Riello ProtoNode Start-up Guide
Page 24 of 43
8
LONWORKS (FPC-N39): COMMISSIONING PROTONODE ON A LONWORKS
NETWORK
Commissioning may only be performed by the LonWorks administrator.
8.1 Commissioning ProtoNode FPC-N39 on a LonW orks Network
During the commissioning process, the LonWorks Administrator will prompt the User to hit the
Service Pin on the ProtoNode FPC-N39 at a specific point (this step occurs at different points of the
commissioning process for each LonWorks Network Management Tool).
If an XIF file is required, see steps in
Section
8.1.1 Instructions to Download XIF File from ProtoNode FPC -N39 Using Browser
Connect a CAT5 Ethernet cable (Straight through or Cross-Over) between the PC and
ProtoNode.
The Default IP Address of ProtoNode is
192.168.1.24
, Subnet Mask is
255.255.255.0
. If the PC
and ProtoNode are on different IP Networks, assign a static IP Address to the PC on the
192.168.1.xxx network.
For Windows XP:
Go to
>
>
Right-click on Local Area Connection > Properties
Highlight
>
For Windows 7 or later:
Go to
>
>
>
>
Right-click on Local Area Connection > Properties
Highlight
>
Figure 21: LonWorks Service Pin Location