QuickServer Start-Up Guide
Page 41 of 43
Appendix C.3. Compliance with UL Regulations
For UL compliance, the following instructions must be met when operating QuickServer.
•
The units shall be powered by listed LPS or Class 2 power supply suited to the expected
operating temperature range.
•
The interconnecting power connector and power cable shall:
o
Comply with local electrical code
o
Be suited to the expected operating temperature range
o
Meet the current and voltage rating for QuickServer/Net
•
Furthermore, the interconnecting power cable shall:
o
Be of length not exceeding 3.05m (118.3”)
o
Be constructed of materials rated VW-1, FT-1 or better
•
If the unit is to be installed in an operating environment with a temperature above 65 °C, it should
be installed in a Restricted Access Area requiring a key or a special tool to gain access.
•
This device must not be connected to a LAN segment with outdoor wiring.
Appendix C.4. Dimension Drawing FS-QS-2XX0-XXXX
R1 Serial Port
Power Port
R2 Serial Port
Figure 33: QuickServer Dimension Drawing