72 130 275 410 780 1 250 2 200 4 500 150 8 17 31 64 120 250 380 710 1 130 2 000 4 100 175 7 15 28 59 110 225 350 650 1 050 1 850 3 800 200 6 14 26 55 100 210 320 610 980 1 700 3 500 1 4 3 8 1 2 3 4 1 1 1 4 1 1 2 2 2 1 2 3 4 326 493 622 824 1 049 1 380 1 610 2 067 2 ...

Page 11: ... right of the primary pressuretrol when facing the front of the boiler Connect wiring assemblies provided on boiler from the low water cut off or transformer to the primary pressure control and from the gas valve to the secondary pressure control as shown in Fig 2 12 Do not readjust the secondary pressuretrol its purpose is to interrupt thermocouple power to the gas valve in case the primary press...

Page 12: ...NOTE Boiler transformer must not be used to power external accessories i e zone valves relays etc Otherwise transformer will be overloaded and burn out 12 FIGURE 2 13 WIRING DIAGRAM OPERATION SEQUENCE FOR BOILERS WITH STANDING PILOT MCDONNELL MILLER 67 LOW WATER CUT OFF EXCEPT GB250 8 GB250 9 N G FIGURE 2 14 WIRING DIAGRAM OPERATION SEQUENCE FOR BOILERS EQUIPPED WITH STANDING PILOT MCDONNELL MILLE...

Page 13: ...ILERS EQUIPPED WITH INTERMITTENT PILOT VENT DAMPER MCDONNELL MILLER 67 LOW WATER CUT OFF FIGURE 2 14 WIRING DIAGRAM OPERATION SEQUENCE FOR BOILERS EQUIPPED WITH STANDING PILOT VENT DAMPER MCDONNELL MILLER 67 LOW WATER CUT OFF EXCEPT FOR GB250 8 GB250 9 N G ...

Page 14: ...SEQUENCE FOR BOILERS EQUIPPED WITH STANDING PILOT VENT DAMPER MCDONNELL MILLER 67 LOW WATER CUT OFF FOR GB250 8 GB250 9 N G FIGURE 2 16 WIRING DIAGRAM OPERATION SEQUENCE FOR BOILERS EQUIPPED WITH INTERMITTENT PILOT VENT DAMPER 400 SERIES LWCO ...

Page 15: ...ATION SEQUENCE FOR BOILERS EQUIPPED WITH STANDING PILOT VENT DAMPER 400 SERIES LWCO EXCEPT FOR GB 250 8 9 FIGURE 2 18 WIRING DIAGRAM OPERATION SEQUENCE FOR BOILERS EQUIPPED WITH STANDING PILOT VENT DAMPER 400 SERIES LWCO GB250 8 9 ONLY ...

Page 16: ...er sits SYSTEM START UP ADJUSTMENTS Safe lighting and other performance criteria were met with the gas manifold and control assembly provided on the boiler when the boiler underwent tests specified in ANSI Z21 13 1 Check combination gas valve on boiler and make sure it is in the OFF position 2 For vent damper equipped models with the thermostat set to call for heat observe that vent damper positio...

Page 17: ...essures If rated input cannot be obtained with adjustment gas supply pressure or orifice size may be cause Consult local utility and Smith 8 Gas burner orifices supplied with boiler have been carefully designed to provide correct gas input rate for most gas conditions typically found in the U S and Canada Occasionally however local gas characteristics may not allow unit to be properly adjusted for...

Page 18: ...nclosing the pilot 7 Find pilot Follow metal tube from gas control The pilot is between the central burner tubes behind the base door 8 Turn knob on gas control counterclockwise to Pilot 9 Push down and hold the red button Immediately light the pilot with a match Continue to hold the red button down for about one 1 minute after the pilot is lit Release button and it will pop back up Pilot should r...

Page 19: ...ON THE TOP SURFACE UPRIGHT 5 When a low water cut off has been utilized follow the manufacturer s maintenance instructions As a minimum test the operation of electronic controls at least once a year Remove clean and inspect the probe If the LWCO fails to operate properly it must be replaced Float type controls should be flushed once a month during the heating season 6 Follow System Start Up Adjust...

Page 20: ...can also be checked by using a pin gauge 4 All orifices are screwed into the manifold and may be removed by using a 5 8 wrench or socket 5 Reverse procedures above to install orifices and burners BE SURE TO REINSTALL BURNERS WITH BURNER PORTS ON TOP SURFACE UPRIGHT HEATING SYSTEM PROBLEMS CAUSES No Heat 1 Blown fuse or circuit breaker 2 Switch turned off 3 Pilot outage 4 IID system malfunction 5 F...

Page 21: ...ld 63276 1 1 Manifold 59123 1 Manifold 63278 1 Manifold 59125 1 Manifold 59126 1 11 Burner Orifice No 31 N G 59141 6 Burner Orifice No 32 N G 59142 5 9 10 Burner Orifice No 33 N G 59143 8 Burner Orifice No 34 N G 59144 5 Burner Orifice No 52 L P 59150 5 5 6 8 9 10 MODEL GB250 SERIES REPLACEMENT PARTS LIST ORDERING INFORMATION When ordering replacement parts provide the model and serial number show...

Page 22: ...Hood 8 For Spill Switch 59217 1 Draft Hood 8 59218 1 Draft Hood 9 59219 1 1 31 Junction Box 4 x 4 60178 1 1 1 1 1 1 Silicone Sealant 11 oz 40440 3 8 Fiberglass Rope 5 Ft Block to Base Seal 60024 32 Vent Damper 7 w Harness Ass y 69496 1 1 Vent Damper 8 w Harness Ass y 69497 1 1 Vent Damper 9 w Harness Ass y 69498 1 1 Cable Bracket 59270 1 1 1 1 1 1 33 Manual Reset Spill Switch 59273 1 1 1 34 Manual...

Page 23: ...51B 1103 72360 1 1 Pilot Ass y L P Q3451B 1103 72361 1 N A N A Pilot Ass y L P Q3451B 1103 70008 1 10 Gas Valve N G VR8304P 4332 59136 1 1 1 1 1 1 Gas Valve L P VR8304P 3340 59137 1 1 1 Gas Valve L P VR8304P 4330 59138 1 1 1 Ignition Control S8600M 1013 51177 1 1 1 1 1 1 Ignition Cable 36 Lg 59308 1 1 1 1 1 1 30 Transformer 120 24 1006 43VA 50172 1 1 1 1 1 1 23 REF GB250 GB250 GB250 GB250 GB250 GB...

Page 24: ...24 29 33 17 15 14 13 18 19 25 27 10 6 7 4 3 11 31 30 5 2 28 32 1 JACKET ASSEMBLY 34 16 26 9 23 24 22 ...

Page 25: ...ce venting system pipes or chimney escaping into the living space Flames coming out around the appliance Yellow colored flames in the appliance Stale or smelly air The presence of soot or carbon in or around the appliance Very high unexplained humidity inside the building If any of the symptoms CO poisoning occur or if any of the signs of carbon monoxide are present vacate the premises immediately...

Page 26: ...26 ...

Page 27: ...27 ...

Page 28: ...WESTCAST INC 260 NORTH ELM STREET WESTFIELD MA 01085 TEL 413 562 9631 FAX 413 562 3799 www smithboiler com ...

Reviews: